background image

5

Table 3 – Standard Control

MODE

DEHUMIDISTAT

POSITION

OPERATION

DAMPER

POSITION

FAN SPEED

ON LED

AIR EXCHANGE

LED

Off

Any

Off

Closed to outside

Off

Off

Off

Low

Satisfied

Air exchange with outside Open to outside

Low

On

On

Call for dehumidification

High

On

Intermittent

Satisfied

Off

Closed to outside

Off

Off

Call for dehumidification Air exchange with outside Open to outside

High

On

Table 4 – Automatic Control

MODE

DEHUMIDISTAT

POSITION

OPERATION

DAMPER

POSITION

FAN

SPEED

INDICATOR LEDs

Off

Any

Off

Closed to outside

Off

Off

Intermittent

Satisfied

Off

Closed to outside

Off

Intermittent ON

Call for dehumidification

Air exchange with outside

Open to outside

High

Intermittent and Exchange ON

Continuous

Satisfied

Low

Continuous and Exchange ON

Call for dehumidification

High

Recirculation

Satisfied

Recirculation

Closed to outside

High

Recirculation ON

Call for dehumidification

Air exchange with outside

Open to outside

High

Recirculation and Exchange ON

Maintenance

(open door)

Any

Off

Closed to outside

Off

Maintenance

NOTE

:

This control is designed to be used primarily with

installations which are independent of a forced air system.

1. Initially the switch is off. All LEDs are off and HRV is in-

operative

2. First push of mode button puts HRV into intermittent mode.

The HRV operates at high speed when there is a call for de-
humidification. Intermittent and exchange LEDs are illu-
minated. When dehumidistat is satisfied, HRV shuts down

and exchange LED goes out.

3. Next push of mode button puts system in continuous mode.

Continuous and exchange LEDs remain on. The HRV oper-
ates at high--speed blower during calls for dehumidification

and low--speed when dehumidistat is satisfied.

4. Next push of mode button and exchange puts system in cir-

culation mode. HRV operates in high speed at all times. Cir-

culation LED remains on. When there is a call for dehumid-
ification, exchange LED is on and HRV exchanges air with

outside. When dehumidistat is satisfied, HRV dampers close
which recirculates indoor air. The exchange LED goes off.

5. The maintenance light illuminates every 3 months to indic-

ate filter should be cleaned. It is reset by opening the door to
the HRV.

NOTE

: The standard and automatic controls sense humidity not

temperature. Either control must be located in an area where it will
continually monitor fresh air circulating within the home. Install
HRV wall control as close as possible to main system thermostat
and follow same guidelines as installing a thermostat, (locate
approximately 5 ft. (1.5 m) above floor, mount on an inside
partitioning wall, etc.).

NOTE

: The HRV may be controlled using the Infinity System

Control. The HRV may be connected using either a NIM or a
4--Zone Damper Module. See the appropriate instructions if using
the NIM of a 4--Zone Damper Module for connection instructions.
Blower interlock relay is not needed for use with the Infinity

system control. The Infinity System Control will simultaneously

control the HRV and the indoor blower.
Push Button Timers may be used and are connected to the HRV as

shown in Fig. 6. However, the Infinity system should be set to
continuous fan to ensure that the fresh air is circulated in the home.

In a Zoned System, at least one zone should be set to continuous
fan.

3

4

5

I

OC

OL

YELLOW

BLACK

RED

ELECTRONIC CONTROL

BOARD

BACK OF PUSH BUTTON SWITCH

J3

J1

6

7

8

9

4

1

7

5

2

8

6

3

9

BLACK – (J3- 4)

COMMON

TERMINAL

STRIP

YELLOW – (J3- 3)

INDICATOR

TERMINAL STRIP

RED – (J3- 5)

SWITCH

TERMINAL STRIP

BLACK –

COMMON, (J3--4)

YELLOW –

INDICATOR, (J3--3)

THE WIRES FROM THE SWITCH

RED –

SWITCH, (J3--5)

(OC)

(I)

(OL)

(OPTIONAL)

60 MINUTE TIMER

(OPTIONAL)

PUSH BUTTON SWITCHES

(5 SWITCHES MAXIMUM)

A98386

Fig. 6 -- Push Button Timer Wiring Layout

OPERATING THE HRV WITH THE

INFINITY AND EVOLUTION CONTROL

The ventilator has four settings in heating mode and three settings

in cooling mode.

Heating:

AUTO -- the ventilator selects the speed based on indoor humidity
and outdoor temperature. It may cycle on/off every 30 minutes

depending on humidity and outside temperature.
LOW -- low speed all of the time.
HIGH -- high speed all of the time.
DEHUM -- will only turn on if humidity is 3% over setpoint. The
speed is determined by indoor humidity and outdoor temperature.

Summary of Contents for HRVXXLVU

Page 1: ...alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...turn air duct of forced air system 13 Terminal connector block for wiring wall and timer con trols 14 Electrical cord connects to standard 115V outlet Select Location The HRV should be located in a co...

Page 3: ...il This connection should be direct see Fig 4 This is to allow incoming fresh air to mix before entering indoor equipment Connect Ducts to HRV PROPERTY DAMAGE HAZARD Failure to follow this caution may...

Page 4: ...ere are three selections High Low Intermittent The power indicator light indicates which mode has been selected See Table 2 Table 2 OneTouch Push Button Control MODE OPERATION DAMPER POSITION FAN SPEE...

Page 5: ...ecirculates indoor air The exchange LED goes off 5 The maintenance light illuminates every 3 months to indic ate filter should be cleaned It is reset by opening the door to the HRV NOTE The standard a...

Page 6: ...power cord attached to unit and ready to plug into a fused outlet Unit must be grounded for proper operation All electrical connections must comply with National and Local Electrical Codes or other o...

Page 7: ...s should be tightly closed No exhaust systems such as range top exhausts dryer exhaust fume hoods bath or roof fans should be in operation The forced air furnace if used for circulation should be oper...

Page 8: ...ined use Product Data Sheets to reference unit airflow delivery and performance The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required T...

Page 9: ...dels 10 30 10 20 10 15 LINE VOLTAGE CLASS 2 LOW VOLTAGE AND FIELD WIRING F Door interlock switch J1 3 120V 60Hz LINE NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 FAN MOTOR 2 IS USED ONLY WI...

Page 10: ...on K2 relay and opens outdoor air damper 120VAC is applied between Red and Gray wires on Molex plug pins 1 and 4 and blower motor runs in low speed operation CARE AND MAINTENANCE ELECTRICAL SHOCK HAZA...

Page 11: ...its equipped with manual switch such as the new horizontal units Also configuration jumpers located on control board must match configuration setup shown on Fig 14 under Jumper Table In addition outsi...

Page 12: ...ctuator may be defective S Feed 120 V directly to the damper actuator If the problem persists replace the damper actuator S The circuit board may be defective S Replace the circuit board if the proble...

Page 13: ...Orange Orange High No Connection No Connection Blue Cap Medium J1 4 Red Red Low Table 9 Modify Blower Connection High or Medium Speed CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED J1...

Page 14: ...signaled by the wall control automatic wall control only In case of error indicators on wall control will flash When error occurs set dehumidistat at 80 position This will enable you to properly trou...

Reviews: