Fig. 14 - Enthalpy Control Sensor, 

Dimensions and DIP Switch Location

Table 9 - Enthalpy Control Sensor 

Wiring Terminations

a

Table 10 - Enthalpy Control Sensor DIP Switch

Terminal

Type

Description

Nbr

Label

1

S─BUS

S─BUS

S─Bus Communications

(Enthalpy Control Sensor Bus)

2

S─BUS

S─BUS

S─Bus Communications

(Enthalpy Control Sensor Bus)

Use

DIP Switch Positions for Switches 1,2, & 3

1

2

3

DA

a

OFF

ON

OFF

RA

b

ON

OFF

OFF

OA

c

OFF

OFF

OFF

a     DA = Discharge Air or Supply Sensor

b     RA = Return Air

c     OA = Outside Air

OPERATION

Cooling, Unit with EconoMi$er X

For Occupied mode operation of EconoMi$er X, here must be a 24-v 

signal at terminals R and OCC (provided through PL6-3 from the unit’s 

IFC coil).  Removing the signal at OCC places the EconoMi$er X con-

trol in Unoccupied mode.
During Occupied mode operation, indoor fan operation will be accom-

panied by economizer dampers moving to Minimum Position setpoint 

for ventilation. If indoor fan is off, dampers will close.  During Unoc-

cupied mode operation, dampers will remain closed unless a Cooling 

(by free cooling) or DCV demand is received.
When free cooling using outside air is not available, the unit cooling 

sequence will be controlled directly by the space thermostat.  Outside 

air damper position will be closed or Minimum Position as determined 

by Occupancy mode and fan signal.

When free cooling is available as determined by the appropriate change-

over command (dry bulb, outdoor enthalpy, differential dry bulb or dif

-

ferential enthalpy), a call for cooling (Y1 closes at the thermostat) will 

cause the economizer control to modulate the dampers open and closed 

to maintain the unit supply air temperature at 50 to 55

o

F.  Compressor 

will not run.
During free cooling operation, a supply air temperature (SAT) above 

50

o

F will cause the dampers to modulate between Minimum Position 

setpoint and 100% open.  With SAT from 50

o

F to 45

o

F, the dampers will 

maintain at the Minimum Position setting.  With SAT below 45

o

F, the 

outside air dampers will be closed.  When SAT rises to 48

o

F, the damp

-

ers will re-open to Minimum Position setting.
Should 100% outside air not be capable of satisfying the space tempera-

ture, space temperature will rise until Y2 is closed.  The economizer 

control will call for compressor operation.  Dampers will modulate to 

maintain SAT at 50 to 55

o

F concurrent with Compressor 1 operation.  

The Low Ambient Lockout Thermostat will block compressor operation 

with economizer operation below 42

o

F outside air temperature.

When space temperature demand is satisfied (thermostat Y1 opens), the 

dampers will return to Minimum Damper position if indoor fan is run-

ning or fully closed if fan is off.

If accessory power exhaust is installed, the power exhaust fan motors 

will be energized by the economizer control as the dampers open above 

the EXH1 SET setpoint and will be-energized as the dampers close 

below the EXH1 SET setpoint.
Damper movement from full closed to full open (or vice versa) will take 

between 1-1/2 and 2-1/2 minutes.

Heating with EconoMi$er X

During Occupied mode operation, indoor fan operation will be ac-

companied by economizer dampers moving to Minimum Position 

setpoint for ventilation.  If indoor fan is off, dampers will close.  During 

Unoccupied mode operation, dampers will remain closed unless a DCV 

demand is received.

When the room temperature calls for heat (W1 closes), the heating 

controls are energized.

Demand Controlled Ventilation

If a field-installed CO

2

 sensor is connected to the EconoMi$er X 

control, a Demand controlled Ventilation strategy will operate automati-

cally.  As the CO

2

 level in the space increases above the setpoint (on 

the EconoMi$er X controller), the minimum position of the dampers 

will be increased proportionally, until the Maximum Ventilation setting 

is reached. As the space CO

2

 level decreases because of the increase in 

fresh air, the outdoor damper will follow the higher demand condition 

from the DCV mode or from the free cooling mode.
DCV operation is available in Occupied and Unoccupied periods with 

EconoMi$er X.  However, a control modification will be required on the 

48TC units to implement the Unoccupied period function.

Summary of Contents for CRECOMZR067A00

Page 1: ...entilation is supported Units displaying 17th position of the model number to indicate that the unit is equipped with the factory installed VFD Variable Frequency Drive option for 2 speed indoor fan control The VFD option is required for units equipped with EconoMi er X For detailed information on the VFD see the Variable Frequency Drive VFD Installation Setup and Troubleshooting Supplement The Ec...

