Table 5 — PremierLink™ Controller Sensor Usage

LEGEND

NOTES:

1. CO

2

 Sensors (Optional)

2. OAT  (Outdoor-Air  Thermistor)  included  with  EconoMi$er

accessory.  Space      sensor  required  when  using  PremierLink

controls

INSTALLATION

Vertical Installation

These  economizers  are  designed  to  work  in  both  vertical  and

horizontal applications. For a vertical installation:

1. Turn off unit’s power supply and install lockout tag. 

2. Prepare the unit for economizer installation: 

 a. For units with 2 position damper installed, remove the

outside  air  hood.  Unplug  the  damper  actuator  and

remove assembly from unit.

 b. For  units  with  manual  damper  installed,  remove  the

manual damper and hood.

3. Remove the upper panel and bottom panel (provided with the

HVAC  unit)  on  the  end  of  the  unit  to  expose  the  return

section. Save the screws for later when replacing the bottom

panel.  The  panels  shipped  with  the  unit  can  be  discarded.

(See Fig. 1.)

4. Remove the unit’s left side corner post and left side panel to

allow for easy economizer installation. (See Fig. 2.

.

Fig. 1 — Upper and Bottom Panel on End of Unit

Fig. 2 — Unit Left Side Panel and Corner Post

5. Install economizer, with shroud attached as shown in Fig. 2,

into the return air section of the unit. Be careful not to pinch

the wires during installation. The bottom of economizer will

rest on the base of the unit. (See Fig. and 4.)

NOTE: The outside air damper is rated to meet ASHRAE require

-

ments  for  leakage. It  is  important  that  the  damper  be perfectly

square in the unit.

6. Reinstall the left side corner post on to the unit. 
NOTE: The corner post will sit behind the economizer shroud

flange. (See Fig. 5.) Screw through the corner post and through

the economizer shroud. (See Fig. and 5.)

7. Insert  provided  screw  through  the  bottom  left  rear  of  the

economizer and into the unit base. (See Fig. 3.) Reinstall the

unit’s left side panel. 

 

Fig. 3 — Side View

8. Before the economizer is secured in place on the right hand

side, remove and save the 12-pin jumper plug from the unit

wiring harness. (See Fig. 6.) Insert the economizer plug into

the unit wiring harness plug. (See Fig. 6.)

DESIRED CONTROL 

METHOD

FIELD-INSTALLED DRY BULB 

ACCESSORY EconoMi$er

®

2

FACTORY-INSTALLED DRY BULB 

SENSOR EconoMi$er

®

2

FACTORY-INSTALLED ENTHALPY 

SENSOR EconoMi$er

®

2

SINGLE DRY BULB 

TEMPERATURE 

CONTROL

NONE: Outside air dry bulb sensor is 

factory-installed

NONE: Outside air dry bulb sensor is 

factory-installed

N/A

DIFFERENTIAL DRY 

BULB TEMPERATURE 

CONTROL

(1) CRTEMPSN001A00 or

(1) 33ZCT55SPT, T56, T59 or 

(1) 33PILOT-01

(1) CRTEMPSN001A00 or 

(1) 33ZCT55SPT, T56, T59 or 

(1) 33PILOT-01

N/A

SINGLE ENTHALPY

(1) 33CSENTHSW

(1) 33CSENTHSW

NONE: Outside air dry bulb sensor is 

factory-installed

DIFFERENTIAL 

ENTHALPY

(1) 33CSENTHSW OR 

(1) 33CSENTSEN

(1) 33CSENTHSW and 

(1) 33CSENTSEN

Outside Air Enthalpy sensor is factory-

installed plus (1) 33CSENTSEN

N/A

— Not available

Upper End Panel
Shipped On 
Base Unit

Bottom Panel
Shipped On 
Base Unit

Indoor Fan Panel

Unit’s Left
Side Panel

Economizer

Shroud

Left
Corner
Post

EconoMi$er X

EconoMi$er 2

Shroud

Screw

Economizer

To Base

Economizer
Actuator

Summary of Contents for CRECOMZR072A01

Page 1: ...to the equipment and any other safety precautions that apply Follow all safety codes Wear safety glasses and work gloves Use care in handling and installing this accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER...

Page 2: ...d relief air damper leakage requirements and when used with Carrier ComfortLink RTU Open Premierlink SystemVu or I O Flex control systems meet IECC 2015 section C403 2 4 7 for Fault Detection and Diagnostic requirements Note IECC 2015 section C403 2 4 7 1 requires differential return air sensor which must be ordered separately Outside air and return air volume dampers are AMCA Air Movement and Con...

Page 3: ...It is important that the damper be perfectly square in the unit 6 Reinstall the left side corner post on to the unit NOTE The corner post will sit behind the economizer shroud flange See Fig 5 Screw through the corner post and through the economizer shroud See Fig 3 and 5 7 Insert provided screw through the bottom left rear of the economizer and into the unit base See Fig 3 Reinstall the unit s le...

Page 4: ... 9 10 11 12 WHT WHT YEL PINK VIO BLK BLK BLK BLU RED RED RED 73 73 73 69 69 69 69 69 73 To Optional Enthalpy Sensor 500 OHM Resistor Actuator Outside Air Sensor Units Left Side Panel Left Front Corner Post Screw Economizer Flange Economizer Shroud Jumper Plug Remove Harness Plug From Economizer Harness Plug From HVAC ...

Page 5: ...ood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is perpendicular to the hood and each filter support Secure using the screws provided i Apply seal strip to top diverters Item 7 j Secure top diverters Item 7 to the hood top Item 3 k Install outdoor air screens by sliding them into each of the four spaces created by the hood filter...

Page 6: ... 3 3 Side Retainer 2 4 Hood Top 1 5 Left Hood Side 1 6 Right Hood Side 1 7 Top Diverters 2 8 Deflector 3 Apply seal strip to the front of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange Apply seal strip to the back of this flange 7 7 3 5 6 8 8 2 8 6 4 2 1 2 Insert Air Screen Slide Into Position Outdoor Air Hood CRBARHOD001A00 Relief Hood Ordered ...

Page 7: ...ve and save the 12 pin jumper plug from the unit wiring harness See Fig 6 Insert the EconoMi er 2 plug into the unit wiring harness plug See Fig 6 NOTE The 12 pin jumper plug should be saved for future use in the event that the EconoMi er2 is removed from the unit The jumper plug is not needed as long as the EconoMi er 2 is installed 9 Install the provided bottom panel with the horizontal return d...

Page 8: ... 19 illustrates the installed barometric hood parts Fig 19 Installed Barometric Hood Side View and Isometric View For horizontal return and field installed economizer install the economizer as follows 1 Install the field provided horizontal ductwork onto the unit Duct height must be at least 19 1 2 inches high however the duct can be no taller than the top of the relief opening in the bottom panel...

Page 9: ...e 12 pin economizer harness pin 5 and 6 are used to connect the OAT sensor to the PremierLink board INDOOR AIR QUALITY CO2 SENSOR Mount the optional indoor air quality CO2 sensor according to manufacturer specifications A separate field supplied transformer must be used to power the CO2 sensor Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controller Refer to the Premie...

Page 10: ... 11 12 13 14 15 16 17 GRN DDC CONTROL RMTOCC CMPSAFE FSD SFS NOT USED RED PNK RED WHT RED BLU RED YEL RED 18 19 20 21 22 23 24 25 26 ORN RED ENTH POSITION 0 POSITION 1 1 LEN CCN 4 NO ACTION LOAD FACTORY DEFAULTS ON POWERUP 0 1 1234 ECONO J9 J7 NOT USED J8 FAN GRN CMP1 YEL CMP2 BLU HS1 WHT HS2 HS3 EXH RVS PNK ORNRED PWR RELAYS RED CUT FOR DUAL TRANSFORMER EQUIPMENT BLK WHT RED DISCRETE J4 0 20mA IN...

Page 11: ...eturn air enthalpy sensor to the enthalpy controller 2 At the enthalpy control remove the factory installed resistor from the SR and terminals 3 Connect the field supplied RED wire to spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller Connect the BLK wire to S spade connector on the return air enthalpy sensor and the SR ter minal on the enthalpy contro...

Page 12: ...EQUIRES BOTH AN ENTHALPY SWITCH RECEIVER 33CSENTHSW AND AN ENTHALPY SENSOR 33CSENTSEN The enthalpy switch receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy The enthalpy sensor is mounted in the return airstream and calculates the enthalpy of the indoor air For differential enthalpy control the enthalpy switch receiver energizes the HI enthalpy relay output when the o...

Page 13: ...set point has not been reached By the time the CO2 level reaches the set point the damper will be at maximum ventilation and should maintain the set point In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to remove contaminants during unoccupied periods ...

Page 14: ... cooling occurs when there is no call from the thermostat except G Pre cooling is defined as the economizer modulates to provide 70 F supply air When free cooling is available the PremierLink control will control the compressors and economizer to provide a supply air temperature determined to meet the Y1 and Y2 calls from the thermostat using the following 3 routines The 3 control routines are bas...

Page 15: ... or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step 4 4 Make sure the control signal positive is connected to Wire No 3 and control signal negative is connected to Wire No 1 Most control problems are caused by reversing these two wires Verify that the reversing switch is all the CCW or CW Drives to Control...

Page 16: ...st 30 seconds The SPT SAT and OAT inputs must have valid readings OAT must be less than 75 F OAT must be less than SPT Enthalpy must be LOW may be jumpered if an enthalpy sensor is not available Economizer position is NOT forced When free cooling is available the outdoor air damper is positioned through the use of a Proportional Integral Derivative Loop PID control process to provide a calculated ...

Page 17: ... the number of heat stages is calculated otherwise the required number of heat stages will be set to 0 If the PremierLink controller determines that heat stages are re quired the economizer damper will be moved to minimum posi tion if occupied and closed if unoccupied Staging should be as follows IF HEATING PID STAGES 2 HEAT STAGES 1 50 capacity will energize HS1 HEAT STAGES 2 100 capacity will en...

Page 18: ......

Page 19: ......

Page 20: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480313 01 Printed in U S A Form IIK CRECOMZR72 03 Pg 20 8 21 Replaces IIK CRECOMZR72 02 2021 Carrier ...

Reviews: