![Carrier Graviner Mk7 Installation, Operation And Maintenance Manual Download Page 117](http://html.mh-extra.com/html/carrier/graviner-mk7/graviner-mk7_installation-operation-and-maintenance-manual_2563926117.webp)
March 2021
Page 106 of 143
59812-K007 Rev 17
Business Confidential
Figure 160
Pulling Tool
Figure 161
Fan Removal
4.
Examine the 4 off compression springs and the fan retainer plug; replace any bent or damaged items
from the spares.
5.
Remove the fixing screw holding the fan socket to the mounting plate and unplug the fan from the
detector head.
6.
Discard the failed fan and fit a replacement fan in reverse order of disassembly.
7.
Reconnect the detector head to the base and to the Control Unit, ensure that the fault does not
reoccur.
5.2.7
Gain Digipot Read Fault
The gain digipot is a component within a detector used to ensure the correct calibration of the detector.
The digipot value is set during the production of the detector and cannot be changed. The detector
constantly monitors the digipot value to ensure that it has not been corrupted and communicates the
fault to the Control Unit If an error in the value is identified a Gain Digipot Read Fault will be indicated.
To identify which detector is at fault, from the Engine Overview Screen, Figure 148, select the required
engine.
Fan Retaining
Plug
One Fixing
Screw