EXAMPLE SHEET
Engine
Generator 1
Detector Name
Det. 1
Det. 2
Det. 3
Det. 4
Original
Contamination
Value
3948
3004
3564
2754
Contamination
Low Limit
1974
1502
1782
1377
Date
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
Current
Contamination
Value
15/06/20
3881
2970
3363
2701
22/06/20
3652
2506
3153
2875
29/06/20
3777
2049
2497
2267
06/07/20
3026
1703
2118
1994
06/07/20
After Cleaning
3547
2165
3378
2599
Detector 2 is not withing 20% of the original contamination value after cleaning and should be replaced.