background image

2

COMPONENT DESCRIPTION

The following listed items are components of HRVXXLVU. See
Fig. 1).

12

8

13

14

9

6

3

11

2

1

5

10

4

7

A12505

Fig. 1 -- HRVXXLVU Components

1. Stale--air return from building connected to return--air duct

system.

2. Fresh--air intake connected to outdoor air inlet hood.
3. Exhaust--air connected to outdoor air exhaust hood.
4. Dampers are used to control air exchange with outdoor air

during defrost mode.

5. Mechanical filters trap dust contained in the air.
6. Heat recovery core is either a cross--flow type for compact

models, or a counter--flow type for high--efficiency models.

The core transfers heat between the 2 air streams. See Fig.
2.

Stale air
from building

Fresh air
from outside

Fresh air
to building

Stale air
to outside

A12506

Fig. 2 -- HRVXXLVU Airflow During Air Exchange

7. Blowers bring in fresh--air from outside and exhaust stale--

air to outside.

8. Capacitor required for motor operation.
9. Condensation tray collects condensate from heat recovery

core.

10. Drainage tubes connect to sleeved grommets.
11. Electronic control circuit ensures proper unit operation.
12. Fresh air supply from HRV connect to return--air duct of

forced--air system.

13. Terminal connector block for wiring wall and timer con-

trols.

14. Electrical cord connects to standard 115V outlet.

Select Location

The HRV

should be located in a conditioned space

and in close

proximity to a fused power source. It should be easily accessible

for routine maintenance.
If HRV is installed independent of a forced--air system, unit should

be located near the center of the air distribution system. If HRV is

installed in conjunction with a forced--air system, unit should be
located next to (or close to) the indoor equipment.

UNIT INSTALLATION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not install HRV in a corrosive or contaminated

atmosphere.

CAUTION

!

Mount Unit

The HRV can be suspended from floor joists using chains and 4

springs. Attach metal hanging bracket to all 4 sides of cabinet (see
Fig. 3). Unit should always be installed as level as possible.

 

A05331

Fig. 3 -- Chain Spring Installation

Independent System Application

In the absence of a forced--air system and a typical duct system

layout, the HRV can be applied as an independent or stand alone
unit. To ensure comfort, this type of application involves running

both fresh--air and return--air registers (or stale--air pickup registers)
throughout the home.

Summary of Contents for HRVXXLVU

Page 1: ...alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which wi...

Page 2: ...turn air duct of forced air system 13 Terminal connector block for wiring wall and timer con trols 14 Electrical cord connects to standard 115V outlet Select Location The HRV should be located in a co...

Page 3: ...il This connection should be direct see Fig 4 This is to allow incoming fresh air to mix before entering indoor equipment Connect Ducts to HRV PROPERTY DAMAGE HAZARD Failure to follow this caution may...

Page 4: ...ere are three selections High Low Intermittent The power indicator light indicates which mode has been selected See Table 2 Table 2 OneTouch Push Button Control MODE OPERATION DAMPER POSITION FAN SPEE...

Page 5: ...ecirculates indoor air The exchange LED goes off 5 The maintenance light illuminates every 3 months to indic ate filter should be cleaned It is reset by opening the door to the HRV NOTE The standard a...

Page 6: ...power cord attached to unit and ready to plug into a fused outlet Unit must be grounded for proper operation All electrical connections must comply with National and Local Electrical Codes or other o...

Page 7: ...s should be tightly closed No exhaust systems such as range top exhausts dryer exhaust fume hoods bath or roof fans should be in operation The forced air furnace if used for circulation should be oper...

Page 8: ...ined use Product Data Sheets to reference unit airflow delivery and performance The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required T...

Page 9: ...dels 10 30 10 20 10 15 LINE VOLTAGE CLASS 2 LOW VOLTAGE AND FIELD WIRING F Door interlock switch J1 3 120V 60Hz LINE NOTES 1 CONTROLS AVAILABLE SEE THE INSTRUCTION MANUAL 2 FAN MOTOR 2 IS USED ONLY WI...

Page 10: ...on K2 relay and opens outdoor air damper 120VAC is applied between Red and Gray wires on Molex plug pins 1 and 4 and blower motor runs in low speed operation CARE AND MAINTENANCE ELECTRICAL SHOCK HAZA...

Page 11: ...its equipped with manual switch such as the new horizontal units Also configuration jumpers located on control board must match configuration setup shown on Fig 14 under Jumper Table In addition outsi...

Page 12: ...ctuator may be defective S Feed 120 V directly to the damper actuator If the problem persists replace the damper actuator S The circuit board may be defective S Replace the circuit board if the proble...

Page 13: ...Orange Orange High No Connection No Connection Blue Cap Medium J1 4 Red Red Low Table 9 Modify Blower Connection High or Medium Speed CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED J1...

Page 14: ...signaled by the wall control automatic wall control only In case of error indicators on wall control will flash When error occurs set dehumidistat at 80 position This will enable you to properly trou...

Reviews: