Table 7 — 

 Economizer Module - Left Hand Terminal 

Blocks

Table 8 — 

 Economizer Module - Right Hand Terminal 

Blocks

Timeout and Screen Saver

When  no  buttons  have  been  pressed  for  10  minutes,  the  LCD

displays  a  screen  saver,  which  cycles through the Status items.

Each status item displays in turn and cycles to the next item after

5 seconds.

HH79AH001 Dry Bulb Sensor

Economizers are shipped standard with an HH79AH001 outside

air  dry  bulb  sensor  (see  Fig.  34).  System  default  setting  (high

temp limit) is 63°F, and has a range of 48°F to 80°F. The sensor is

factory installed on the economizer. 

NOTE:  A second HH79AH001 sensor is provided for mixed

air temperature.

Fig. 34 — 

HH79AH001 Dry Bulb and Mixed Air Sensor

NOTE:  California  high  temperature  setting  requirements  by

region are shown below in Table 9.

Table 9 — 

 California Title 24 Regional High Limit Dry 

Bulb Temperature Settings

Only  the  high  limit  control  devices  listed  are  allowed  to  be  used  and  at  the

setpoints listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy,

and  Differential  Enthalpy  Controls,  may  not  be  used  in  any  climate  zone  for

compliance  with  Section  140.4(e)1  unless  approval  for  use  is  provided  by  the

Energy Commission Executive Director.

† 

At altitudes substantially different than sea level, the Fixed Enthalpy limit value

shall  be  set  to  the  enthalpy  value  at  75°F  and  50%  relative  humidity.  As  an

example, at approximately 6,000 foot elevation, the fixed enthalpy limit is approxi-

mately 30.7 Btu/lb.

Enthalpy Settings (Enthalpy Optional)

If  installing  the  optional  HH57AC081  enthalpy  sensor.  The

HH79AH001 dry bulb outside air sensor must first be removed.

Wire  enthalpy  to  S-BUS  connections  on  W7220  controller

through (2) gray wires.

When the OA temperature, enthalpy and dew point are below the

respective setpoints, the outdoor air can be used for economizing.

Figure  35  shows  the  new  single  enthalpy  boundaries  in  the

W7220.  There  are  5  boundaries  (setpoints  ES1  through  ES5),

which  are  defined  by  dry  bulb  temperature,  enthalpy  and  dew

point.

See Table 10 for ENTH CURVE setpoint values.

To use enthalpy the W7220 must have a HH57AC081 enthalpy

control sensor for OA. The W7220  calculates the enthalpy and

dewpoint using the OA temperature and humidity input from the

OA sensor. When the OA temperature, OA humidity and OA dew

point are all below the selected boundary, the economizer sets the

economizing mode to YES, economizing is available.

When all of the OA conditions are above the selected boundary,

the conditions are not good to economize and the mode is set to

NO. If using OA enthalpy sensor option, remove and discard the

dry  bulb  sensor  shipped  with  the  economizer.  System  default

setting is ES3 enthalpy curve. See Table for California Title 24

high limit dry bulb temperature settings.

Figure 35 shows the 5 current boundaries. There is also a high

limit boundary for differential enthalpy. The high limit boundary

is ES1 when there are no stages of mechanical cooling energized

and HL (high limit) when a compressor stage is energized.

Table 10 provided the values for each boundary limit.

LABEL

TYPE

DESCRIPTION

Top Left Terminal Block

MAT

MAT

20k NTC 

and COM

Mixed Air Temperature Sensor (Polarity 

Insensitive Connection)

OAT

OAT

20k NTC 

and COM

Outdoor Air Temperature Sensor (Polarity 

Insensitive Connection)

S-BUS

S-BUS

S-BUS 

(Sylk Bus)

Enthalpy Control Sensor 

(Polarity Insensitive Connection)

Bottom Left Terminal Block

IAQ 2-10

2-10 vdc

Air Quality Sensor Input (e.g. CO

2

 sensor)

IAQ COM

COM

Air Quality Sensor Common

IAQ 24V

24 vac

Air Quality Sensor 24 vac Source

ACT 2-10

2-10 vdc

Damper Actuator Output (2-10 vdc)

ACT COM

COM

Damper Actuator Output Common

ACT 24v

24 vac

Damper Actuator 24 vac Source

LABEL

TYPE

DESCRIPTION

Top Right Terminal Blocks

AUX2 I

24 vac IN

The first terminal is not used.

OCC

24 vac IN

Shut Down (SD) or HEAT (W) 

Conventional only

and

Heat Pump Changeover (O-B) in Heat 

Pump mode.

E-GND

E-GND

Occupied/Unoccupied Input

EXH1

24 vac OUT Exhaust Fan 1 Output

AUX1 O

24 vac OUT

Programmable:

Exhaust fan 2 output

or

ERV

or

System alarm output

Bottom Right Terminal Blocks

Y2-I

24 vac IN

Y2 in - Cooling Stage 2 Input from space 

thermostat

Y2-O

24 vac OUT Y2 out - Cooling Stage 2 Output to stage 

2 mechanical cooling

Y1-I

24 vac IN

Y1 in - Cooling Stage 2 Input from space 

thermostat

Y1-O

24 vac OUT Y1 out - Cooling Stage 2 Output to stage 

2 mechanical cooling

C

COM

24 vac Common

R

24 vac

24 vac Power (hot)

DEVICE TYPE*

CLIMATE 

ZONES

REQUIRED HIGH LIMIT 

(ECONOMIZER OFF 

WHEN):

DESCRIPTION

FIXED DRY BULB

1, 3, 5, 11-16

OAT exceeds 75°F

2, 4, 10

OAT exceeds 73°F

6, 8, 9

OAT exceeds 71°F

7

OAT exceeds 69°F

DIFFERENTIAL DRY 

BULB

1, 3, 5, 11-16

OAT exceeds RA Temp.

2, 4, 10

OAT exceeds -2°F

6, 8, 9

OAT exceeds -4°F

7

OAT exceeds -4°F

FIXED ENTHALPY† 

+ FIXED DRY BULB

ALL

OAT exceeds 28 Btu/lb of 

dry air or OAT exceeds 75°F

Honeywell

HH79AH001

Summary of Contents for CRECOMZR074A01

Page 1: ...symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are us...

Page 2: ...nomizer Table 1 Carrier Usage Chart CARRIER MODEL NUMBER ECONOMI ER X PART NUMBER 48 50TC 17 24 CRECOMZR074A00 48 50HC 17 20 48 50LC 14 48 50TCQ 17 24 48 50TC 28 30 CRECOMZR075A00 48 50HC 24 28 48 50L...

Page 3: ...with shroud attached as shown in Fig 3 into the return air section of the unit Be careful not to pinch the wires during installation The bottom of the economizer will rest on the base of the unit See...

Page 4: ...crew panel into economizer in two places See Fig 9 Fig 9 End View of Unit 11 Locate the mixed supply air temperature sensor HH79AH001 in the economizer hardware bag A 2 wire sensor harness with spade...

Page 5: ...Item 1 so that central retainer is perpendicular to hood and each filter support Secure using screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to hood top Item...

Page 6: ...conomizer shroud flange Screw through the corner post and through the economizer shroud See Fig 5 and 6 7 Insert provided screw through the bottom left rear of the economizer and into the unit base Se...

Page 7: ...tical applications Reinstall the hinges and damper on the side of the field supplied return duct See page 8 NOTE A relief hood for the horizontal application can be ordered separately part number CRBA...

Page 8: ...CRBARHOD001A00 hood sides and top together See Fig 25 Caulk the backside of the mating flanges to ensure a watertight seal Install the CRBARHOD001A00 over the relief damper and screw to the return du...

Page 9: ...d with economizer accessory 7 Inside the control box the brown and orange wires with male terminals from the 50HEHMRAE A10 harness connect to the female terminals on the pink and violet wires from the...

Page 10: ...10 Fig 28 Typical EconoMi er X Wiring Diagram for 1 and 2 Speed Units...

Page 11: ...3 Speed Unit Instructions for Complete Diagram NOTES 1 Wires shown in bold are part of 48LCHSRADH A00 harness which is provided with 48 50LC 14 26 size with 3 speed units 2 Harness 50HEHMRAEH A00 whic...

Page 12: ...8LCHSRADH A00 Harness for 3 Speed Units 48 50LC 14 26 Provided with 3 Speed Units Field Attached to W7220 Controller FIELD ATTACH TO W7220 CONTROLLER CONNECT TO UNIT TERMINAL BOARD CONNECT TO UNIT TER...

Page 13: ...on to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus USING THE KEYPAD WITH SETTINGS AND PARAMETERS To use th...

Page 14: ...d the setting under SYSTEM SETUP FAN TYPE must be changed to 1 speed ROOF TOP UNIT Y1O Y2O Y1I Y2I OCC 24 VAC E GND Y1 G W2 W1 Y2 O B OCC W7220 ECONOMIZER CONTROLLER MODULE THERMOSTAT CO2 SENSOR 2 10...

Page 15: ...40 F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40...

Page 16: ...led by CFM VENTMIN L 3 7 V N A N A VENTMIN H 2 8 V N A N A ERV OAT SP 32 F 0 to 50F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan s...

Page 17: ...f the dampers Resets ventilation based on the RA OA and MA sensor conditions Requires all 3 RA OA and MA sensors MAT T CAL 0 0 F 2 5 F Allows for the operator to adjust for an out of calibration tempe...

Page 18: ...hen replace sensor if the alarm continues OA SENS T ERR N A N A Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A Actu...

Page 19: ...tem as a test that the system is operable SETUP AND CONFIGURATION W7220 Economizer Module Wiring Use Fig 33 and Tables 7 and 8 to locate the wiring terminals for the economizer module NOTE The four te...

Page 20: ...below the selected boundary the economizer sets the economizing mode to YES economizing is available When all of the OA conditions are above the selected boundary the conditions are not good to econom...

Page 21: ...12 HH57AC081 Sensor DIP Switch If using differential return enthalpy or temperature option see Table 9 for California Title 24 setting requirements by region ENTHALPY CURVE TEMP DRY BULB F TEMP DEWPOI...

Page 22: ...until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at set point concurrent with Compressor 1 operation The Low T Temp setting default 32...

Page 23: ...inals Temperature sensors are to be wired to the OAT and MAT terminals If my enthalpy sensor drifts in accuracy over time can I re calibrate it The sensor is not able to be re calibrated in the field...

Page 24: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480147 01 Printed in U S A Form IIK CRECOMZR74 04 Pg 24 9 21 Replaces...

Reviews: