36
Table 22 — Service Function and Subfunction Directory (cont)
SUBFUNCTION
KEYPAD ENTRY
DISPLAY
COMMENT
7 Transducer Calibration (cont)
Calibrate All at 0 PSIG
No
Last Calibration Date
mmm-dd-yy
8 Manual Control Table
Manual Control Enable
Dsable
LOR switch should be in OFF position
Password Protected
Enter:
Will be displayed if not entered earlier in HSIO use
Manual Control Enable
Dsable
Manual control must be disabled to resume normal capacity control
Manual Control Enable
Enable
Switch LOR switch to Local before proceeding
Circuit A Compressor 1
Off
Circuit A Compressor 1
On
Provided no alarms exist, control will attempt circuit start within 2 minutes.
Press
to stop circuit.
Circuit A Compressor 2
Off
to enable,
to stop
Circuit A Loader 1
Off
to enable,
to stop
Circuit A Loader 2
Off
to enable,
to stop
Circuit A Min Load Valve
Off
to enable,
to stop
Circuit B Compressor 1
Off
to enable,
to stop
Circuit B Compressor 2
Off
to enable,
to stop
Circuit B Loader 1
Off
to enable,
to stop
Circuit B Loader 2
Off
to enable,
to stop
Circuit B Min Load Valve
Off
to enable,
to stop
9 Dual Chiller Configuration
(Series Water Flow Only)
MST_SLV
Master/Slave Select
0/1/2
0 = Disabled
1 = Master
2 = Slave
Slave Address
0
Default = 0
Adjustable from 0-236
Lead/Lag Balance
0/1
0 = Disabled
1 = Enabled
Lead/Lag Balance Delta
xxx hours
Default = 168
Adjustable from 40-400
LEGEND
CCN
— Carrier Control Network
CHW
— Chilled Water
CPM
— Compressor Protection Module
dF
— Degrees Fahrenheit
HSIO
— Standard Keypad
HTW
— Hot Water
LOR
— Local/Off/Remote
MOP
— Maximum Operating Pressure
OAT
— Outside Air Temperature
PID
— Proportional Integral Derivative