CL-6
REVIEW AND RECORD FACTORY CONFIGURATION CODES,
CONFIGURATION CODE 1: ______________________
CONFIGURATION CODE 2: ______________________
CONFIGURATION CODE 3: ______________________
CONFIGURATION CODE 4: ______________________
CONFIGURATION CODE 5: ______________________
REVIEW AND RECORD SOFTWARE VERSION,
SOFTWARE CESR_500100 VERSION ________________
REVIEW AND RECORD FIELD CONFIGURATION,
COOLER FLUID SELECT ______________________
MIN LOAD VALVE SELECT ____________________
LOADING SEQ. SELECT_______________________
LEAD/LAG SEQ. SELECT ______________________
HEAD PRESSURE CONTROL __________________
MOTORMASTER SELECT _____________________
WATER VALVE TYPE _________________________
EXTERNAL RESET SENSOR ___________________
COOLER PUMP INTERLOCK___________________
COOLER PUMP CONTROL ____________________
CONDENSER PUMP CONTROL ________________
CONDENSER FLOW SWITCH _________________
CONDENSER WATER SENSORS _______________
REVIEW AND RECORD RESET CONFIGURATION,
COOLING RESET TYPE 1
Degrees Reset at 20 mA _______________________
COOLING RESET TYPE 2
Remote Temp (No Reset) ______________________
Remote Temp (Full Reset ______________________
Degrees Reset _______________________________
COOLING RESET TYPE 3
CHW Temp (No Reset) ________________________
CHW Temp (Full Reset) _______________________
Degrees Reset _______________________________
COOLING RESET
Select/Enable Reset Type ______________________
DEMAND LIMIT
Demand Limit at 20 mA ______________________
Loadshed Group Number ______________________
Loadshed Demand Delta ______________________
Maximum Loadshed Time _____________________
WATER VALVE PID
Proportional PID Gain ________________________
Integral PID Gain ____________________________
Derivative PID Gain __________________________
AIR MOTORMASTER PID
Proper Manual PID Gain ______________________
Integral PID Gain ____________________________
Derivative PID Gain __________________________
TO START THE CHILLER:
BE SURE THAT ALL SERVICE VALVES ARE OPEN, AND ALL PUMPS ARE ON BEFORE ATTEMPTING TO START
THIS MACHINE. ONCE ALL CHECKS HAVE BEEN MADE, MOVE THE SWITCH TO “LOCAL” OR “REMOTE” FROM
“OFF.”
UNIT STARTS AND OPERATES PROPERLY.