manualshive.com logo in svg
background image

 

 

 

Page 1 - Set RID, PAN ID and RF Channel in E528.4G and E527.4G

 

Set Room ID, PAN ID and RF Channel in INNCOM 

E528.4G and E527.4G Thermostats 

Enter Service Mode 

 

Service mode is accessed by executing the following button sequence: 

1.

 

Press and 

hold

 F/C.                   

                      

2.

 

Press and release OFF/AUTO. 

   

3.

 

Press and release DISPLAY.  

         

4.

 

Release F/C. 

The LCD display will now read “rid” confirming that you are in service mode. 

    

Set Room ID 

 

A unique 5-digit Room ID is required in each INNCOM thermostat. 

Enter Service Mode and follow the procedure below to set the Room ID of the thermostat. 

1.

 

Scroll to 

rId

 

2.

 

Press 

DISPLAY

 button and the current Room ID will scroll on the display. 

3.

 

After the Room ID scrolls, the highest digit of the Room ID will be displayed with the 

HI

 fan indicator. Use the up or down arrow buttons to change the value and press 

OFF/AUTO

4.

 

The next 2 digits of the Room ID are now displayed along with the 

MED 

fan indicator. 

 Use the up or down arrow buttons to change the value and press 

OFF/AUTO.

 

5.

 

The last 2 digits of the Room ID are now displayed along with the 

LO 

fan indicator 

Use the up or down arrow buttons to change the value and press 

OFF/AUTO

6.

 

Press the 

DISPLAY

 button to store the new Room ID. The new Room ID will scroll 

across the display. 

 

Example of RID for Room 515 (00515) 