Table 5 

 Menu Structure

a

 (cont)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and Increment

b

Notes

SETPOINTS

MAT SET

53

o

F

38 to 65

o

F;

increment by 1

Setpoint determines where the economizer will modulate the OA 

damper to maintain the mixed air temperature.

LOW T LOCK

32

o

F

-45 to 80

o

F;

increment by 1

Setpoint determines outdoor temperature when the mechanical cooling 

cannot be turned on. Commonly referred to as the Compressor lockout.

DRYBLB SET

63

o

F

48 to 80

o

F;

increment by 1

Setpoint determines where the economizer will assume outdoor air 

temperature is good for free cooling; e.g.; at 63

o

F unit will economize at 

62

o

F and below and not economize at 64

o

F and above. There is a 2

o

deadband.

ENTH CURVE

ES3

ES1,ES2,ES3,ES4, or

ES5

Enthalpy boundary “curves” for economizing using single enthalpy

DCV SET

1100ppm

500 to 2000ppm;

increment by 100

Displays only if CO

2

 sensor is connected. Setpoint for Demand Control 

Ventilation of space. Above the setpoint, the OA dampers will modulate 

open to bring in additional OA to maintain a space ppm level below the 

setpoint.

MIN POS

4.4 V

2 to 10 Vdc

Displays ONLY if a CO

2

 sensor is NOT connected

VENTMAX  With 2-speed 

fan units VENTMAX L (low 

speed fan) and VENTMAX 

H (high speed fan) settings 

are required

4.4 V

2 to 10 Vdc

or

100 to 9990 cfm

increment by 10

Displays only if a CO

2

 sensor is connected. Used for Vbz (ventilation 

max cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA,OA, and MA). 

In AUTO mode dampers controlled by CFM

VENTMAX L

6 V

VENTMAX H

4.4 V

VENTMIN  With 2-speed 

fan units VENTMIN L (low 

speed fan) and VENTMIN 

H (high speed fan) set

2.8 V

2 to 10 Vdc

or 100 to 9990 cfm

increment by 10

Displays only if a CO

2

 sensor is connected. Used for Ba (ventilation min 

cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA, and MA). Va 

is only set if DCV is used. This is the ventilation for less than maximum 

occupancy of the space. In AUTO mode dampers controlled by CFM.

VENTMIN L

3.7 V

VENTMIN H

2.8 V

ERV OAT SP

32

o

F

0 to 50

o

F;

increment by 1

Only when AUX1 O = ERV

EXH1 SET  With 2-speed 

fan units Exh1 L (low speed 

fan) and Exh1 H (high 

speed fan) settings are 

required

50%

0 to 100%;

increment by 1

Setpoint for OA damper position when exhaust fan 1 is powered by the 

economizer.

Exh1 L

65%

Exh1 H

50%

EXH2 SET  With 2-speed 

fan units Exh2 L (low speed 

fan) and Exh2 H (high 

speed fan) settings are 

required

75%

0 to 100%;

increment by 1

Setpoint for OA damper position when exhaust fan 2 is powered by the 

economizer. Only used when AUX is set to EHX2.

Exh2 L

80%

Exh2 H

75%

SYSTEM

SETUP

INSTALL

01/01/10

Display order = MM/DD/YY

Setting order = DD, MM, then YY.

UNITS DEG

o

F

o

F or 

o

C

Sets economizer controller in degrees Fahrenheit or Celsius

EQUIPMENT

CONV

Conventional or HP

CONV = conventional; HP O/B = Enable Heat Pump mode. Use AUX2 I 

for Heat Pump input from thermostat or controller.

AUX2 I

W

SD/W or HP(O)/HP(B)

In CONV mode: SD + Enables configuration of shutdown (default); W 

= Informs controller that system is in heating mode. In HP O/B mode: 

HP(O) = energize heat pump on Cool (default); HP(B) = energize heat 

pump on heat.

FAN TYPE

2 speed

1 speed/2 speed

Sets the economizer controller for operation of 1 speed or 2 speed 

supply fan.

