background image

6

Cooling:

AUTO -- the ventilator selects the speed based on indoor humidity

and outdoor temperature. It may cycle on/off every 30 minutes
depending on humidity and outside temperature.
LOW -- low speed all of the time.
HIGH -- high speed all of the time.
If the fan speed is set to Auto and the ventilator wants to run, the
fan speed will run at High continuous speed. Otherwise, the fan

will stay at the chosen continuous fan speed.

Wiring

Remove top cover assembly from wall control and pass thermostat
wire through hole located on back of control before attaching to

wall. Connect Y, R, G, and B (yellow, red, green and black)
between wall control and HRV circuit board. Following color code

(see Fig. 7 and Fig. 8). Replace top cover assembly.

NOTE

: HRV wall control and circuit board operate on 12vdc.

YELLOW

Y

R

GB

RED

GREEN

BLACK

A98383

Fig. 7 -- Typical Wall Control

% D’HUMIDITE RELATIVE HUMIDITY

% HUM. RELATIVE HUM.

55%
45%
35%
30%

EXT. TEMP. EXT.

MODE

MAINTENANCE

AIR EXCHANGE

ECHANGE D’AIR

20

25

30

40

50

60

70

80

10

o

C/50

o

F

0

o

C/32

o

F

–10

o

C/14

o

F

–20

o

C/– 4

o

F

CONTROL

CONNECTOR

WALL CONTROL

YELLOW

RED

GREEN

BLACK

A98410

Fig. 8 -- Control Connections

Humidity Selector

The humidity selector is a built--in dehumidistat designed to
properly control the level of humidity in the house during the

winter months. This control helps avoid condensation problems in
upper northern regions where indoor humidity is a problem during

the winter season.

NOTE

: This control is not to be confused with a dehumidistat

used during the summer months to control high relative indoor
humidity.

Table 5 recommends humidity levels to avoid condensation.

Table 5 – Recommended Humidity Levels

OUTSIDE

TEMPERATURE

DOUBLE---PANE

WINDOWS

TRIPLE---PANE

WINDOWS

50

°

F / 10

°

C

55%

65%

32

°

F / 0

°

C

45%

55%

14

°

F / ---10

°

C

35%

45%

---4

°

F / ---20

°

C

30%

45%

---22

°

F / ---30

°

C

25%

35%

ELECTRICAL CONNECTIONS

115--VAC Wiring

The HRV operates on 115VAC. It comes with a power cord
attached to unit and ready to plug into a fused outlet. Unit must be

grounded for proper operation.
All electrical connections must comply with National and Local
Electrical Codes, or other ordinances that might apply.

ELECTRICAL SHOCK / FIRE HAZARD

Failure to follow this warning could result in property or unit

damage.
Do not use an extension cord as a power source for operating

the HRV.

!

WARNING

12--vdc Wiring

The HRV circuit board, wall control, and accessories operate on
12vdc. See Wall Control section, item Wiring and Fig. 7 and Fig. 8

for more information.

ACCESSORIES

NOTE

: Interlock relay is now integrated into the control.

The purpose of interlock relay is to energize indoor system
equipment (furnace or fan coil) blower whenever HRV is calling. If

HRV is energized, and indoor system equipment is not, interlock
relay will energize and make R and G at indoor equipment. This

will ensure fresh air distribution throughout the building via the
central duct system.

20 Minute Timer

A push button timer can be used to override the wall control and

put the HRV into high speed for 20 minutes. Connect switches in
parallel and connect leads to HRV terminals I, OC, and OL (see

Fig. 8). Push button locations are ideal in special activity areas,
such as, bathroom, or kitchen, where high--speed exhaust operation

is needed for a short period of time.

NOTE

: The 20 minute timer will not function properly unless

HRV wall control is applied and working correctly. Timing
function is internal to electronic circuit board, it is activated by a
momentary contact between OC and OL. The I connection is to
illuminate the push button. The maximum number of push button
timers that can be applied is 5.

60 Minute Adjustable Timer

A 60 minute adjustable timer can also be used to override wall
control and put HRV into high--speed operation for a select amount

of time. Connect timer in parallel with push button timers, or to
HRV terminals OC and OL (see Fig. 8).
The 60 minute timer will provide a minimum of 10 minutes, and a

maximum of 60 minutes of ventilation at high speed.

Summary of Contents for HRVXXLVU

Page 1: ...alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...turn air duct of forced air system 13 Terminal connector block for wiring wall and timer con trols 14 Electrical cord connects to standard 115V outlet Select Location The HRV should be located in a co...

Page 3: ...il This connection should be direct see Fig 4 This is to allow incoming fresh air to mix before entering indoor equipment Connect Ducts to HRV PROPERTY DAMAGE HAZARD Failure to follow this caution may...

Page 4: ...ere are three selections High Low Intermittent The power indicator light indicates which mode has been selected See Table 2 Table 2 OneTouch Push Button Control MODE OPERATION DAMPER POSITION FAN SPEE...

Page 5: ...ecirculates indoor air The exchange LED goes off 5 The maintenance light illuminates every 3 months to indic ate filter should be cleaned It is reset by opening the door to the HRV NOTE The standard a...

Page 6: ...power cord attached to unit and ready to plug into a fused outlet Unit must be grounded for proper operation All electrical connections must comply with National and Local Electrical Codes or other o...

Page 7: ...s should be tightly closed No exhaust systems such as range top exhausts dryer exhaust fume hoods bath or roof fans should be in operation The forced air furnace if used for circulation should be oper...

Page 8: ...ined use Product Data Sheets to reference unit airflow delivery and performance The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required T...

Page 9: ...dels 10 30 10 20 10 15 LINE VOLTAGE CLASS 2 LOW VOLTAGE AND FIELD WIRING F Door interlock switch J1 3 120V 60Hz LINE NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 FAN MOTOR 2 IS USED ONLY WI...

Page 10: ...on K2 relay and opens outdoor air damper 120VAC is applied between Red and Gray wires on Molex plug pins 1 and 4 and blower motor runs in low speed operation CARE AND MAINTENANCE ELECTRICAL SHOCK HAZA...

Page 11: ...its equipped with manual switch such as the new horizontal units Also configuration jumpers located on control board must match configuration setup shown on Fig 14 under Jumper Table In addition outsi...

Page 12: ...ctuator may be defective S Feed 120 V directly to the damper actuator If the problem persists replace the damper actuator S The circuit board may be defective S Replace the circuit board if the proble...

Page 13: ...Orange Orange High No Connection No Connection Blue Cap Medium J1 4 Red Red Low Table 9 Modify Blower Connection High or Medium Speed CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED J1...

Page 14: ...signaled by the wall control automatic wall control only In case of error indicators on wall control will flash When error occurs set dehumidistat at 80 position This will enable you to properly trou...

Reviews: