![Carrier HRVXXLVU Installation Instructions Manual Download Page 10](http://html1.mh-extra.com/html/carrier/hrvxxlvu/hrvxxlvu_installation-instructions-manual_2563549010.webp)
10
CONTROL BOARD OPERATION
Board Function
NOTE
:
To ensure proper operation of HRV, configuration
jumpers are located on electronic control board and must match
configuration setup shown on Fig. 14 under Jumper Table.
Jumpers are factory set and do not require any changes unless
control board is replaced. If control board is replaced, or you
encounter unusual start--up operation, check jumpers to make sure
they are located properly (see Fig. 14).
Defrost
The HRV continually monitors the outside air temperature. If the
outside air is at or below 23
°
F (--5
°
C), the HRV will initiate a
defrost cycle by closing the outside air damper and recirculating
warm indoor air through the heat recovery core. This happens
every 32 min. with 6 minute defrost cycle. During this process,
core is defrosted without the use of electric strip heat. At 5
°
F
(--15
°
C), unit will defrost for 6 minutes every 32 min. At --17
°
F
(--27
°
C), the unit will sense a need to defrost every 20 minutes with
a 6 minute cycle. See the Troubleshooting section for a control
logic explanation. See Fig. 15.
STALE AIR
FROM BUILDING
FILTERED AIR
TO BUILDING
A92385
Fig. 15 -- HRVXXLVU Airflow During
Recirculation and Defrost
Off and Intermittent/Off Mode
When HRV is Off, K1 relay is open, and K5 relay is energized
which closes outside air damper (see Logic Diagram in Fig. 14).
High--Speed Air Exchange
When high--speed air exchange occurs, K1 and K2 relays are
energized and K5 relay is de--energized. This opens low--speed
contacts, and closes high--speed contact on K2 relay. This also
opens contact on K5 relay which opens outside air damper. Then,
115VAC is applied between orange and gray wires on Molex plug
(pins 1 and 6) and blower motor runs in high--speed operation (see
Logic Diagram in Fig. 14).
Low--Speed Air Exchange
When low--speed air exchange occurs, K1 Relay is energized
which closes the contacts. K2 and K5 relays are de--energized. This
keeps low--speed contacts closed and high--speed contacts open on
K2 relay, and opens outdoor air damper. 120VAC is applied
between Red and Gray wires on Molex plug (pins 1 and 4) and
blower motor runs in low--speed operation.
CARE AND MAINTENANCE
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing or servicing system, always turn off, tag and
lockout main power to system. There may be more than 1
disconnect switch.
!
WARNING
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.
CAUTION
!
Door
HRV door can be removed by unlatching brief case style latches,
then slide door to the right and remove it from hinges. Door must
be in place and secured shut for proper operation.
Filter
Filters in HRV are washable and should be cleaned every 3
months. Use a vacuum cleaner to remove heaviest portion of
accumulated dust, then wash in lukewarm water. Allow filter to
completely dry before reinstalling. A dirty air filter will cause
excessive strain on blower motor. Never operate unit without a
filter. Vacuum out debris.
In addition, regularly check and clean screens on exterior intake
and exhaust hoods when necessary.
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
DO NOT clean filters in a dishwasher and DO NOT dry them
with a heating appliance or permanent damage will result.
CAUTION
!
Blower Motor and Wheel
HRV blower motors are factory lubricated for life. Lubricating
bearings is not recommended. However, inspect and clean any
accumulated dirt and grease from blower motor and wheel
annually.
Cleaning the Core
HRV unit is equipped with special heat recovery core and must be
handled with care. We recommend that it be washed once a year
following the season of most intense use. This will ensure
maximum efficiency of the plastic partitions within the core.
Allow heat recovery core to soak for 3 hours in a solution of warm
water and mild soap. Rinse under stream of water. Hot water and
strong detergent will damage core and should NOT be used.