Page 2: ...y installed outdoor dry bulb temperature sensor with accessory enthalpy sensor HH57AC081 See Fig 1 12 Remove the indoor fan motor access panel See Fig 9 13 The supply air temperature sensor looks like an eyelet terminal with wires running to it The sensor is located on the crimp end and is sealed from moisture Mount the supply air temperature sensor provided to the lower left section of the indoor...

Page 3: ... 43 19 05 29 5 55 lb CRECOMZR069A00 40 37 22 28 24 48 36 27 80lb CRECOMZR071A00 52 92 27 03 33 41 49 92 98lb NOTE The CRECOMZR071A00 hood has 2 aluminum filters and a hood filter divider that installs between the filters See Fig 5A Fig 5 EconoMi er X Installed in HVAC Unit 3 to 6 Ton Shown Fig 4A Hood for Extra Large Cabinet Hood Filter Divider HVAC Unit Filters Insert Screw in EconoMi er X Flange...

Page 4: ...xhaust instructions instead 16 Install the EconoMi er X hood over the EconoMi er X Use screws provided See Fig 10 17 The W7220 EconoMi er X controller is shipped mounted to a bracket Install the controller bracket in the top left corner of the unit control box as shown in wiring diagram Fig 8 Screw in place through pre punched holes 18 Connect the plugs coming from the controller as shown in wirin...

Page 5: ...3 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus Press the Up arrow button to move to the previous menu Press the Down arrow button to move to the next menu Press the Enter button to display the first item in the currently displayed menu Press the Menu Up ...

Page 6: ... sensor Displays _ _ _ o F if not connected short or out of range DA TEMP _ _ _o F 0 to 140o F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _o F if sensor sends invalid value if not con nected short or out of range OA TEMP _ _ _o F 40 to 140o F Displays measured value of outdoor air temperature Displays _ _ _o F if sensor sends invalid va...

Page 7: ...a is only set if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32o F 0 to 50o F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan settings are required 50 0 to 100 increment by 1 Setpoint for OA damper position when ex...

Page 8: ...or an out of calibration temperature sensor RA H CAL 0 RH 10 RH Allows for operator to adjust for an out of calibration humidity sensor DA T CA 0 0o F 2 5o F Allows for the operator to adjust for an out of calibration temperature sensor CHECKOUT DAMPER VMIN HS n a n a Positions damper to VMIN position DAMPER VMAX HS n a n a Positions damper to VMAX position DAMPER OPEN n a n a Position damper to t...

Page 9: ...and Terminal Blocks Time out and Screen Saver When no buttons have been pressed for 10 minutes the LCD displays a screen saver which cycles through the Status items Each Status item displays in turn and cycles to the next item after 5 seconds Label Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity insensitive connections OAT OAT 20k NTC and COM ...

Page 10: ...o F Enthalpy btu lb da Point P1 Point P2 Temp o F Humidity RH Temp o F Humidity RH ES1 80 0 60 0 28 0 80 0 36 8 66 3 80 1 ES2 75 0 57 0 26 0 75 0 39 6 63 3 80 0 ES3 70 0 54 0 24 0 70 0 42 3 59 7 81 4 ES4 65 0 51 0 22 0 65 0 44 8 55 7 84 2 ES5 60 0 48 0 20 0 60 0 46 9 51 3 88 5 HL 86 0 66 0 32 4 86 0 38 9 72 4 80 3 Fig 13 shows the 5 current boundaries There is also a high limit boundary for differ...

Page 11: ...dampers will be closed When SAT rises to 48o F the damp ers will re open to Minimum Position setting Should 100 outside air not be capable of satisfying the space tempera ture space temperature will rise until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at 50 to 55o F concurrent with Compressor 1 operation The Low Ambient Lockout The...

Page 12: ... power returns above 18 Vac Alarms The Economizer module provides alarm messages that display on the 2 line LCD NOTE Upon power up the module waits several seconds before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational If one or more alarms are present and there has been no keypad activity for at least 5 minutes the Alarms menu display...

Page 13: ...I am using enthalpy sensors Why did the control ask me to input a dry bulb changeover temperature In the even the humidity sensor in the enthalpy sensors fails the backup algorithm in the control is to default to the temperature sensor in the enthalpy sensor In checkout the outdoor damper closes when I command it to open Check the actuator linkage or rotation In the CHECKOUT mode the outdoor dampe...

Page 14: ...n 7310 W Morris St Indianapolis IN Manufacturer reserves the right to discontinue or change at any time specification or designs without notice and without incurring obligations Catalog No IIK CRECOMZR67 01 Edition Date 5 12 Replaces New ...

Reviews: