31
Table 20 — Set Point Function and Subfunction Directory
NOTE: If metric option is selected under
, temperatures are
expressed in degrees Celsius and pressures are expressed in kPa.
SUBFUNCTION
KEYPAD ENTRY
DISPLAY
COMMENT
1 Set Point Table
COOLING
Cool Setpoint 1
x.xx dF
Default: 44.0
Cool Setpoint 2
xx.x dF
Default: 44.0
Cooling Ramp Loading
xx.x dF
Default: 0.5
HEATING
NOT SUPPORTED
Heat Setpoint 1
xx.x dF
NOT SUPPORTED
Default: 98.0
Heat Setpoint 2
xx.x dF
NOT SUPPORTED
Default: 98.0
Heating Ramp Loading
xx.x dF
NOT SUPPORTED
Default: 0.5
HEAD PRESSURE
Head Pressure Setpoint A
xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
Head Pressure Setpoint B
xxx.x dF
Default: 113.0 (GX)
100.0 (HXA) 85.0 (HXC)
DEMAND LIMIT
Demand Switch 1 Setpoint
xxx.x%
Default: 80.0%
Demand Switch 2 Setpoint
xxx.x%
Default: 50.0%
LCW Delta Alarm Limit
xxx.x dF
Default: 50.0 dF
Minutes Off Time
xxx min
Default: 0 min
Motor Temp Set Point
xxx.x dF
Default: 200.0 dF
2 Units
US IMPERIAL/METRIC
0
0 = English (Default)
1 = Metric
3 Address
TARGET ADDRESS
x
Default: 1
TARGET BUS NUMBER
x
Default: 0
4 Time
Day of Week
Monday
Mon=1, Tues=2, etc.
Day of Week
Wednsday
Day of week set
TIME (HOUR/MIN)
00:00
Enter military format
TIME (HOUR/MIN)
10:30
Time of day set
DAY OF MONTH
xx
DAY OF MONTH
20
Day of month set
MONTH OF YEAR
xx
MONTH OF YEAR
05
Month of year set
YEAR OF CENTURY
xx
YEAR OF CENTURY
96
Year of century set
5 CCN Disable
Disable CCN Control
x
0=no, 1=yes
Default: 0
LEGEND
CCN
— Carrier Comfort Network
dF
— Degrees Fahrenheit
LCW — Leaving Chilled Water
ENTER
ENTER
ENTER
ENTER
ENTER