background image

23

Demand Controlled Ventilation (DCV)

If a field-installed CO

2

 sensor is connected to the EconoMi$er X

control,  a  Demand  Controlled  Ventilation  strategy  will  operate

automatically. As the CO

2

 level in the space increases above the

setpoint (on the EconoMi$er X controller), the minimum position

of  the  dampers  will  be  increased  proportionally,  until  the

Maximum Ventilation setting is reached. As the space CO

2

 level

decreases because of the increase in fresh air, the outdoor damper

will follow the higher demand condition from the DCV mode or

from the free cooling mode.

DCV operation is available in Occupied and Unoccupied periods

with EconoMi$er X Controller. However, a control modification

will be required on the units to implement the Unoccupied period

function.

TROUBLESHOOTING

For a list of common operating issues and concerns see Table 14.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored after any power

loss or interruption, as all settings are stored in the Economizer

controller’s non-volatile flash memory.

NOTE: If the power goes below 18 Vac, the W7220 controller

module assumes a power loss and the 5 minute power up delay

will become functional when power returns above 18 Vac.

Alarms

The economizer module provides alarm messages that display on

the 2-line LCD.

NOTE: Upon power up, the module waits several seconds before

checking  for  alarms.  This  allows  time  for  all  the  configured

devices (e.g., sensors, actuator) to become operational.

If one or more alarms are present and there has been no keypad

activity  for  at  least  5  minutes,  the Alarms  menu  displays  and

cycles through the active alarms.

The Alarms menus can be navigated to at any time. See Table 6

for the Alarms menu.

Clearing Alarms

Once  the  alarm  has  been  identified  and  the  cause  has  been

removed (e.g., replaced faulty sensor) the alarm can be cleared

from the display.

To clear an alarm, perform the following: 

1. Navigate to the desired alarm. 

2. Press the 

 button. 

3. ERASE? displays. 
4. Press the 

 button. 

5. ALARM ERASED displays. 
6. Press the 

 (Menu Up) button to complete the action and

return to the previous menu.

NOTE: If the alarm still exists after it is cleared, it is redisplayed

within 5 seconds.

Table 14 — 

 Operating Issues and Concerns

ISSUE OR CONCERN

POSSIBLE CAUSE AND REMEDY

My outdoor temperature reading on the

STATUS menu is not accurate

Check the sensor wiring:

•  Enthalpy sensors are to be wired to the S-Bus terminals.

•  Temperature sensors are to be wired to the OAT and MAT terminals.

If my enthalpy sensor drifts in accuracy over time, can I re-

calibrate it?

The sensor is not able to be re-calibrated in the field. However there is a menu item 

under the ADVANCED menu  to input a limited off set in temperature and humidity for 

each sensor connected to the economizer.

Can I go back to factory defaults and start over?

Under the SYSTEM SETUP menu you can change the setpoints to the factory 

defaults.

Will I be able to see the LCD screen when it is in the unit?

The LCD screen has a backlight that is always illuminated.

What is a good setpoint for the Mixed Air

Temperature (MAT)?

The mixed are temperature is the temperature of air that you want to supply to the 

space. In a commercial building, this is between 50°F and 55°F (10°C and 13°C). The 

mixed air is the mixing of the return air and the outdoor air.

I am using enthalpy sensors. Why did the control ask me to 

input a dry bulb changeover temperature?

In the even the humidity sensor in the enthalpy sensors fails, the backup algorithm in 

the control is to default to the temperature sensor in the enthalpy sensor.

In checkout, the outdoor damper closes when I command it 

to open.

Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper 

should drive open or closed with the return air damper having the opposite effect.

How do I set my minimum position?

The minimum position is set using the VENTMIN and VENTMAX setup in the 

SETPOINTS menu. VENTMIN is the minimum ventilation required when using an 

occupancy sensor and VENTMAX is the minimum ventilation when not using an 

occupancy sensor for Demand Controlled Ventilation. The VENTMAX position is set 

the same as with the potentiometer on the analog economizers and is the output 

voltage to the damper actuator. The range is 2 Vdc closed OA damper and 10 Vdc 

open OA damper.

What if my damper does not go completely closed in the 

checkout operation?

Check the damper linkage or hub to make sure the damper is able to close 

completely.

How do I set the OCC?

There are two settings for the OCC setting: INPUT and ALWAYS. INPUT is from the 

space thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied 

mode, if the economizer is powered (fan on).

Does the economizer save my program values if the unit 

loses power?

Yes, once the changes are stored in the controller they will be stored until they are 

changed by the operator.

If the unit is left in checkout, how long will the unit stay in 

checkout mode without input?

The unit will remain in checkout for 10 minutes, then return to normal operation.

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: