manualshive.com logo in svg
background image

HZ322 TrueZONE

Zone Panel Professional Installation Guide

69-2199-01

Содержание HZ322 True ZONE

Страница 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide 69 2199 01 ...

Страница 2: ...Configuration 8 Operation 9 Checkout 9 Warranty 10 Read and save these instructions Need Help For assistance with this product please visit http yourhome honeywell com or call Honeywell Zoning Hotline toll free at 1 800 828 8367 U S Registered Trademark Patents pending Copyright 2008 Honeywell International Inc All rights reserved ...

Страница 3: ...ote All versions of the model numbers listed above will work with the applications they re listed for Wireless adapter also required Table 2 Recommended Dampers Type Honeywell Damper Round Rectangular Zone Spring open power closed ARD ZD Zone Power open power closed MARD RRD For recommended dampers call the Honeywell Zoning Hotline at 1 800 828 8367 Bypass Static pres sure regulat ing damper SPRD ...

Страница 4: ... details 1 2 Separate the zone panel cover from the base and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss or four screws for duct or drywall plaster installations Fig 2 Fig 3 SUPPLY DUCT DATS AT LEAST 3 FT FROM PLENUM DATS ALTERNATE LOCATION TrueZONE P...

Страница 5: ...one panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on top of the terminal In retrofit applications trim end of wire if not straight 3 Install dampers using instructions provided with dampers Connect dampers to zone panel NOTE Multiple dampers can be wired in parallel 4 M28023 Rc R C W W2 Y Y2 G M1 M4 M6 R C W...

Страница 6: ...ect DATS as shown 5 Connect equipment as shown 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect transformer as shown DEDICATED TRANSFORMER R C M24806 R C POWER L1 HOT L2 RH RC W1 E W2 Y1 Y2 G O B DS BK M28025 HVAC FAN RELAY 24 VOLT TRANS G Y Y2 C R W COMPRESSOR RELAY W2 EQUIPMENT Wiring Fig 7 Fig 8 Fig 10 7 If using any wireless device connect the ABCD terminals for the wireless interface module M28...

Страница 7: ... W1 E W2 Y1 Y2 G O B DS BK HZ322 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 2 DAMPER THERMOSTAT SENSOR DATS DATS EQUIPMENT R C POWER M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 3 DAMPER THERMOSTAT A B C D WIRELESS ADAPTER WIRELESS CONNECT POWER THM4000R CONNECTED W...

Страница 8: ...IF HVAC EQUIPMENT USES THE SAME SOURCE OF HEAT FOR AUXILIARY AND EMERGENCY HEAT JUMPER W1 E AND W2 M4 OPEN M6 CLOSED M1 COMMON M28020 R C L1 HOT L2 AIR HANDLER FAN RELAY EM HEAT AUX HEAT G Y 24 VOLT TRANS C R E W2 C7735A1000 DATS HEAT PUMP Y C R DEDICATED TRANSFORMER ARD OR ZD DAMPER SPRING OPEN POWER CLOSED ARD OR ZD DAMPER SPRING OPEN POWER CLOSED RRD OR MARD DAMPER POWER OPEN POWER CLOSED REVER...

Страница 9: ... Back and Next buttons to navigate through the configuration menus Pressing Next enters the selected option for that menu item and advances to the next menu Adjust settings up or down by pressing the Adjust Setting button The flow chart below illustrates basic zone panel configuration For additional configuration see Advanced Configuration on page 8 The label on the inside cover of the HZ322 Zone ...

Страница 10: ...H LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Disabled Enables or disables outdoor temperature sensor If Disabled the Multistage OT Temp Lockout setting is Disabled NO YES Enabled OT Trip Point for Multistage Lockout OT LOCKOUT TEMP 0 F 50 F 50 F 0 deg F 50 de...

Страница 11: ...Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons Steps 3 10 cycle through heating and cooling stages and open and close dampers to verify proper operation Steps 11 14 verify thermostat operation and correct wiring This is done by making the thermostats call for heat or cool and viewing ...

Страница 12: ...r air quality and zoning products with a date code of 0452 or earlier twenty four 24 months from date of installation unless specified other wise Variable frequency drive devices VFD and accessories new products for thirty six 36 months and factory refurbished drives for twelve 12 months from date of installation when start up and commissioning is performed by Honeywell VFD Authorized and trained ...

Отзывы: