background image

3

A12454

Fig. 4 -- Exhaust Ventilation

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury

or death.
Do not install return--air registers (or stale--air pickup

registers) in same room as gas furnace or water heater.

!

WARNING

Fresh--air registers are normally located in bedrooms, dining room,

living room, and basement. It is recommended that registers be
placed 6 to 12 in. (152 to 305 mm) from the ceiling on an interior

wall and airflow directed toward ceiling. If registers are floor
installed, airflow should be directed toward the wall.
Return--air (or stale--air pickup registers) are normally located to
draw from kitchen, bathroom, basement, or other rooms where

stale--air can exist.
Proper size and type of registers must be used to minimize pressure
drop. The velocity of airflow through register should not be above

400 ft/minute.
Maximum length of duct for the system should be designed

according to the highest speed of the unit. Refer to specifications

listed in unit Product Data for ventilation capacities.

Forced--Air Application

Most HRV applications will be installed in conjunction with new

or existing forced--air system. To operate properly, the fresh--air
supply and stale--air return from HRV connect directly to return--air

duct system. This is how the HRV distributes fresh air and removes

stale air from inside of building (see Fig. 4). For these installations,
furnace or fan coil blower must be interlocked and operate

continuously whenever HRV is energized.
Interlock relay is now integrated into the control and is designed to

interlock HRV with indoor equipment blower. When HRV is
energized, R and G circuit inside of furnace or fan coil will

energize.

NOTE

: The fresh air from HRV is introduced into return--air duct

at a point no less than 10 ft (3m) upstream of furnace or fan coil.
This connection should be direct (see Fig. 4). This is to allow
incoming fresh--air to mix before entering indoor equipment.

Connect Ducts to HRV

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in minor property

damage from sweating duct or loss of unit efficiency and

capacity.
If HRV duct work is installed in an unconditioned space,

insulated flexible duct is required.

CAUTION

!

Insulated flexible duct is required on both fresh--air inlet and

exhaust--air outlet ducts connecting to exterior wall.

When

using insulated flexible duct, the vapor barrier of the flexible ducts
must be taped very tight to prevent condensation problems. To

reduce pressure drop, stretch the flex duct and support it in a proper
manner to avoid reduced airflow.
When connecting the HRV to a return--air duct system, insulated

flexible duct can be used. However, when metal or rigid ducts are
applied use approximately 18--in. (457 mm) of flexible duct at

HRV ports for fresh--air supply, and stale--air return. When using
metal duct from fresh--air supply to system duct work, the metal

duct should be insulated. This can act as a silencer when

connecting ducts to return--air duct system. This should eliminate
transmission of noise or vibration from unit to main duct system.

NOTE

: Balancing dampers should be installed in stale--air exhaust

and fresh air intake ducts before connecting to the HRVXXLVU
units. Make sure both balancing dampers are left in fully open
position before connecting the ducts to these ports. See Integrated
balancing damper illustration.

Condensate Drain

To connect condensate drain, proceed as follows:

1. Insert sleeved grommets into bottom of unit using the gas-

ket washer and nut (see Fig. 5).

2. Cut two sections of plastic tubing, about 12--in. (305 mm)

long and attach them to each drain.

3. Join the two short sections of plastic tubing to the “T” con-

nector and the main tube as shown.

4. Make a loop in the tubing below the “T” connector to create

a trap to prevent sewer gases from entering the ventilation
system (see Fig. 5).

Summary of Contents for HRVXXLVU

Page 1: ...alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...turn air duct of forced air system 13 Terminal connector block for wiring wall and timer con trols 14 Electrical cord connects to standard 115V outlet Select Location The HRV should be located in a co...

Page 3: ...il This connection should be direct see Fig 4 This is to allow incoming fresh air to mix before entering indoor equipment Connect Ducts to HRV PROPERTY DAMAGE HAZARD Failure to follow this caution may...

Page 4: ...ere are three selections High Low Intermittent The power indicator light indicates which mode has been selected See Table 2 Table 2 OneTouch Push Button Control MODE OPERATION DAMPER POSITION FAN SPEE...

Page 5: ...ecirculates indoor air The exchange LED goes off 5 The maintenance light illuminates every 3 months to indic ate filter should be cleaned It is reset by opening the door to the HRV NOTE The standard a...

Page 6: ...power cord attached to unit and ready to plug into a fused outlet Unit must be grounded for proper operation All electrical connections must comply with National and Local Electrical Codes or other o...

Page 7: ...s should be tightly closed No exhaust systems such as range top exhausts dryer exhaust fume hoods bath or roof fans should be in operation The forced air furnace if used for circulation should be oper...

Page 8: ...ined use Product Data Sheets to reference unit airflow delivery and performance The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required T...

Page 9: ...dels 10 30 10 20 10 15 LINE VOLTAGE CLASS 2 LOW VOLTAGE AND FIELD WIRING F Door interlock switch J1 3 120V 60Hz LINE NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 FAN MOTOR 2 IS USED ONLY WI...

Page 10: ...on K2 relay and opens outdoor air damper 120VAC is applied between Red and Gray wires on Molex plug pins 1 and 4 and blower motor runs in low speed operation CARE AND MAINTENANCE ELECTRICAL SHOCK HAZA...

Page 11: ...its equipped with manual switch such as the new horizontal units Also configuration jumpers located on control board must match configuration setup shown on Fig 14 under Jumper Table In addition outsi...

Page 12: ...ctuator may be defective S Feed 120 V directly to the damper actuator If the problem persists replace the damper actuator S The circuit board may be defective S Replace the circuit board if the proble...

Page 13: ...Orange Orange High No Connection No Connection Blue Cap Medium J1 4 Red Red Low Table 9 Modify Blower Connection High or Medium Speed CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED J1...

Page 14: ...signaled by the wall control automatic wall control only In case of error indicators on wall control will flash When error occurs set dehumidistat at 80 position This will enable you to properly trou...

Reviews: