4. Inadequate performance

of the unit:

If the unit’s performance is not adequate, and no technical causes or anomalies can

be identified, it is necessary to check that the cell doors are perfectly sealed, that
there are no leaks from the cell, that no foodstuffs or non frozen liquids have been
inserted in the low temperature cell and that no ice has formed on the evaporator.

It is therefore advisable to locate the unit away from doors, especially if these are

opened several times a day.

WARNING:

It absolutely forbidden to remove the safety devices provided by the anufacturer

to protect operators while the machine is in operation.

5. 

Other malfunctions may be due to the triggering of the following electrical

safety devices:

a) Fan thermal protection

(incorporated in the motor) - automatic resetting. This

device is designed to safeguard electrical fans against excessive current absorp-

tion due to:

- overheating
- lack of one phase (only for three phase models)
- dirt in the condenser

- ice in the evaporator

b) Discharge Line Thermostat

Protects the compressor against elevated discharge temperatures which can

typically occur in certain conditions such as low gas charge or failed condenser

fan.

c) High pressure switch

- manual resetting

It is designed to protect the compressor from excessive pressure, which cause

the pressure switch to be triggered too often, deriving from:

- dirt in the condenser
- condenser fans not working
- excessive temperature in the room where the system is located
- use of the system in unsuitable conditions or with inappropriate products.

To reset press the button on the pressure switch.

d) Low pressure switch 

- automatic resetting

It is generally used to stop the unit working in pump-down mode.
The triggering of the pressure switch can also indicate excessively low pressure

in relation to the set points, due to one of the following causes:

- lack of gas due to the breakage of a pipe or to loose hub
- clogged up filters
- solenoid valve failure
- ice in the evaporator 

The minimum and maximum temperature pressure switches and the oil pressure

switch are located inside the motor casing. Before resetting, disconnect from mains.

e) Thermistors

- automatic resetting

These are inserted in the compressor’s coil to protect the motor from overheating

(see electrical diagram)

f) Minimum and maximum tension electronic relay

(Monitor) - automatic reset

(where applicable). It is used to protect the unit against anomalies in the power

supply (+/-12% of nominal value). The unit starts with a delay of 8 minutes, indi-

cated on the panel by a LED.

The main factors that cause the triggering of the device are anomalies in the

power supply (for further information see attachment)

g) Phase sequencing relay 

Is an electronic device which prevents the compressor from starting if the phases

are not connected in the correct sequence. This device can be found either in the

electrical panel or integtrated in the compressor protection module. 

h) Condenser fans variable speed drive

Electronic system for checking the speed of condenser fans. 
In case of system malfunction:

- turn off at mains
- open the electric control panel
- the variable speed drive is located inside the control panel.

Move the switch to position (1)

- close the electric control panel and reset the unit
- replace the variable speed drive as soon as possible
- having replaced it, move the variable speed drive to the automatic 
position (0).

Summary of Contents for DB-S Series

Page 1: ...AN NL LE EI IT TU UN NG G B BE ED DI IE EN NU UN NG GS SA AN NL LE EI IT TU UN NG G I IN NS ST TR RU UC CT TI IO ON NS S D D U US SA AG GE E E ET T E EN NT TR RE ET TI IE EN N I IN NS ST TR RU UC CT T...

Page 2: ...SHEET SERVICEBLATT FICHE DE SERVICE FOGLIO SERVIZIO DATE DATUM OPERATION MASSNAHME SERVICE FIRM SERVICEFIRMA SIGNATURE UNTERSCHRIFT DATE DATA OPERATION OPERAZIONE ETS DE SERVICE DITTA ASSISTENZA SIGNA...

Page 3: ...ng the unit to external power sources page 13 6 2 1 Power mains connection page 13 6 2 2 Water mains connection page 14 6 3 Checks adjustments and settings page 14 7 Placing into service of the unit p...

Page 4: ...unit and a remote control panel This feature permits to overcome the problems due to the lack of space external to the cell which prevent the assembling unit in fact the two parts can be istalled wit...

Page 5: ...mpressor against excessive current absorption 2 High pressure switch with automatic resetting protects against excessively high pressure 3 Thermistors with automatic resetting protects the motor again...

