background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53480147-01

Printed in U.S.A.

Form IIK-CRECOMZR74-04

Pg 1 

9-21 Replaces: IIK-CRECOMZR74-03

Installation Instructions

Part No: CRECOMZR074A01 and CRECOMZR075A01

CONTENTS

Page

SAFETY CONSIDERATIONS   . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Compliance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Vertical Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . 6
Barometric Hood Assembly  . . . . . . . . . . . . . . . . . . . . 7

• BAROMETRIC HOOD (VERTICAL CONFIGURATION)

• BAROMETRIC HOOD (HORIZONTAL 

CONFIGURATION)

Vertical and Horizontal Applications . . . . . . . . . . . . . 8
Wiring Instructions for 1 and 2 Speed Units   . . . . . . 9
EconoMi$er X System . . . . . . . . . . . . . . . . . . . . . . . . 13

• W7220 ECONOMIZER CONTROLLER

• USER INTERFACE

• KEYPAD

• USING THE KEYPAD WITH MENUS

• USING THE KEYPAD WITH SETTINGS AND 

PARAMETERS

• MENU STRUCTURE

• CHECKOUT TESTS

SETUP AND CONFIGURATION   . . . . . . . . . . . . . . . . 19
W7220 Economizer Module Wiring  . . . . . . . . . . . . . 19
Timeout and Screen Saver  . . . . . . . . . . . . . . . . . . . . 20
HH79AH001 Dry Bulb Sensor . . . . . . . . . . . . . . . . . . 20
Enthalpy Settings (Enthalpy Optional)  . . . . . . . . . . 20
Enthalpy Control Sensor Configuration  . . . . . . . . . 21
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Cooling, Unit with EconoMi$er X System  . . . . . . . . 22
Heating with EconoMi$er X System   . . . . . . . . . . . . 22
Demand Controlled Ventilation (DCV) . . . . . . . . . . . 23
TROUBLESHOOTING  . . . . . . . . . . . . . . . . . . . . . . . . 23
Power Loss (Outage or Brownout)  . . . . . . . . . . . . . 23
Alarms   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Clearing Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

SAFETY CONSIDERATIONS

Installation  of  this  accessory  can  be  hazardous  due  to  system

pressures, electrical components, and equipment location (such as

a roof or elevated structure). Only trained, qualified installers and

service  technicians  should  install,  start-up,  and  service  this

equipment. 

When  installing  this  accessory,  observe  precautions  in  the

literature, labels attached to the equipment, and any other safety

precautions that apply:

• Follow all safety codes

• Wear safety glasses and work gloves

• Use care in handling and installing this accessory

It is important to recognize safety information. This is the safety-

alert symbol: 

. When you see this symbol on the unit and in

instructions  or  manuals,  be  alert  to  the  potential  for  personal

injury.

Understand the signal words DANGER, WARNING, CAUTION,

and NOTE. These words are used with the safety-alert symbol.

DANGER identifies the most serious hazards which 

will

 result in

severe  personal  injury  or  death.  WARNING  signifies  hazards

which 

could

 result in personal injury or death. CAUTION is used

to identify unsafe practices, which 

may

 result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which 

will

 result in enhanced installation, reliability,

or operation.

GENERAL

The  EconoMi$er

®

  X  system  utilizes  the  latest  technology

available for integrating the use of free cooling with mechanical

cooling for packaged rooftop units. The solid-state control system

optimizes  energy  consumption,  zone  comfort,  and  equipment

cycling  by  operating  the  compressors  when  the  outdoor-air

temperature is too warm, integrating the compressor with outdoor

air when free cooling is available, and locking out the compressor

when  outdoor-air  temperature  is  too  cold.  Demand  control

ventilation is supported. 

This EconoMi$er  X  system  can  be used  with 1,  2,  or  3 speed

(48/50LC 14) units.

CAUTION

Failure  to  follow this caution  may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and

wear  appropriate  protective  clothing,  safety  glasses,  and

gloves when handling parts and servicing rooftop units.

CAUTION

Failure to follow this caution may result in personal injury and

damage to the unit. Cover the duct opening as a precaution so

objects  cannot  fall  into  the  return  duct  opening.  Be  sure  to

remove the cover when installation is complete.

WARNING

Electrical shock can cause personal injury and death. Shut off

all power to this equipment during installation. There may be

more than one disconnect switch. Tag all disconnect locations

to alert others not to restore power until work is completed.

Medium Rooftop Units

12.5 to 27.5 Tons

Ultra Low Leak EconoMi$er

®

 X Accessory

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...