6.3.7.1. Freeze Limits
This setting controls the temperature level to which the loop liquid can drop before
the Geo HP unit will stop operating. See the Geo HP Installation Instructions for
more details. Typically, 26F is chosen for open--loop systems using untreated water;
and 15F is chosen for closed--loop systems using glycol or other anti--freeze
solutions. After the selection is made, touch
SAVE
.
S
Freeze Limits:
26F or 15F
d
Default = 26F
A150179
6.3.7.2. Lockout Count
This setting controls the number of times within an hour that the HPS or LPS trips
before the Geo HP compressor will lockout for four hours. After the selection is
made, touch
SAVE
.
S
Lockout Count:
4 or 2
d
Default = 2