and can be removed from the W7220 and discarded. Follow all

local and other applicable codes.

Wiring Instructions for 1 and 2 Speed Units

1. Install W7220  (with  harnesses  attached)  in unit top  left  of

control box. See wiring diagram in instructions.

2. Mount supply air temperature (SAT) sensor, with 2 wire SAT

harness attached, in the indoor blower section.

3. Unplug  the  EconoMi$er  X  harness  from  PL6  with  10-pin

plug shown in Fig. 27, from Central Terminal Board (CTB).

4. Attach 10-pin plug disconnected from (CTB) to 10-pin plug

harness from W7220 controller.

5. Connect  other  10-pin  plug  from  W7220  controller  into

ECONO terminals on CTB. (See Fig. 27.)

6. Inside  control  box  –  connect  4-pin  plug  from  the W7220

controller to the 4-pin 50HEHMRAE--A10 harness provided

with economizer accessory.

7. Inside the  control box  – the brown  and  orange  wires with

male  terminals  from  the  50HEHMRAE--A10  harness

connect to the female terminals on the pink and violet wires

from the PL6 harness. 

8. Inside the control  box – connect  the pink and violet wires

with female terminals on 50HEHMRAE--A10,  to the pink

and violet wires with male terminals from the PL6 harness.

9. Inside the Indoor Blower Section connect the pink and violet

wires from the PL6 harness to the (2) green wires leading to

the SAT.

Fig. 27 — 

Harness Detail

PL6

SAT

ORN

BRN

CONTROL BOX

CENTRAL

TERM.BRD

.

ECONO

W7720

 

48TMHSRSE--A20 

SEE DETAIL

Unplug the 10-pin plug from
Pl6 from the central terminal
Board (in control box) and plug
Into 10-pin plug from W7220.

Plug 10-pin from
W7220 into econo
Terminals on central
Terminal board.

INDOOR BLOWER
SECTION

CONNECT SAT SENSOR AND PINK
AND VIOLET WIRES FROM PL6 TO
THE 48TMHSRSE--A20
HARNESS.

HARNESS WITH 4-PIN
PLUG

ECONOMIZER X

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: