The  EconoMi$er  2  system  uses  gear-drive  technology  with  a

direct-mount spring return actuator that will close  upon loss  of

power. Differential dry bulb, enthalpy,  and  differential enthalpy

sensors  are  available  for  field  installation.  Field-installed  CO

2

sensors are available. (See Table 5.)

Optional  barometric  relief  dampers  provide  natural  building

pressurization control. An optional power exhaust system is avail

-

able for applications requiring even greater exhaust capabilities.

The power exhaust set point is adjustable at the EconoMi$er 2

controller.

To see which economizer is used on specific Carrier, Bryant, or

ICP models see Tables 1-3. See Table 4 for package contents and

Table 5 for PremierLink

 controller sensor usage.

Compliance

EconoMi$er 2 outside air dampers meet the ASHRAE (American

Society  of  Heating,  Refrigeration,  and  Air-Conditioning

Engineers) 90.1-2016, IECC (International Energy Conservation

Code) 2015, and Title 24 2016 leakage requirements.

Economizers meet California Energy Commission Title 24-2013 /

2016 prescriptive section 140.4 (damper leakage etc.), and when

used  with  Carrier  ComfortLink,  RTU  Open,  PremierLink™,

SystemVu™, or I/O Flex 6126 control systems, meet mandatory

section 120.2.i for Fault Detection and Diagnostic requirements.

Economizers meet ASHRAE 90.1-2013 / 2016 damper leakage

requirements as stated in Section 6.5.1.1.4 and Table 6.4.3.4.3, and

meet 2016 Fault Detection and Diagnosis requirements in section

6.4.3.12  when  used  with  Carrier  ComfortLink,  RTU  Open,

PremierLink, SystemVu, or I/O Flex control systems.

Economizers  meet  IECC  2012  section  C402.4.5.2  and,  IECC

2015 sections C403.2.4.3 and C403.3.3.5 for outside air, return air,

and relief air damper leakage requirements, and when used with

Carrier ComfortLink, RTU Open, Premierlink, SystemVu, or I/O

Flex  control  systems  meet  IECC  2015  section  C403.2.4.7  for

Fault Detection and Diagnostic requirements. Note: IECC 2015

section C403.2.4.7.1 requires differential return air sensor, which

must be ordered separately.

Outside  air  and  return  air  (volume)  dampers  are AMCA  (Air

Movement and Control Association) rated. Relief air dampers are

also AMCA rated.

Table 1 —  Carrier Usage Chart

Table 2 —  Bryant Usage Chart

Table 3 —  ICP Usage Chart

Table 4 —  Package Contents

CARRIER MODEL NUMBER

EconoMi$er

®

PART NUMBER

48/50TC 17-24

CRECOMZR072A01

48/50HC 17-20

50TCQ 17, 24

48/50TC 28-30

CRECOMZR073A01

48/50HC 24-28

BRYANT MODEL NUMBER

EconoMi$er®2 

PART NUMBER

580J, 558J 17-24

CRECOMZR072A01

581J, 551J 17-20

548J 17-24

580J, 558J 28

CRECOMZR073A01

581J, 551J 24-28

ICP MODEL NUMBER

EconoMi$er

®

PART NUMBER

RGS, RAS 181, 183, 210, 213, 240, 243

CRECOMZR072A01

RGH, RAH 181, 210

RHS 181, 240

RGS, RAS 300, 303, 336

CRECOMZR073A01

RGH, RAH 240, 300

EconoMi$er

®

PART NUMBER

QTY

CONTENTS

CRECOMZR072A01

1

Damper Assembly With Shroud

1

Upper End Economizer Panel

1

Bottom Panel With Relief Damper 

(for vertical only)

1

Bottom Panel #2 (for horizontal only)

1

Side Replacement Panel 

(for horizontal only)

3

Filter Supports

3

Central Retainer

2

Side Retainer

1

Hood Top

1

Left Hood Side

1

Right Hood Side

2

Top Diverters

3

Deflector

4

Outside Air Filter Screens

60

Screws #10 — 16 x 7/8 in.

14

Seal Strip (ft) — 1/8 in. x 3/4 in.

CRECOMZR073A01

1

Damper Assembly With Shroud

1

Upper End Economizer Panel

1

Bottom Panel With Relief Damper 

(for vertical only)

1

Bottom Panel #2 (for horizontal only)

3

Filter Supports

3

Central Retainer

2

Side Retainer

1

Hood Top

1

Left Hood Side

1

Right Hood Side

2

Top Diverters

3

Deflector

4

Outdoor Air Filter Screens

60

Screws #10 — 16 x 7/8 in.

14

Seal Strip (ft) — 1/8 in. x 3/4 in.

Summary of Contents for CRECOMZR072A01

Page 1: ...to the equipment and any other safety precautions that apply Follow all safety codes Wear safety glasses and work gloves Use care in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER...

Page 2: ...d relief air damper leakage requirements and when used with Carrier ComfortLink RTU Open Premierlink SystemVu or I O Flex control systems meet IECC 2015 section C403 2 4 7 for Fault Detection and Diagnostic requirements Note IECC 2015 section C403 2 4 7 1 requires differential return air sensor which must be ordered separately Outside air and return air volume dampers are AMCA Air Movement and Con...

Page 3: ...It is important that the damper be perfectly square in the unit 6 Reinstall the left side corner post on to the unit NOTE The corner post will sit behind the economizer shroud flange See Fig 5 Screw through the corner post and through the economizer shroud See Fig 3 and 5 7 Insert provided screw through the bottom left rear of the economizer and into the unit base See Fig 3 Reinstall the unit s le...

Page 4: ... 9 10 11 12 WHT WHT YEL PINK VIO BLK BLK BLK BLU RED RED RED 73 73 73 69 69 69 69 69 73 To Optional Enthalpy Sensor 500 OHM Resistor Actuator Outside Air Sensor Units Left Side Panel Left Front Corner Post Screw Economizer Flange Economizer Shroud Jumper Plug Remove Harness Plug From Economizer Harness Plug From HVAC ...

Page 5: ...ood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is perpendicular to the hood and each filter support Secure using the screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to the hood top Item 3 k Install outdoor air screens by sliding them into each of the four spaces created by the hood filter...

Page 6: ... 3 3 Side Retainer 2 4 Hood Top 1 5 Left Hood Side 1 6 Right Hood Side 1 7 Top Diverters 2 8 Deflector 3 Apply seal strip to the front of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange 7 7 3 5 6 8 8 2 8 6 4 2 1 2 Insert Air Screen Slide Into Position Outdoor Air Hood CRBARHOD001A00 Relief Hood Ordered ...

Page 7: ...ve and save the 12 pin jumper plug from the unit wiring harness See Fig 6 Insert the EconoMi er 2 plug into the unit wiring harness plug See Fig 6 NOTE The 12 pin jumper plug should be saved for future use in the event that the EconoMi er2 is removed from the unit The jumper plug is not needed as long as the EconoMi er 2 is installed 9 Install the provided bottom panel with the horizontal return d...

Page 8: ... 19 illustrates the installed barometric hood parts Fig 19 Installed Barometric Hood Side View and Isometric View For horizontal return and field installed economizer install the economizer as follows 1 Install the field provided horizontal ductwork onto the unit Duct height must be at least 19 1 2 inches high however the duct can be no taller than the top of the relief opening in the bottom panel...

Page 9: ...e 12 pin economizer harness pin 5 and 6 are used to connect the OAT sensor to the PremierLink board INDOOR AIR QUALITY CO2 SENSOR Mount the optional indoor air quality CO2 sensor according to manufacturer specifications A separate field supplied transformer must be used to power the CO2 sensor Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller Refer to the Premie...

Page 10: ... 11 12 13 14 15 16 17 GRN DDC CONTROL RMTOCC CMPSAFE FSD SFS NOT USED RED PNK RED WHT RED BLU RED YEL RED 18 19 20 21 22 23 24 25 26 ORN RED ENTH POSITION 0 POSITION 1 1 LEN CCN 4 NO ACTION LOAD FACTORY DEFAULTS ON POWERUP 0 1 1234 ECONO J9 J7 NOT USED J8 FAN GRN CMP1 YEL CMP2 BLU HS1 WHT HS2 HS3 EXH RVS PNK ORNRED PWR RELAYS RED CUT FOR DUAL TRANSFORMER EQUIPMENT BLK WHT RED DISCRETE J4 0 20mA IN...

Page 11: ...eturn air enthalpy sensor to the enthalpy controller 2 At the enthalpy control remove the factory installed resistor from the SR and terminals 3 Connect the field supplied RED wire to spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller Connect the BLK wire to S spade connector on the return air enthalpy sensor and the SR ter minal on the enthalpy contro...

Page 12: ...EQUIRES BOTH AN ENTHALPY SWITCH RECEIVER 33CSENTHSW AND AN ENTHALPY SENSOR 33CSENTSEN The enthalpy switch receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy The enthalpy sensor is mounted in the return airstream and calculates the enthalpy of the indoor air For differential enthalpy control the enthalpy switch receiver energizes the HI enthalpy relay output when the o...

Page 13: ...set point has not been reached By the time the CO2 level reaches the set point the damper will be at maximum ventilation and should maintain the set point In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to remove contaminants during unoccupied periods ...

Page 14: ... cooling occurs when there is no call from the thermostat except G Pre cooling is defined as the economizer modulates to provide 70 F supply air When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following 3 routines The 3 control routines are bas...

Page 15: ... or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step 4 4 Make sure the control signal positive is connected to Wire No 3 and control signal negative is connected to Wire No 1 Most control problems are caused by reversing these two wires Verify that the reversing switch is all the CCW or CW Drives to Control...

Page 16: ...st 30 seconds The SPT SAT and OAT inputs must have valid readings OAT must be less than 75 F OAT must be less than SPT Enthalpy must be LOW may be jumpered if an enthalpy sensor is not available Economizer position is NOT forced When free cooling is available the outdoor air damper is positioned through the use of a Proportional Integral Derivative Loop PID control process to provide a calculated ...

Page 17: ... the number of heat stages is calculated otherwise the required number of heat stages will be set to 0 If the PremierLink controller determines that heat stages are re quired the economizer damper will be moved to minimum posi tion if occupied and closed if unoccupied Staging should be as follows IF HEATING PID STAGES 2 HEAT STAGES 1 50 capacity will energize HS1 HEAT STAGES 2 100 capacity will en...

Page 18: ......

Page 19: ......

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480313 01 Printed in U S A Form IIK CRECOMZR72 03 Pg 20 8 21 Replaces IIK CRECOMZR72 02 2021 Carrier ...

Reviews: