Figure 52
Detector Menu
The display will return to the Detector Status Screen, Figure 51.
the detector Selection Screen, Figure 50.
Repeat setting Detector settings for the number of Detectors connected.
Figure 53
Alarm Levels Saved
to return to Engine Overview screen.
Repeat setting Engine Names & Detector settings for the number of Engines connected.
The OMD Mk7 System should now be setup.
2.10
CONTROL UNIT MODBUS ADDRESSING
When more than one Control Unit is connected on a system, the Modbus address must be set up in each
Control Unit before the system will communicate correctly with a Remote Display Unit.
NOTE: For multiple Control Units per system, each Control Unit must have its own Modbus
address and they must be sequential
All Control Units are configured with a Modbus address 01 (1
st
Control Unit) when shipped.
There are 2 methods to change the Modbus address, the first is via the Membrane (refer Section 2.10.1),
the second is via the USB connection on the PCB (refer Section 2.10.2)
2.10.1
Setting the Modbus address via the Control Unit Membrane
To change the Modbus address via the front Membrane
a)
With no Faults or Alarms on the Control Unit to be addressed, press the Accept button for a
minimum 1sec. (Refer Figure 54)
b)
Then press the Reset button for a minimum of 1sec. (Refer Figure 54)