9

Fig. 20 — Relief Damper

Fig. 21 — Installing CRBARHOD001A00 Over Relief 

Damper

Fig. 22 — CRBARHOD001A00 Hood Sides and Top

Accessories

SUPPLY AIR TEMPERATURE SENSOR (SAT) 
When the unit is supplied with a factory-mounted PremierLink™

control, the supply air temperature (SAT) sensor (33ZCENSAT) is

factory supplied and wired. The wiring is routed from the Premier

-

Link control over the control box, through a grommet, into the fan

section, down along the back side of the fan, and along the fan

deck over to the supply-air opening.

The SAT sensor is wire tied to the supply air opening (on the hori

-

zontal opening end) in its shipping position. Remove the sensor

for installation. Re-position the sensor in the flange of the supply

air opening or in the supply air duct (as required by local codes).

Drill  or  punch  a  1/2  in.  hole  in  the  flange  or  duct.  Use  two

field-supplied, self-drilling screws to secure the sensor probe in a

horizontal orientation.

NOTE: The sensor must be mounted in the discharge airstream

downstream of the cooling coil and any heating devices. Be sure

the probe tip does not come in contact with any of the unit or heat

surfaces.
OUTDOOR AIR TEMPERATURE SENSOR (OAT) 
When the unit is supplied with a factory-mounted PremierLink™

control,  the  outdoor  air  temperature  sensor  (OAT)  is  factory

supplied  and  wired.  The  pink  and  violet  wires  of  the  12-pin

economizer harness (pin 5 and 6) are used to connect the OAT

sensor to the PremierLink board. 
INDOOR AIR QUALITY (CO

2

) SENSOR 

Mount the optional indoor air quality (CO

2

) sensor according to

manufacturer specifications. 

A separate field-supplied transformer must be used to power the

CO

2

 sensor. 

Wire the CO

2

 sensor to the COM and IAQI terminals of J5 on the

PremierLink  controller.  Refer  to  the  PremierLink  Installation,

Start-up, and Configuration Instructions for detailed wiring and

configuration information. 
ENTHALPY SENSORS AND CONTROL 
Two  different  sets  of  enthalpy  sensors  can  be  used  with  the

PremierLink  control.  For  single  enthalpy  control,  either  the

HH57AC077  or 33CENTHSW outdoor enthalpy sensor can be

used.  For  differential  enthalpy  control,  either  the  HH57AC077

and  HH57AC078  sensors  or  the  33CSENTHSW  and

33CSENTSEN sensors are used. Refer to the appropriate sections

below for sensor installation.
OUTDOOR  AIR  ENTHALPY  SENSOR/ENTHALPY

CONTROLLER (HH57AC077) 
The  enthalpy  control  (HH57AC077)  is  supplied  as  a

field-installed accessory to be used with the economizer damper

control  option.  The  outdoor  air  enthalpy  sensor  is  part  of  the

enthalpy  control.  (See  Fig.  23.)  The  separate  field-installed

accessory return air enthalpy sensor (HH57AC078) is required for

differential enthalpy control. (See Fig. 24.)

Unit

Outside

Air Hood

Min

19 1/2"

Relief 

Opening

Return 

Duct

16"

1"

18 3/8"

Outdoor Air
Hood

CRBARHOD001A00
Relief Hood
Ordered Separately

Field Supplied

Return Duct

Relief Damper

Min 19-1/2

*Blade Bracket

*Provided with Economizer

Summary of Contents for CRECOMZR072A01

Page 1: ...to the equipment and any other safety precautions that apply Follow all safety codes Wear safety glasses and work gloves Use care in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER...

Page 2: ...d relief air damper leakage requirements and when used with Carrier ComfortLink RTU Open Premierlink SystemVu or I O Flex control systems meet IECC 2015 section C403 2 4 7 for Fault Detection and Diagnostic requirements Note IECC 2015 section C403 2 4 7 1 requires differential return air sensor which must be ordered separately Outside air and return air volume dampers are AMCA Air Movement and Con...

Page 3: ...It is important that the damper be perfectly square in the unit 6 Reinstall the left side corner post on to the unit NOTE The corner post will sit behind the economizer shroud flange See Fig 5 Screw through the corner post and through the economizer shroud See Fig 3 and 5 7 Insert provided screw through the bottom left rear of the economizer and into the unit base See Fig 3 Reinstall the unit s le...

Page 4: ... 9 10 11 12 WHT WHT YEL PINK VIO BLK BLK BLK BLU RED RED RED 73 73 73 69 69 69 69 69 73 To Optional Enthalpy Sensor 500 OHM Resistor Actuator Outside Air Sensor Units Left Side Panel Left Front Corner Post Screw Economizer Flange Economizer Shroud Jumper Plug Remove Harness Plug From Economizer Harness Plug From HVAC ...

Page 5: ...ood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is perpendicular to the hood and each filter support Secure using the screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to the hood top Item 3 k Install outdoor air screens by sliding them into each of the four spaces created by the hood filter...

Page 6: ... 3 3 Side Retainer 2 4 Hood Top 1 5 Left Hood Side 1 6 Right Hood Side 1 7 Top Diverters 2 8 Deflector 3 Apply seal strip to the front of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange 7 7 3 5 6 8 8 2 8 6 4 2 1 2 Insert Air Screen Slide Into Position Outdoor Air Hood CRBARHOD001A00 Relief Hood Ordered ...

Page 7: ...ve and save the 12 pin jumper plug from the unit wiring harness See Fig 6 Insert the EconoMi er 2 plug into the unit wiring harness plug See Fig 6 NOTE The 12 pin jumper plug should be saved for future use in the event that the EconoMi er2 is removed from the unit The jumper plug is not needed as long as the EconoMi er 2 is installed 9 Install the provided bottom panel with the horizontal return d...

Page 8: ... 19 illustrates the installed barometric hood parts Fig 19 Installed Barometric Hood Side View and Isometric View For horizontal return and field installed economizer install the economizer as follows 1 Install the field provided horizontal ductwork onto the unit Duct height must be at least 19 1 2 inches high however the duct can be no taller than the top of the relief opening in the bottom panel...

Page 9: ...e 12 pin economizer harness pin 5 and 6 are used to connect the OAT sensor to the PremierLink board INDOOR AIR QUALITY CO2 SENSOR Mount the optional indoor air quality CO2 sensor according to manufacturer specifications A separate field supplied transformer must be used to power the CO2 sensor Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller Refer to the Premie...

Page 10: ... 11 12 13 14 15 16 17 GRN DDC CONTROL RMTOCC CMPSAFE FSD SFS NOT USED RED PNK RED WHT RED BLU RED YEL RED 18 19 20 21 22 23 24 25 26 ORN RED ENTH POSITION 0 POSITION 1 1 LEN CCN 4 NO ACTION LOAD FACTORY DEFAULTS ON POWERUP 0 1 1234 ECONO J9 J7 NOT USED J8 FAN GRN CMP1 YEL CMP2 BLU HS1 WHT HS2 HS3 EXH RVS PNK ORNRED PWR RELAYS RED CUT FOR DUAL TRANSFORMER EQUIPMENT BLK WHT RED DISCRETE J4 0 20mA IN...

Page 11: ...eturn air enthalpy sensor to the enthalpy controller 2 At the enthalpy control remove the factory installed resistor from the SR and terminals 3 Connect the field supplied RED wire to spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller Connect the BLK wire to S spade connector on the return air enthalpy sensor and the SR ter minal on the enthalpy contro...

Page 12: ...EQUIRES BOTH AN ENTHALPY SWITCH RECEIVER 33CSENTHSW AND AN ENTHALPY SENSOR 33CSENTSEN The enthalpy switch receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy The enthalpy sensor is mounted in the return airstream and calculates the enthalpy of the indoor air For differential enthalpy control the enthalpy switch receiver energizes the HI enthalpy relay output when the o...

Page 13: ...set point has not been reached By the time the CO2 level reaches the set point the damper will be at maximum ventilation and should maintain the set point In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to remove contaminants during unoccupied periods ...

Page 14: ... cooling occurs when there is no call from the thermostat except G Pre cooling is defined as the economizer modulates to provide 70 F supply air When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following 3 routines The 3 control routines are bas...

Page 15: ... or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step 4 4 Make sure the control signal positive is connected to Wire No 3 and control signal negative is connected to Wire No 1 Most control problems are caused by reversing these two wires Verify that the reversing switch is all the CCW or CW Drives to Control...

Page 16: ...st 30 seconds The SPT SAT and OAT inputs must have valid readings OAT must be less than 75 F OAT must be less than SPT Enthalpy must be LOW may be jumpered if an enthalpy sensor is not available Economizer position is NOT forced When free cooling is available the outdoor air damper is positioned through the use of a Proportional Integral Derivative Loop PID control process to provide a calculated ...

Page 17: ... the number of heat stages is calculated otherwise the required number of heat stages will be set to 0 If the PremierLink controller determines that heat stages are re quired the economizer damper will be moved to minimum posi tion if occupied and closed if unoccupied Staging should be as follows IF HEATING PID STAGES 2 HEAT STAGES 1 50 capacity will energize HS1 HEAT STAGES 2 100 capacity will en...

Page 18: ......

Page 19: ......

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480313 01 Printed in U S A Form IIK CRECOMZR72 03 Pg 20 8 21 Replaces IIK CRECOMZR72 02 2021 Carrier ...

Reviews: