EconoMi$er X System

The field-installed accessory consists of the following:

• Low leak economizer assembly 

• HH79AH001 OA Dry Bulb Sensor

• HH79AH001 Mixed Air Sensor and Harness

• W7220 Controller

• 50HEHMRAE--A10 Harness (not used on 3 speed units)

W7220 ECONOMIZER CONTROLLER
The economizer controller used on electro-mechanical units is a

Honeywell W7220 which is to be located in the RTU base unit’s

control  box.  See  Fig.  31  for  button  description  of  the  W7220

controller. See the Installation Instruction for your base unit for

the location of the Control Box access panel.
USER INTERFACE
The  user  interface  consists  of  a  LCD  display  and  a  4-button

keypad on the front of the economizer controller.
KEYPAD
The  four  navigation  buttons  (see  Fig.  31)  are  used  to  scroll

through  the menus  and  menu  items,  select  menu  items,  and  to

change parameter and configuration settings.
USING THE KEYPAD WITH MENUS
To use the keypad when working with menus:

• Press the  ▲  (Up  arrow) button to move to  the previous

menu.

• Press  the  ▼  (Down  arrow)  button  to  move  to  the  next

menu.

• Press  the  (Enter)  button  to  display  the  first  item  in  the

currently displayed menu.

• Press the 

 (Menu Up/Exit) button to exit a menu’s item

and return to the list of menus.

USING  THE  KEYPAD  WITH  SETTINGS  AND

PARAMETERS
To  use  the  keypad  when  working  with  Setpoints,  System  and

Advanced Settings, Checkout Tests and Alarms:

1. Navigate to the desired menu.

2. Press  the  (Enter)  button  to  display  the  first  item  in  the

currently displayed menu.

3. Use the ▲ and ▼ buttons to scroll to the desired parameter.
4. Press the (Enter) button to display the value of the currently

displayed item.

5. Press  the  ▲  button  to  increase  (change)  the  displayed

parameter value.

6. Press  the  ▼  button  to  decrease  (change)  the  displayed

parameter value.

NOTE:  When values are displayed, pressing and holding the

▲ or ▼ button causes the display to automatically increment.

7. Press  the  (Enter)  button  to  accept  the  displayed  value  and

store it in nonvolatile RAM.

8. “CHANGE STORED” displays.
9. Press  the  (Enter)  button  to  return  to  the  current  menu

parameter.

10. Press the 

 (Menu Up/Exit) button to return to the previous

menu.

MENU STRUCTURE
Table  6  illustrates  the  complete  hierarchy  of  menus  and

parameters for the EconoMi$er X system.

The Menus in display order are:

• STATUS

• SETPOINTS

• SYSTEM SETUP

• ADVANCED SETUP

• CHECKOUT

• ALARMS

Fig. 31 — 

W7220 Controller

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: