The EconoMi$er X system utilizes gear-drive technology with a

direct-mount spring  return  actuator that will  close  upon loss  of

power.  The  EconoMi$er  X  system  comes  standard  with  an

outdoor air temperature sensor, mixed air temperature sensor (also

called supply air  temperature  sensor). Outdoor enthalpy, indoor

(return) dry bulb or enthalpy, and CO

2

 sensors are available for

field installation. 

Standard  barometric  relief  dampers  provide  natural  building

pressurization  control.  An  optional  power  exhaust  system  is

available  for  applications  requiring  even  greater  exhaust

capabilities.  The  power  exhaust  set  point  is  adjustable  at  the

EconoMi$er X controller.

See  Tables  1-3  for  package  usage.  See  Table  4  for  package

contents. See Table 5 for sensor usage.

Compliance

Economizers meet California Energy Commission Title 24-2016

prescriptive section 140.4 (damper leakage etc.), and mandatory

section 120.2.i for Fault Detection and Diagnostic controls.

Economizers  meet  ASHRAE  90.1-2016  damper  leakage

requirements  as  stated  in  Section  6.5.1.1.4  and Table  6.4.3.4.3,

and  meet  2016  Fault  Detection  and  Diagnosis  requirements  in

section 6.4.3.12.

Economizers  meet  IECC  2012  section  C402.4.5.2  and,  IECC

2015 sections  C403.2.4.3 and C403.3.3.5 for outside air, return

air, and relief air damper leakage requirements, and IECC 2015

section  C403.2.4.7  for  Fault  Detection  and  Diagnostic

requirements. 

NOTE:  IECC  2015  section  C403.2.4.7.1  requires  differential

return air sensor, which must be ordered separately. 

Relief air, outside air, and return air (volume) dampers are AMCA

rated.

 

IMPORTANT:  Read  these  instructions  completely  before

attempting to install the accessory economizer.

Table 1 — 

Carrier Usage Chart

CARRIER MODEL NUMBER

ECONOMI$ER

®

 X PART 

NUMBER

48/50TC 17-24

CRECOMZR074A00

48/50HC 17-20

48/50LC 14

48/50TCQ 17-24

48/50TC 28-30

CRECOMZR075A00

48/50HC 24-28

48/50LC 16-26

Table 2 — 

   

Bryant Usage Chart

BRYANT MODEL NUMBER

ECONOMI$ER X

®

 PART 

NUMBER

580J, 558J 17-24

CRECOMZR074A00

581J, 551J 17-20

548J 17-24

580J, 558J 28

CRECOMZR074A00

581J, 551J 24-28

Table 3 — 

ICP Usage Chart

ICP MODEL NUMBER

ECONOMI$ER X

®

 PART 

NUMBER

RGS, RAS 181, 183, 210, 213, 240, 243

CRECOMZR074A00

RGH, RAH 181, 210

RHS 181, 240

RGS, RAS 300, 303, 336

CRECOMZR075A00

RGH, RAH 240, 300

Table 4 — 

Package Contents

ECONOMIZER PART 

NUMBER

QTY

CONTENTS

CRECOMZR074A01

1

Damper Assembly with Shroud

1

Upper End Economizer Panel

1

Bottom Panel with Relief Damper 

(for vertical only)

1

Bottom Panel #2 with Return Duct 

Opening 

(for horizontal only)

1

Side Replacement Panel 

(for horizontal only)

3

Filter Supports

3

Central Retainer

1

Hood Top

1

Left Hood Side

1

Right Hood Side

2

Side Retainer

2

Top Diverters

3

Deflector

4

Outside Air Filter Screens

1

Mixed (Supply) Air Temperature 

Sensor HH79AH001 and Harness

1

50HEHMRAE-A10 Harness

1

Parts Bag with W7220 Controller 

with 50HEHMRAE-A00 Harness 

Attached

60

Screws #10 - 16 in. x 7/8 in.

14 ft

Seal Strip 1/8 in. x 3/4 in.

CRECOMZR075A01

1

Damper Assembly with Shroud

1

Upper End Economizer Panel

1

Bottom Panel with Relief Damper 

(for vertical only)

1

Bottom Panel #2 with Return Duct 

Opening 

(for horizontal only)

1

Side Replacement Panel 

(for horizontal only)

3

Filter Supports

3

Central Retainer

1

Hood Top

1

Left Hood Top

1

Right Hood Top

2

Side Retainer

2

Top Diverters

3

Deflector

4

Outside Air Filter Screens

1

Mixed (Supply) Air Temperature 

Sensor HH79AH001 and Harness

1

50HEHMRAE--A10 Harness

1

Parts Bag with W7220 Controller 

with 50HEHMRAEH-A00 Harness 

Attached

60

Screws #10 - 16 in. x 7/8 in.

14 ft

Seal Strip 1/8 in. x 3/4 in.

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...