Fig. 13 — Hood Assembly — Completed

Fig. 14 — 

Hood Assembly Installed

Horizontal Installation

These  economizers  are  designed  to  work  in  both  vertical  and

horizontal  applications.  These  instructions  are  for  horizontal

applications.

The  unit  has  a  horizontal  duct  opening  next  to  the  horizontal

supply  duct  opening.  However,  in  this  application,  with  an

economizer, the horizontal duct will actually come into the unit

underneath the outdoor air hood. (See Fig. 15.)

Fig. 15 — 

Install Bottom Panel with Horizontal Return 

Duct Opening

1. Turn off unit power supply and install lockout tag.

2. Prepare the unit for economizer installation: 

 a. For units with 2 position damper installed, remove the

outside  air  hood.  Unplug  the  damper  actuator  and

remove assembly from unit. 

 b. For  unit  with  manual  damper  installed,  remove  the

manual damper and hood.

3. Remove the upper panel and bottom panel (provided with the

HVAC  unit).  On  the  end  of  the  unit  to  expose  the  return

section.  (See  Fig.  2.)  Save  the  screws  for  use  later  when

replacing the panel. The panels can be discarded.

4. Remove the unit’s left side corner post and left side panel

from the unit to allow for easy economizer installation. (See

Fig. 16.) 

NOTE: The unit’s left side panel has a duct opening in it, but

this panel/duct opening will not be used in this application

and can be discarded.

Fig. 16 — 

Remove Unit Corner Post and Side Panel

5. Install economizer with shroud attached, as shown in Fig. 3,

into the return air section of the unit. Be careful not to pinch

the wires during installation. The bottom of economizer will

rest on the base of the unit. (See Fig. 4.)

6. Reinstall the left side corner post on the unit. Note the corner

post  will  sit  behind  the  economizer  shroud  flange.  Screw

through the corner post and through the economizer shroud.

(See Fig. 5 and 6.)

7. Insert  provided  screw  through  the  bottom  left  rear  of  the

economizer and into the unit base. (See Fig.  4). Install the

new (provided) left side panel without the duct opening on

the unit.

8. Before the economizer is secured in place on the right hand

side, remove and save the 12-pin jumper plug from the unit

wiring harness. Insert the EconoMi$er X plug into the unit

wiring harness plug. (See Fig.7.)
NOTE: The 12-pin jumper plug should be saved for future

use in the event that the EconoMi$er X is removed from the

unit.  The  jumper  plug  is  not  needed  as  long  as  the

EconoMi$er X is installed.

9. Install the bottom panel (provided) with the horizontal return

duct opening on the unit (see Fig. 15 and 17). Screw the panel

into place.

10. Install the upper end economizer panel in place over the econ

-

omizer’s  outside  air  damper,  and  above  the  bottom  panel.

Screw panel in place and screw panel into the economizer in

2 places.

11. Locate  the  mixed  (supply)  air  temperature  sensor

(HH79AH001)  in  the  economizer  hardware  bag. A  2-wire

sensor harness with spade terminals is supplied with the sen

-

sor. Plug the harness into the top of the HH79AH001 sensor.

Mount the sensor in the indoor fan section of the unit. Locate

the orange and brown wires in the wire bundle in the indoor

fan  section.  Connect  these  orange  and  brown  wires  to  the

2-wire harness attached to the HH79AH001 sensor. Mixed air

default setting is 53°F and can be adjusted from 38°F to 70°F.

Assemble the outside air hood per Fig. 12 and 13
 a. Install four hood angles to the upper end panel using the

screws provided. 

 b. Apply seal strip to mating flanges on the side plates of

the hood and the hood top. 

Outdoor 
Air Hood

Relief Damper

Bottom Panel With
Return Duct Opening

Unit’s Left Side

Panel With 
Duct Opening

Left Front

Corner Post

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: