background image

16

ROUTINE 2 (DXCTLO < OAT < 68°F)

• If only Y1 energized, the economizer maintains a 

SASP = ( 3)

• If  SAT  >  SASP  +  5  and  economizer  position  >  80%

economizer will go to minimum position for 3 minutes or

until SAT > 68° F.

• First stage of mechanical cooling will be energized.

• Integrator resets.

• Economizer  opens  again  and  controls  to  current  SASP

after stage one on for 90 seconds.

• With Y1 and Y2 energized, economizer maintains a 

SASP =  3

• If  SAT  >  SASP  +  5  and  economizer  position  >  80%

economizer will go to minimum position for 3 minutes or

unit SAT > 68° F.

• If compressor one is on then second stage of mechanical

cooling will be energized. Otherwise the first stage will be

energized.

• Integrator resets.

• Economizer opens again and controls to SASP after stage

one on for 90 seconds.

ROUTINE 3 (OAT > 68° F)

• Economizer is opened 100%

• Compressors 1 and 2 are cycled based on Y1 and Y2 using

minimum  on  and  off  times  and  watching  the  supply  air

temperature  as  compared  to  SATLO1  and  SATLO2  set

points.

Heating, Units with EconoMi$er 2, PremierLink

Control and a Thermostat 

When the thermostat calls for heating, terminal W1 is energized.

The PremierLink control will move the economizer damper to the

minimum position if there is a call for G and closed if there is a

call for W1 without G. In order to prevent thermostat from short

cycling, the unit is locked into the heating mode for at least 10

minutes when W1 is energized. The induced draft motor is then

energized and the burner ignition sequence begins. 

On units equipped for two stages of heat, when additional heat is

needed, W2 is energized and the high fire solenoid on the main

gas valve (MGV) is energized. When the thermostat is satisfied

and W1 is de-energized, the IFM stops after 45 second time-off

delay, unless G is still maintained. 

Cooling, Units with EconoMi$er2, 

PremierLink Control and a Room Sensor 

When  free  cooling  is  not  available,  the  compressors  will  be

controlled  by  the  PremierLink  controller  using  a  Proportional

Integral  Derivative  Loop  (PID)  Error  reduction  calculation  as

indicated by Fig. 31.

Fig. 31 — DX Cooling Temperature Control Example

NOTE: PremierLink control performs smart staging of 2 stages of

DX cooling and up to 3 stages of heat.

The PremierLink controller will use the following information to

determine if free cooling is available: 

• Indoor fan has been on for at least 30 seconds. 

• The SPT, SAT, and OAT inputs must have valid readings. 

• OAT must be less than 75°F. 

• OAT must be less than SPT. 

• Enthalpy must be LOW (may be jumpered if an enthalpy

sensor is not available). 

• Economizer position is NOT forced. 

When  free  cooling  is  available,  the  outdoor  air  damper  is

positioned through the use of a Proportional Integral Derivative

Loop  (PID)  control  process  to  provide  a  calculated  supply  air

temperature into the zone. The supply air will maintain the space

temperature  between  the  heating  and  cooling  set  points  as

indicated in Fig. 32.

 

Fig. 32 — Economizer Temperature Control Example

The PremierLink

 

controller

 

will integrate the compressor stages

with the economizer based on similar logic as the three routines

listed in the previous section. The SASP will float up and down

based  on  the  error  reduction  calculations  that  compare  space

temperature and space set point. 

When outside air temperature conditions require the economizer

to  close  for  a  compressor  stage-up  sequence,  the  economizer

control integrator is reset to zero after the stage-up sequence is

completed.  This  prevents  the  supply  air  temperature  from

dropping too quickly and creating a freeze condition that would

make the compressor turn off prematurely. 

The high space set point is used for DX (direct expansion) cooling

control, while the economizer space set point is a calculated value

between the heating and cooling set points. The economizer set

point  will always  be  at  least  one degree  below  the  cooling  set

point, allowing for a smooth transition from mechanical cooling

with economizer assist, back to economizer cooling as the cooling

set  point  is  achieved. The  compressors  may  be  used  for  initial

cooling  then  the  PremierLink  controller  will  modulate  the

economizer using an error reduction calculation to hold the space

temperature  between  the  heating  and  cooling  set  point  (See

Fig. 32).

The  controller  uses  the  following  conditions  to  determine

economizer cooling: 

• Enthalpy is low

• SAT reading is available

• OAT reading is available

• SPT reading is available

• OAT ≤ SPT

• Economizer position is NOT forced

If  any  of  the  above  conditions  are  not  met,  the  economizer

submaster reference (ECSR) is set to the maximum limit and the

damper moves to minimum position. The operating sequence is

complete. The ECSR is recalculated every 30 seconds. 

TEMPERATURE CONTROL

75

74

73

72

71

70

69

68

SP

ACE TEMPERA

T

URE

SETPOINT

TEMPERATURE

TIME

TEMPERATURE CONTROL

75

74

73

72

71

70

69

68

SP

ACE TEMPERA

T

URE

COOL SETPOINT

TEMPERATURE
HEAT SETPOINT

TIME

Summary of Contents for CRECOMZR072A01

Page 1: ...to the equipment and any other safety precautions that apply Follow all safety codes Wear safety glasses and work gloves Use care in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER...

Page 2: ...d relief air damper leakage requirements and when used with Carrier ComfortLink RTU Open Premierlink SystemVu or I O Flex control systems meet IECC 2015 section C403 2 4 7 for Fault Detection and Diagnostic requirements Note IECC 2015 section C403 2 4 7 1 requires differential return air sensor which must be ordered separately Outside air and return air volume dampers are AMCA Air Movement and Con...

Page 3: ...It is important that the damper be perfectly square in the unit 6 Reinstall the left side corner post on to the unit NOTE The corner post will sit behind the economizer shroud flange See Fig 5 Screw through the corner post and through the economizer shroud See Fig 3 and 5 7 Insert provided screw through the bottom left rear of the economizer and into the unit base See Fig 3 Reinstall the unit s le...

Page 4: ... 9 10 11 12 WHT WHT YEL PINK VIO BLK BLK BLK BLU RED RED RED 73 73 73 69 69 69 69 69 73 To Optional Enthalpy Sensor 500 OHM Resistor Actuator Outside Air Sensor Units Left Side Panel Left Front Corner Post Screw Economizer Flange Economizer Shroud Jumper Plug Remove Harness Plug From Economizer Harness Plug From HVAC ...

Page 5: ...ood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is perpendicular to the hood and each filter support Secure using the screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to the hood top Item 3 k Install outdoor air screens by sliding them into each of the four spaces created by the hood filter...

Page 6: ... 3 3 Side Retainer 2 4 Hood Top 1 5 Left Hood Side 1 6 Right Hood Side 1 7 Top Diverters 2 8 Deflector 3 Apply seal strip to the front of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange 7 7 3 5 6 8 8 2 8 6 4 2 1 2 Insert Air Screen Slide Into Position Outdoor Air Hood CRBARHOD001A00 Relief Hood Ordered ...

Page 7: ...ve and save the 12 pin jumper plug from the unit wiring harness See Fig 6 Insert the EconoMi er 2 plug into the unit wiring harness plug See Fig 6 NOTE The 12 pin jumper plug should be saved for future use in the event that the EconoMi er2 is removed from the unit The jumper plug is not needed as long as the EconoMi er 2 is installed 9 Install the provided bottom panel with the horizontal return d...

Page 8: ... 19 illustrates the installed barometric hood parts Fig 19 Installed Barometric Hood Side View and Isometric View For horizontal return and field installed economizer install the economizer as follows 1 Install the field provided horizontal ductwork onto the unit Duct height must be at least 19 1 2 inches high however the duct can be no taller than the top of the relief opening in the bottom panel...

Page 9: ...e 12 pin economizer harness pin 5 and 6 are used to connect the OAT sensor to the PremierLink board INDOOR AIR QUALITY CO2 SENSOR Mount the optional indoor air quality CO2 sensor according to manufacturer specifications A separate field supplied transformer must be used to power the CO2 sensor Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller Refer to the Premie...

Page 10: ... 11 12 13 14 15 16 17 GRN DDC CONTROL RMTOCC CMPSAFE FSD SFS NOT USED RED PNK RED WHT RED BLU RED YEL RED 18 19 20 21 22 23 24 25 26 ORN RED ENTH POSITION 0 POSITION 1 1 LEN CCN 4 NO ACTION LOAD FACTORY DEFAULTS ON POWERUP 0 1 1234 ECONO J9 J7 NOT USED J8 FAN GRN CMP1 YEL CMP2 BLU HS1 WHT HS2 HS3 EXH RVS PNK ORNRED PWR RELAYS RED CUT FOR DUAL TRANSFORMER EQUIPMENT BLK WHT RED DISCRETE J4 0 20mA IN...

Page 11: ...eturn air enthalpy sensor to the enthalpy controller 2 At the enthalpy control remove the factory installed resistor from the SR and terminals 3 Connect the field supplied RED wire to spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller Connect the BLK wire to S spade connector on the return air enthalpy sensor and the SR ter minal on the enthalpy contro...

Page 12: ...EQUIRES BOTH AN ENTHALPY SWITCH RECEIVER 33CSENTHSW AND AN ENTHALPY SENSOR 33CSENTSEN The enthalpy switch receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy The enthalpy sensor is mounted in the return airstream and calculates the enthalpy of the indoor air For differential enthalpy control the enthalpy switch receiver energizes the HI enthalpy relay output when the o...

Page 13: ...set point has not been reached By the time the CO2 level reaches the set point the damper will be at maximum ventilation and should maintain the set point In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to remove contaminants during unoccupied periods ...

Page 14: ... cooling occurs when there is no call from the thermostat except G Pre cooling is defined as the economizer modulates to provide 70 F supply air When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following 3 routines The 3 control routines are bas...

Page 15: ... or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step 4 4 Make sure the control signal positive is connected to Wire No 3 and control signal negative is connected to Wire No 1 Most control problems are caused by reversing these two wires Verify that the reversing switch is all the CCW or CW Drives to Control...

Page 16: ...st 30 seconds The SPT SAT and OAT inputs must have valid readings OAT must be less than 75 F OAT must be less than SPT Enthalpy must be LOW may be jumpered if an enthalpy sensor is not available Economizer position is NOT forced When free cooling is available the outdoor air damper is positioned through the use of a Proportional Integral Derivative Loop PID control process to provide a calculated ...

Page 17: ... the number of heat stages is calculated otherwise the required number of heat stages will be set to 0 If the PremierLink controller determines that heat stages are re quired the economizer damper will be moved to minimum posi tion if occupied and closed if unoccupied Staging should be as follows IF HEATING PID STAGES 2 HEAT STAGES 1 50 capacity will energize HS1 HEAT STAGES 2 100 capacity will en...

Page 18: ......

Page 19: ......

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480313 01 Printed in U S A Form IIK CRECOMZR72 03 Pg 20 8 21 Replaces IIK CRECOMZR72 02 2021 Carrier ...

Reviews: