background image

2

MODE BUTTON — The Mode button selects the operating
mode of the thermostat.

If OFF is selected, the thermostat will not enter Heating
or Cooling mode.

If HEAT is selected, the thermostat will only enter Heat-
ing mode (if the room temperature is below the heating
set point). The thermostat will not provide cooling.

If COOL is selected, the thermostat will only enter Cool-
ing mode (if the room temperature is above the cooling
set point). The thermostat will not provide heating.

If AUTO is selected, the thermostat will enter Heating or
Cooling mode based on the room temperature and the
heating and cooling set points. The thermostat will pro-
vide automatic changeover from Heating to Cooling
mode and Cooling to Heating mode when required. The
thermostat will automatically switch to maintain the
desired temperature setting. The thermostat does not
need to be manually changed from heating or cooling or
cooling to heating operation.

If PROGRAM ON is selected, the thermostat will oper-
ate as in the AUTO mode (see above). PROGRAM ON
enables the thermostat to follow the programmed daily
schedule stored in its memory.

Keypad Lock —

To prevent unauthorized use of the ther-

mostat, the front panel buttons can be disabled. To disable or
lock the keypad, press and hold the Mode button. While hold-
ing down the Mode button, press the UP and DOWN ARROW
buttons simultaneously. The “Locked” icon will appear on the
display.

The thermostat is unlocked by performing the same proce-

dure. Press and hold the Mode button. While holding down the
Mode button, Press the UP and DOWN ARROW buttons
simultaneously. The “Locked” icon will be removed from the
display.

Set Clock —

The Set Clock function allows the user to

change the time and day displayed on the thermostat. Press and
hold the Mode and Override buttons at the same time until the
display changes. The display will show the setup annunciator.
The current time will blink on and off. Press the UP ARROW
or DOWN ARROW button until the correct time is shown.
Hold down the buttons to quickly move through the time dis-
play. The AM and PM annunciators will automatically change.

To scroll through by hours instead of minutes, hold down the
Override button while pressing UP ARROW or DOWN AR-
ROW. To ensure the schedules are properly followed, make
sure that AM or PM is correct for the time chosen. When the
correct time is shown, press the Mode button to modify the day
of the week. The current day will blink on and off. Press the UP
ARROW or DOWN ARROW button until the correct day is
shown. Press and hold the Mode and Override buttons at the
same time again to exit the Set Clock mode.

Program Thermostat Schedules —

Before pro-

gramming the thermostat, plan the thermostat daily schedule.
The schedule is divided into 7 days (Monday through Sunday).
Each day has from 2 to 4 time periods (Occupied 1, Occu-
pied 2, Occupied 3, Unoccupied) depending on the configura-
tion of the thermostat. Each occupied time period has a start
time, stop time, heating set point, and cooling set point. The un-
occupied time period has a heating set point and a cooling set
point. The unoccupied time period is active whenever an occu-
pied time period is not active. Fill in Table 1 as an aid to pro-
gramming the daily schedules.
PROGRAMMING MODE — To program the daily sched-
ules, perform the following procedure:

1. Enter Programming mode by pressing and holding the

Mode and UP ARROW buttons. The Occupied 1
annunciator will appear on the thermostat display. Use
the UP ARROW or DOWN ARROW button to set the
maximum number of Occupied periods for each day.
The thermostat can be set to 1, 2, or 3. After the num-
ber of Occupied periods has been selected, press the
Mode button. See Fig. 3.

2. The cooling set point for Occupied 1 will be displayed.

Use the UP ARROW or DOWN ARROW button to raise
or lower the cooling set point until the desired temperature
is shown. The range of acceptable values is 35 to 99 F
(1 to 37 C). Press the Mode button to continue. See Fig. 3.

3. The heating set point for Occupied 1 will be displayed.

Use the UP ARROW or DOWN ARROW button to raise
or lower the heating set point until the desired temperature
is shown. The range of acceptable values is 35 to 99 F
(1 to 37 C). Press the Mode button to continue. See Fig. 3.

4. The cooling set point for Unoccupied will be displayed.

Use the UP ARROW or DOWN ARROW button to raise
or lower the cooling set point until the desired tempera-
ture is shown. The range of acceptable values is 35 to
99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied cooling). To
configure the Unoccupied Cooling set point to OF, press
the UP ARROW button until 99 F is displayed. Press the
UP ARROW button again to display OF. Press the Mode
button to continue.

5. The heating set point for Unoccupied will be displayed.

Use the UP ARROW or DOWN ARROW button to raise
or lower the heating set point until the desired tempera-
ture is shown. The range of acceptable values is 35 to
99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied heating). To

BACKLIT
LCD DISPLAY

HEAT OR COOL
INDICATOR
(RED=HEAT,
GREEN=COOL)

TEMPERATURE
SENSOR

MODE
BUTTON

OVERRIDE
BUTTON

UP AND DOWN
BUTTONS

Fig. 2 — Thermostat Front Panel

Fig. 3 — Setting Occupied 1 Set Points

105

Summary of Contents for Debonair 33CS220-FS

Page 1: ...e desired set point change the mode program and override the current program See Fig 2 SET POINT BUTTONS The UP ARROW and DOWN ARROW buttons will raise or lower the current desired tem perature set point If the thermostat is in the AUTO or Program mode pressing the UP ARROW or DOWN ARROW button will adjust both the heating and cooling set points Pressing the UP ARROW or DOWN ARROW button in Coolin...

Page 2: ...DOWN ARROW button until the correct day is shown Press and hold the Mode and Override buttons at the same time again to exit the Set Clock mode Program Thermostat Schedules Before pro gramming the thermostat plan the thermostat daily schedule The schedule is divided into 7 days Monday through Sunday Each day has from 2 to 4 time periods Occupied 1 Occu pied 2 Occupied 3 Unoccupied depending on the...

Page 3: ...at day NOTE Occupied 1 schedule heating and cooling set points are the same for each day Occupied 2 and 3 set points may be set to different values for each day of the week If YES was selected the schedule will be copied to the next day The schedule copy may be repeated until Sunday is reached The Sunday schedule cannot be copied to Monday 12 After all the times and set points for each day have be...

Page 4: ...should only be used on electric heat ing applications Do not use with gas heat Holiday Mode When the thermostat is in Holiday mode the thermostat will operate under Unoccupied set points To configure and activate the Holiday mode press the Mode and UP ARROW buttons simultaneously to enter Program ming mode Press the Override button to enter Holiday Pro gramming mode The HOL icon will be displayed ...

Page 5: ...5 ...

Page 6: ...6 ...

Page 7: ......

Page 8: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 353 Printed in U S A Form 33CS 13SO Pg 8 105 11 00 Replaces New Book 1 4 Tab 11a 13a Copyright 2000 Carrier Corporation ...