Page 6: ...LINEA PRINCIPALE CONNECTION SHOULD ALWAYS BE MADE FROM A FUSED ISOLATOR NEVER CONNECT THE CABLE TO THE MAINS SUPPLY LINE DIRECTLY LA CONNEXION DOIT ETRE EFFECTUEE AU MOYEN D UN INTERRUPTEUR MAGNETO T...

Page 7: ...rant Massa C Mass C A Kw Kg Via Martin L King nr 30 46020 PEGOGNAGA Mantova Italy ZANOTTI S S p p A A Modello Model Potenza compressore Compressor power A Assorb Max Max Absor Kw Schemi Diagr 1 Anno d...

Page 8: ...led The unit is shipped packed in a wooden case or in a wooden crate the movement has to be done securing the packaging with a sling in an appro priate way Take special care in ensuring that the packi...

Page 9: ...S 5 5 I IN NS ST TA AL LL LA AT TI IO ON N 5 5 I IN NS ST TA AL LL LA AT TI IO ON N fig 5 1 2 Gas 1170 1220 50 520 690 1104 504 N M 12 1 2 Gas E F G C D Delivery pipe Suction pipe Cod MDB235 10 22 BD...

Page 10: ...that the unit is in a horizontal position so that condensation water can easily be drained 1410 840 Mass 98 Kg Mod A B C D E F Kg MDB335NS02F 670 1350 810 830 1840 750 CU 89 EU 56 MDB335TS02F BDB335NS...

Page 11: ...unit making sure it does not interfere with existing cable connections Connect the condensation water drain located in the lower section of the conden ser to the evaporator proceeding as indicated in...

Page 12: ...Put the heater in the drain pipe without fol ding DB models Put the heater in the drain pipe without fol ding DB models Insulate the whole suction line Insulate the whole suction line Discharge resist...

Page 13: ...power supply cable a 110V 230V 1 50 60 Hz 3 wires Blue neutral Yellow Green earth Brown phase b 230V 3 50 60 Hz 4 wires Blue phase Yellow green earth Brown phase Black phase c 400V 3N 50 60 Hz 5 wires...

Page 14: ...ater mains following the indications water mains water condenser on the plates next to the tubes which are marked IN ENTRATA and OUT USCI TA The diameter of the pipes used to make the connection must...

Page 15: ...hours in winter or more then 6 hours in summer it is necessary to repeat the preheating CAUTION 24 hours after start up check the evaporator If ice has formed on it reduce the interval between defrost...

Page 16: ...are intermittently displayed one after the other on the digital display When the machine is in operation during the normal working cycle the display indicates the cell temperature Parameters being se...

Page 17: ...ll be shown on the display 5 In this condition the unit is ready for programming It is necessary the refore to set the required room temperature bearing in mind the limits of the range which the unit...

Page 18: ...anel tamper with safety and protection devices 9 4 Troubleshooting guide Technical problems that may occur during the operation of the machine 1 In case of malfunction of the system check the refriger...

Page 19: ...n the pressure switch d Low pressure switch automatic resetting It is generally used to stop the unit working in pump down mode The triggering of the pressure switch can also indicate excessively low...

Page 20: ...h time the high pressure switch is tripped If the high pressure switch is tripped more than 10 times in a one hour period the label PP and the cell temperature will appear intermittently one after the...

Page 21: ...parately Electrical components such as switches transformers etc must be disassem bled in order to be reused if they are still in good condition or to be reconditioned and recycled where possible Pneu...

Page 22: ...ssociato al parametro 2C Modify the value pressing 8 and 9 until you reach the required one Um den wert zu nderu 8 und 9 bis zum gew wert dr cken Modifier la valeur en pressant ensamble 8 et 9 jusqu o...

Page 23: ...EMENT DU COMPRESSEUR TEMPO MINIMO di funzionamento del compressore c4 SECURITY RELAY 0 OFF 100 ON SICHERHEITSRELAIS 0 OFF 100 ON SECURITE RELAIS 0 OFF 100 ON SICU REZZA RELE 0 OFF 100 ON DEFROST SETTI...

Page 24: ...0 staendig laufend aus genommen F2 F3 Fd GESTION VENTILATEURS 0 toujours en marche F2 F3 Fd Gestione VENTOLE 0 ventole sempre ON salvo i parametri F2 F3 Fd F1 FAN SWITCH OFF TEMPERATURE TEMPERATUR ABS...

Page 25: ...in Max M B C C F 20 20 0 0 2 1 15 4 4 3 1 15 8 8 4 0 100 0 0 5 flag 0 1 0 0 6 flag 0 1 0 0 rd C F 0 1 19 9 2 2 r1 C F 40 r2 5 25 r2 C F r1 199 10 15 r3 flag 0 1 0 0 r4 C F 0 20 3 3 r5 flag 0 1 0 0 rt...

Page 26: ...86...

Page 27: ...NE MAGNETIQUE VALVOLA SOLENOIDE 10 THERMAL EXPANSION VALVE THERMOSTATVENTIL SOUPAPE THERMOSTATIQUE VALVOLA TERMOSTATICA 11 ELECTRO MOTOR DRIVEN FAN MOTOVENTILATOR VERD MOTOVENTILATEUR EVAP MOTOVENTIL...

Page 28: ...69 58 43 60 61 46 50 64 44 45 42 68 76 75 71 72 73 74 2 1 3 4 41 40 5 6 7 8 9 12 10 11 13 14 36 37 39 38 35 34 15 18 17 19 16 20 21 25 26 33 32 31 30 29 28 27 24 23 22 77 84 83 82 85 78 81 79 80 1 DB...

Page 29: ...6 1 1 1 1 1 25 RELAY BASE RELAISSOCKEL SUPPORT RELAIS ZOCCOLO RELE 3ZCC028 1 1 1 1 1 26 RELAY RELAIS RELAIS RELE 3RLM051 1 1 1 1 1 27 SELECTOREXTENSION W HLERVERL NGERUNG RALLONGESECTIONNEUR PROLUNGA...

Page 30: ...OITE CONNEXION SCATOLACONNESSIONI 3CSD009 1 1 1 1 1 64 VALVE VENTIL VANNE RUBINETTO 3RBN113 1 1 1 1 3RBN114 1 65 VALVE VENTIL VANNE RUBINETTO 3RBN117 1 1 1 1 3RBN118 1 66 DEFROSTHEATER ABTAUHEIZUNGEN...

Page 31: ...91...

Page 32: ...59 63 66 61 64 65 52 49 68 51 71 75 76 74 73 72 1 2 3 5 6 4 14 15 7 13 16 12 9 10 11 21 22 20 17 18 19 46 25 24 23 26 32 33 87 35 36 37 38 39 86 83 30 28 27 29 45 44 43 42 41 8 82 34 40 85 31 84 89 90...

Page 33: ...SB165 40 COMP FUSE HOLDER K O M P R E S S O R S I C H E R U N G S O C K E L SUPPORTFUS COMP BASE FUS COMP 3BSF051 86 FUSE SICHERUNG FUSIBLE FUSIBILE 3FSB168 27 SWITCH SCHALTER INTERRUPTEUR INTERRUTTOR...

Page 34: ...94...

Page 35: ...95...

Page 36: ...IBILE VARIATORE VELOCITA SPEED REGULATOR FUSE FUSIBLE VARIATEUR VITESSE GESCHW REGLERSICHERUNG FUSIBLE VARIADOR VELOCIDAD FUS VEL DO VARIADOR DE VELOCIDADE F6 FUSIBILE VENTOLA CONDENSATORE CONDENSER F...

Page 37: ...EVAPORATORE EVAPORATOR FAN MOTOR MOTEUR VENTILATEUR EVAPORATEUR VERDMF VENTILATORMOTOR MOTOR VENTILADOR EVAPORADOR MOTOR VENTILADOR EVAPORADOR P1MX PRESSOSTATO INSERZIONE VENTOLACOND COND FAN STARTIN...

Page 38: ...0MAN125A 04 2 2 001...

Reviews: