92
APPENDIX D (cont)
DataPort/DataLink Object Definition (cont)
CCN TABLE NAME
DESCRIPTION
STATUS
UNITS
POINT
FORCIBLE
UNIT_3
MISC INPUTS/OUTPUTS
Fan Relay 1
Fan Relay 2
Fan Relay 3
Fan Relay 4
Fan Relay 5
Fan Relay 6
DEMAND LIMIT
4 to 20 mA Demand Signal
Demand Switch 1
Demand Switch 2
CCN Loadshed Signal
Max Allowable CAP
PUMPS
Cooler Pump Relay
Cooler Pump Flow Switch
Condenser Pump Relay
Condenser Pump Flow Switch
MISCELLANEOUS
Ice Valve
Ice Build Complete
Heat/Cool Switch
Dual Set Point Switch
Cooler Heater
Options Temperature 1
Options Temperature 2
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
nn.n
On/Off
On/Off
Normal/Redline/Shed
0-100
On/Off
On/Off
On/Off
On/Off
On/Off
Yes/No
Heat/Cool
On/Off
On/Off
snnn.n
snnn.n
mA
%
°F
°F
FAN_1
FAN_2
FAN_3
FAN_4
FAN_5
FAN_6
LMT_MA
DMD_SW1
DMD_SW2
DL_STAT
DEM_LIM
COOL_PMP
CFLOW_SW
COND_PMP
DFLOW_SW
ICE_VALVE
ICE_DONE
HC_SW
DUAL
COOL_HTR
OPT_TMP1
OPT_TMP2
N
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
N
N
Y
Y
N
N
N
CCN TABLE NAME
DESCRIPTION
STATUS
DEFAULTS
UNITS
POINT
SETPOINT
COOLING
Cool Set Point 1*
Cool Set Point 2*
Cooling Ramp Loading*
HEATING
Heat Set Point 1*
Heat Set Point 2*
Heating Ramp Loading*
HEAD PRESSURE
Head Pressure Set Point A*
Head Pressure Set Point B*
DEMAND LIMIT
Demand Switch 1 Set Point*
Demand Switch 2 Set Point*
LCW Delta Alarm Limit*
Minute off time*
Motor Temp Set Point*
snnn.n
snnn.n
0.2 to 2.0
snnn.n
snnn.n
0.2 to 2.0
nnn.n
nnn.n
0-100
0-100
2.0 to 60
0 to 15
0.0 to 240.0
44.0
44.0
1.0
100.0
100.0
1.0
100.0
100.0
0
0
60.0
0
185.0
°F
°F
^F
°F
°F
^F
°F
°F
%
%
^F
min
°F
CSP1
CSP2
CRAMP
HSP1
HSP2
HRAMP
HSP_A
HSP_B
dlswsp1
dlswsp2
lcw_lmt
delay
mtr_t_sp
*These values may be modified at any time (Unit On/Off).