background image

10

CONTROL BOARD OPERATION

Board Function

NOTE

:

To ensure proper operation of HRV, configuration

jumpers are located on electronic control board and must match
configuration setup shown on Fig. 14 under Jumper Table.
Jumpers are factory set and do not require any changes unless
control board is replaced. If control board is replaced, or you

encounter unusual start--up operation, check jumpers to make sure
they are located properly (see Fig. 14).

Defrost

The HRV continually monitors the outside air temperature. If the

outside air is at or below 23

°

F (--5

°

C), the HRV will initiate a

defrost cycle by closing the outside air damper and recirculating

warm indoor air through the heat recovery core. This happens
every 32 min. with 6 minute defrost cycle. During this process,

core is defrosted without the use of electric strip heat. At 5

°

F

(--15

°

C), unit will defrost for 6 minutes every 32 min. At --17

°

F

(--27

°

C), the unit will sense a need to defrost every 20 minutes with

a 6 minute cycle. See the Troubleshooting section for a control
logic explanation. See Fig. 15.

STALE AIR
FROM BUILDING

FILTERED AIR
TO BUILDING

A92385

Fig. 15 -- HRVXXLVU Airflow During

Recirculation and Defrost

Off and Intermittent/Off Mode

When HRV is Off, K1 relay is open, and K5 relay is energized
which closes outside air damper (see Logic Diagram in Fig. 14).

High--Speed Air Exchange

When high--speed air exchange occurs, K1 and K2 relays are
energized and K5 relay is de--energized. This opens low--speed

contacts, and closes high--speed contact on K2 relay. This also

opens contact on K5 relay which opens outside air damper. Then,
115VAC is applied between orange and gray wires on Molex plug

(pins 1 and 6) and blower motor runs in high--speed operation (see
Logic Diagram in Fig. 14).

Low--Speed Air Exchange

When low--speed air exchange occurs, K1 Relay is energized

which closes the contacts. K2 and K5 relays are de--energized. This
keeps low--speed contacts closed and high--speed contacts open on

K2 relay, and opens outdoor air damper. 120VAC is applied
between Red and Gray wires on Molex plug (pins 1 and 4) and

blower motor runs in low--speed operation.

CARE AND MAINTENANCE

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off, tag and

lockout main power to system. There may be more than 1

disconnect switch.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing and gloves when

handling parts.

CAUTION

!

Door

HRV door can be removed by unlatching brief case style latches,

then slide door to the right and remove it from hinges. Door must
be in place and secured shut for proper operation.

Filter

Filters in HRV are washable and should be cleaned every 3
months. Use a vacuum cleaner to remove heaviest portion of

accumulated dust, then wash in lukewarm water. Allow filter to

completely dry before reinstalling. A dirty air filter will cause
excessive strain on blower motor. Never operate unit without a

filter. Vacuum out debris.
In addition, regularly check and clean screens on exterior intake

and exhaust hoods when necessary.

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in unit component

damage.
DO NOT clean filters in a dishwasher and DO NOT dry them

with a heating appliance or permanent damage will result.

CAUTION

!

Blower Motor and Wheel

HRV blower motors are factory lubricated for life. Lubricating

bearings is not recommended. However, inspect and clean any
accumulated dirt and grease from blower motor and wheel

annually.

Cleaning the Core

HRV unit is equipped with special heat recovery core and must be
handled with care. We recommend that it be washed once a year

following the season of most intense use. This will ensure
maximum efficiency of the plastic partitions within the core.
Allow heat recovery core to soak for 3 hours in a solution of warm

water and mild soap. Rinse under stream of water. Hot water and
strong detergent will damage core and should NOT be used.

Summary of Contents for HRVXXLVU

Page 1: ...alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...turn air duct of forced air system 13 Terminal connector block for wiring wall and timer con trols 14 Electrical cord connects to standard 115V outlet Select Location The HRV should be located in a co...

Page 3: ...il This connection should be direct see Fig 4 This is to allow incoming fresh air to mix before entering indoor equipment Connect Ducts to HRV PROPERTY DAMAGE HAZARD Failure to follow this caution may...

Page 4: ...ere are three selections High Low Intermittent The power indicator light indicates which mode has been selected See Table 2 Table 2 OneTouch Push Button Control MODE OPERATION DAMPER POSITION FAN SPEE...

Page 5: ...ecirculates indoor air The exchange LED goes off 5 The maintenance light illuminates every 3 months to indic ate filter should be cleaned It is reset by opening the door to the HRV NOTE The standard a...

Page 6: ...power cord attached to unit and ready to plug into a fused outlet Unit must be grounded for proper operation All electrical connections must comply with National and Local Electrical Codes or other o...

Page 7: ...s should be tightly closed No exhaust systems such as range top exhausts dryer exhaust fume hoods bath or roof fans should be in operation The forced air furnace if used for circulation should be oper...

Page 8: ...ined use Product Data Sheets to reference unit airflow delivery and performance The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required T...

Page 9: ...dels 10 30 10 20 10 15 LINE VOLTAGE CLASS 2 LOW VOLTAGE AND FIELD WIRING F Door interlock switch J1 3 120V 60Hz LINE NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 FAN MOTOR 2 IS USED ONLY WI...

Page 10: ...on K2 relay and opens outdoor air damper 120VAC is applied between Red and Gray wires on Molex plug pins 1 and 4 and blower motor runs in low speed operation CARE AND MAINTENANCE ELECTRICAL SHOCK HAZA...

Page 11: ...its equipped with manual switch such as the new horizontal units Also configuration jumpers located on control board must match configuration setup shown on Fig 14 under Jumper Table In addition outsi...

Page 12: ...ctuator may be defective S Feed 120 V directly to the damper actuator If the problem persists replace the damper actuator S The circuit board may be defective S Replace the circuit board if the proble...

Page 13: ...Orange Orange High No Connection No Connection Blue Cap Medium J1 4 Red Red Low Table 9 Modify Blower Connection High or Medium Speed CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED J1...

Page 14: ...signaled by the wall control automatic wall control only In case of error indicators on wall control will flash When error occurs set dehumidistat at 80 position This will enable you to properly trou...

Reviews: