Air Cooled chiller with scroll compressors 
 
 

EWAT_B 

 

REV 

00 

Date 

June 2018 

Supersedes  / 

Operating Manual 

D-EOMAC01706-18EN 

Summary of Contents for EWAT_B

Page 1: ...Air Cooled chiller with scroll compressors EWAT_B REV 00 Date June 2018 Supersedes Operating Manual D EOMAC01706 18EN...

Page 2: ...Conservation 18 4 10 1 Demand Limit 18 4 10 2 Setpoint Reset 19 4 10 2 1 Setpoint Reset by OAT A C units only 20 4 10 2 2 Setpoint Reset by External 4 20Ma signal 20 4 10 2 3 Setpoint Reset by DT 21...

Page 3: ...31 5 4 1 Discharge Temperature Sensor fault 31 5 4 2 CxOff OffSuctTempSen Suction Temperature Sensor fault 32 5 4 3 CxOff GasLeakage Gas Leakage fault 32 5 5 Circuit Rapid Stop alarms 32 5 5 1 CxOff C...

Page 4: ...ervice or operate on the unit without having switched off the main switch 1 2 Before switching the unit Before switching on the unit read the following recommendations When all the operations and all...

Page 5: ...ndensing Saturated Refrigerant Temperature DSH Discharge Superheat DT Discharge Temperature E M Energy Meter Module EEWT Evaporator Entering Water Temperature ELWT Evaporator Leaving Water Temperature...

Page 6: ...ows to navigate between lines on a screen page and to increase and decrease changeable values when editing Pushing the wheel acts as an Enter Button and will jump from a link to the next set of parame...

Page 7: ...p phase The controller needs time for starting Flashing Yellow Application not loaded Flashing Yellow Red Fail safe mode in case that the BSP upgrade was interrupted Flashing Red BSP Error software er...

Page 8: ...light emitting diode located below the bell button All viewing and setpoint adjustments available on the unit controller are available on the remote panel Navigation is identical to the unit controlle...

Page 9: ...to click on the value of the quantity to monitor and the following additional screen will become visible Depending on the web browser and its version the trend log feature may not be visible It s req...

Page 10: ...erences about Remote On Off contact Generally this contact is used to bring out from the electrical panel the on off selector Some chiller models can be equipped with additional selectors Q1 Q2 used t...

Page 11: ...programmed up to six time bands with a specific operating mode First operating mode starts at Time 1 ends at Time 2 when will start the second operating mode and so on until the latest Depending on un...

Page 12: ...setpoints need to be defined From main menu with user password press on Setpoint Parameter Range Description Cool LWT 1 Ranges of the Cool Heat Ice setpoint are reported in the IOM of every specific...

Page 13: ...ne of the previous cool mode Cool Cool w Glycol Ice Heat Cool Set in case a dual cool heat mode is required This setting implies an operation with double functioning which is activated through the Coo...

Page 14: ...s limiting the unit capacity as the water temperature is dropping too quickly Capacity Limit Demand limit has been hit Unit capacity will not further increase Current Limit Maximum current has been hi...

Page 15: ...g water temperature setpoint from network Capacity Limit Capacity limitation from network Refer to communication protocol documentation for specific registers addresses and the related read write acce...

Page 16: ...point to stop a compressor Stage Up Delay Minimum time between the compressors startup Stage Down Delay Minimum time between the compressors shutdown Ice Cycle Delay Unit standby period during Ice mod...

Page 17: ...Page View Set Unit Pumps Parameter Range Description Pump Control 1 Only Set to this in case of single pump or twin pump with only 1 operational f e in case of maintenance on 2 2 Only Set to this in...

Page 18: ...mit level is regulated using an external 4 20 mA signal with a linear relationship shown in the picture below A signal of 4 mA indicates the maximum capacity available whereas a signal of 20 mA indica...

Page 19: ...an external signal 4 20mA Setpoint Reset by Evaporator T EWT In order to set the desired setpoint reset strategy go to Main Menu Commission Unit Configuration Options and modify the Setpoint Reset pa...

Page 20: ...ulated applying a correction based on an external 4 20mA signal 4 mA corresponds to 0 C correction i e AS LWT setpoint whereas 20 mA corresponds to a correction of the Max Reset MR quantity i e AS LWT...

Page 21: ...increased if Cooling mode set or decreased if Heating mode is set of a maximum value equal to the Max Reset MR parameter Parameter Default Range Description Actual Reset Actual Reset shows which is th...

Page 22: ...requency Returns the active frequency Parameter Default Range Description Max Reset MR 5 0 C 0 0 C 10 0 C Max Reset setpoint It represents the maximum temperature variation that the selection of the E...

Page 23: ...rent Gateway address PrimDNS xxx xxx xxx xxx The current Primary DNS address ScndDNS xxx xxx xxx xxx The current Secondary DNS address Device POLxxx_xxxxxx The Host Name of the MTIII controller MAC xx...

Page 24: ...Comm Start Off Stop the connection to DoS Start Start the connection to DoS Comm State Connection to DoS is off IPErr Connection to DoS cannot be established Connected Connection to DoS is establishe...

Page 25: ...the heat recovery water temperature HR LWT Heat recovery leaving water temperature HR EWT Heat recovery entering water temperature HR EWT Sp Heat recovery entering water temperature setpoint value HR...

Page 26: ...n the alarm log BadLWTReset String in the alarm snapshot BadLWTReset LWT reset input signal is out of range For this warning out of range is considered to be a signal less than 3mA or more than 21mA C...

Page 27: ...heck flow switch connection and calibration Reset Local HMI Network Auto Reset 5 1 5ExternalEvent External Event This alarm indicates that a device whose operation is linked with this machine is repor...

Page 28: ...ncrease the water flow Inlet temperature to the heat recovery is too low Increase the inlet water temperature Sensors readings entering or leaving are not properly calibrated Check the water temperatu...

Page 29: ...Local HMI Network Auto 5 2 2UnitOffLvgEntWTempSen Evaporator Leaving Water Temperature LWT sensor fault This alarm is generated any time that the input resistance is out of an acceptable range Symptom...

Page 30: ...th this unit operation This external device could be a pump or an inverter Symptom Cause Solution Unit status is Off All circuits are switched off with the normal shutdown procedure Bell icon is movin...

Page 31: ...ater filter is clogged Check flow switch connections Reset Local HMI Network Auto 5 3 5UnitOff EXVDriverComm EXV Driver Extension Communication Error This alarm is generated in case of communication p...

Page 32: ...good connected open Check for correct installation of the sensor on refrigerant circuit pipe Check for absence of water or humidity on sensor electrical contacts Check for correct plug in of the elect...

Page 33: ...not properly connected open Check for correct installation of the sensor on refrigerant circuit pipe The transducer must be able to sense the pressure through the valve s needle Check for absence of w...

Page 34: ...short circuit of the hot air blown from the fans of the same unit or even from fans of next chillers Check IOM for proper installation Entering water temperature at condenser is too high W C units Ch...

Page 35: ...k the low pressure safeties settings Reset Local HMI Network Auto 5 5 6CxOff RestartFault Restart Fault This alarm is generated when the compressor internal protection trips Symptom Cause Solution Com...

Page 36: ...W C units Check the cooling tower operation and settings Check the three way valve operation and settings Mechanical high pressure switch is damaged or not calibrated Check for proper operation of the...

Page 37: ...erly connected Evaporating pressure sensor is not working properly Check for proper operation of evaporating pressure sensor Compressor on circuit is internally damaged with a mechanical problems for...

Page 38: ...se of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe...