Table 6 — 

 Menu Structure (cont) 

See Legend and notes on page 18.

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER RANGE AND 

INCREMENT

NOTES

ADVANCED 

SETUP

MA LO SET

45°F

35°F to 55°F; 

Incremented by 10

Temperature to achieve Freeze Protection (close 

damper and alarm if temperature falls below setup 

value).

FREEZE POS

CLO

CLO or MIN

Damper position when freeze protection is active 

(closed or MIN POS).

CO2 ZERO

0ppm

0 to 500 ppm; Increment by 

10

CO

2

 ppm level to match CO

2

 sensor start level.

CO2 SPAN

2000ppm

1000 to 3000 ppm; 

Increment by 10

CO

2

 ppm span to match CO

2

 sensor.

STG3 DLY

2.0h

0 min, 5 min, 15 min, then 15 

min intervals. Up to 4 h or 

OFF

Delay after stage 2 cool has been active. Turns on 2nd 

stage of cooling when economizer is 1st  stage and 

mechanical cooling is 2nd stage. Allows three stages of 

cooling, 1 economizer and 2 mechanical.

OFF = no Stage 3 cooling

SD DMPR POS

CLO

CLO or OPN

Indicates shutdown signal from space thermostat or 

unitary controller. When controller receives 24 Vac 

input on the SD terminal in conventional mode, the OA 

damper will open if programmed for OPN and OA 

damper will close if programmed for CLO. All other 

controls, e.g., fans, etc. will shut off.

DCVCAL ENA

MAN

MAN (manual) AUTO

Turns on the DCV automatic control of the dampers. 

Resets ventilation based on the RA, OA, and MA 

sensor conditions. Requires all 3 RA, OA, and MA 

sensors.

MAT T CAL

0.0°F

±2.5°F

Allows for the operator to adjust for an out of calibration 

temperature sensor.

OA T CAL

0.0°F

±2.5°F

Allows for the operator to adjust for an out of calibration 

temperature sensor.

OA H CAL

0% RH

±10% RH

Allows for operator to adjust for an out of calibration 

humidity sensor.

RA T CAL

0.0°F

±2.5°F

Allows for the operator to adjust for an out of calibration 

temperature sensor.

RA H CAL

0% RH

±10% RH

Allows for operator to adjust for an out of calibration 

humidity sensor.

DA T CA;

0.0°F

±2.5°F

Allows for the operator to adjust for an out of calibration 

temperature sensor.

CHECKOUT

DAMPER VMIN─HS

N/A

N/A

Positions damper to VMIN position

DAMPER VMAX─HS

N/A

N/A

Positions damper to VMAX position

DAMPER OPEN

N/A

N/A

Position damper to the full open position.

Exhaust fan contacts enable during the DAMPER 

OPEN test. Make sure you pause in the mode to allow 

exhaust contacts to energize due to the delay in the 

system.

DAMPER CLOSE

N/A

N/A

Positions damper to the fully closed position

CONNECT Y1─O

N/A

N/A

Closes the Y1─O relay (Y1─O)

CONNECT Y2─O

N/A

N/A

Closes the Y2─O relay (Y2─O)

CONNECT AUX

N/A

N/A

Energizes the AUX output. If Aux setting is:

• NONE ─ not action taken

• ERV ─ 24 Vac out. Turns on or signals an ERV that 

the conditions are not good for economizing but are for 

ERV operation.

• SYS ─ 24 Vac out. Issues a system alarm

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: