91
APPENDIX D (cont)
DataPort/DataLink Object Definition (cont)
CCN TABLE NAME
DESCRIPTION
STATUS
UNITS
POINT
FORCIBLE
CIRCB_AN
CIRCUIT A ANALOG VALUES
Total Capacity
Available Capacity
Discharge Pressure
Suction Pressure
B1 Oil Pressure Diff.
B2 Oil Pressure Diff.
B1 Oil Pressure
B2 Oil Pressure
Discharge Gas Temperature
B1 Motor Temperature
B2 Motor Temperature
Saturated Condensing Temp
Saturated Suction Temp
EXV Percent Open
Motormaster Speed*
Cooler Level Indicator
CPM B1 Feedback
CPM B2 Feedback
Circuit B ECON Pressure
0-100
0-100
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
0-100
0-100
0-3
0-10
0-10
nnn.n
%
%
PSI
PSI
PSI
PSI
PSI
PSI
°F
°F
°F
°F
°F
%
%
—
Volts
Volts
PSI
CAPB_T
CAPB_A
DP_B
SP_B
DOP_B1
DOP_B2
OP_B1
OP_B2
DISTMP_B
TMTR_B1
TMTR_B2
TMP_SCTB
TMP_SSTB
EXV_B
SPEEDB
LEVEL_B
K_B1_FBK
K_B2_FBK
ECNP_B
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
CIRB_DIO
CIR. B DISCRETE OUTPUTS
Compressor B1
Compressor B2
Loader B1
Loader B2
Min. Load Valve, Valve B
Circuit B Oil Heater
B1 Mtr Cooling Solenoid
B2 Mtr Cooling Solenoid
Circuit B Oil Pump
Oil Solenoid B1
Oil Solenoid B2
CIR B DISCRETE INPUTS
Compressor B1 Feedback
Compressor B2 Feedback
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
K_B1_RLY
K_B2_RLY
LOADR_B1
LOADR_B2
MLV_B
OILB_HTR
MTRCL_B1
MTRCL_B2
OILPMP_B
OILSL_B1
OILSL_B2
K_B1_FBK
K_B2_FBK
N
N
N
N
N
N
N
N
N
N
N
N
N
UNIT_2
UNIT ANALOG PARAMETERS
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Reclaim Entering Fluid
Reclaim Leaving Fluid
5 Volt Supply
TEMPERATURE RESET
4 to 20 mA Reset Signal
Return Reset Signal
External Reset Signal
Outdoor Air Temp
Calculated Reset
snnn.n
snnn.n
snnn.n
snnn.n
snnn.n
snnn.n
sn.n
nn.n
snnn.n
snnn.n
snnn.n
snnn.n
°F
°F
°F
°F
°F
°F
Volts
mA
^F
°F
°F
^F
COOL_EWT
COOL_LWT
COND_EWT
COND_LWT
HR_EWT
HR_LWT
P_REF
RST_MA
RSTRTN
T_SPACE
OAT
sp_delta
N
N
N
N
N
N
N
N
N
Y
Y
N
*These values may be modified at any time (Unit On/Off).