6.3.3
Detector Cable Replacement
1.
Isolate the Detector with the damaged cable.
2.
Remove the cable connector on top of the Detector.
3.
Identify the cable to be removed at the Control Unit
4.
Unscrew the cable connector at the Detector and discard the damaged cable.
5.
Connect the replacement cable to the connector on the Control Unit ensuring it is screwed in place.
6.
Connect the cable connector to the Detector
7.
De-isolate the Detector