FAN CFM

5000cfm

100 to 15000 cfm;

increment by 100

This is the capacity of the RTU. The value is found in the Project 

Submittal documents for the specific RTU.

AUX OUT

NONE

NONE

ERV

EXH2

SYS

•  NONE = not configured (output is not used)

•  ERV = Energy Recovery Ventilatio

n

•  EXH2 = second damper position relay closure for second exhaust fan

•  SYS = use output as an alarm signal

OCC

INPUT

INPUT or ALWAYS

When using a setback thermostat with occupancy out (24 Vac), the 24 

Vac is input “INPUT” to the OCC terminal. If no occupancy output from 

the thermostat then change program to “ALWAYS” OR add a jumper 

from terminal R to OCC terminal

Summary of Contents for CRECOMZR067A00

Page 1: ...entilation is supported Units displaying 17th position of the model number to indicate that the unit is equipped with the factory installed VFD Variable Frequency Drive option for 2 speed indoor fan control The VFD option is required for units equipped with EconoMi er X For detailed information on the VFD see the Variable Frequency Drive VFD Installation Setup and Troubleshooting Supplement The Ec...

Page 2: ...y installed outdoor dry bulb temperature sensor with accessory enthalpy sensor HH57AC081 See Fig 1 12 Remove the indoor fan motor access panel See Fig 9 13 The supply air temperature sensor looks like an eyelet terminal with wires running to it The sensor is located on the crimp end and is sealed from moisture Mount the supply air temperature sensor provided to the lower left section of the indoor...

Page 3: ... 43 19 05 29 5 55 lb CRECOMZR069A00 40 37 22 28 24 48 36 27 80lb CRECOMZR071A00 52 92 27 03 33 41 49 92 98lb NOTE The CRECOMZR071A00 hood has 2 aluminum filters and a hood filter divider that installs between the filters See Fig 5A Fig 5 EconoMi er X Installed in HVAC Unit 3 to 6 Ton Shown Fig 4A Hood for Extra Large Cabinet Hood Filter Divider HVAC Unit Filters Insert Screw in EconoMi er X Flange...

Page 4: ...xhaust instructions instead 16 Install the EconoMi er X hood over the EconoMi er X Use screws provided See Fig 10 17 The W7220 EconoMi er X controller is shipped mounted to a bracket Install the controller bracket in the top left corner of the unit control box as shown in wiring diagram Fig 8 Screw in place through pre punched holes 18 Connect the plugs coming from the controller as shown in wirin...

Page 5: ...3 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus Press the Up arrow button to move to the previous menu Press the Down arrow button to move to the next menu Press the Enter button to display the first item in the currently displayed menu Press the Menu Up ...

Page 6: ... sensor Displays _ _ _ o F if not connected short or out of range DA TEMP _ _ _o F 0 to 140o F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _o F if sensor sends invalid value if not con nected short or out of range OA TEMP _ _ _o F 40 to 140o F Displays measured value of outdoor air temperature Displays _ _ _o F if sensor sends invalid va...

Page 7: ...a is only set if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32o F 0 to 50o F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan settings are required 50 0 to 100 increment by 1 Setpoint for OA damper position when ex...

Page 8: ...or an out of calibration temperature sensor RA H CAL 0 RH 10 RH Allows for operator to adjust for an out of calibration humidity sensor DA T CA 0 0o F 2 5o F Allows for the operator to adjust for an out of calibration temperature sensor CHECKOUT DAMPER VMIN HS n a n a Positions damper to VMIN position DAMPER VMAX HS n a n a Positions damper to VMAX position DAMPER OPEN n a n a Position damper to t...

Page 9: ...and Terminal Blocks Time out and Screen Saver When no buttons have been pressed for 10 minutes the LCD displays a screen saver which cycles through the Status items Each Status item displays in turn and cycles to the next item after 5 seconds Label Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity insensitive connections OAT OAT 20k NTC and COM ...

Page 10: ...o F Enthalpy btu lb da Point P1 Point P2 Temp o F Humidity RH Temp o F Humidity RH ES1 80 0 60 0 28 0 80 0 36 8 66 3 80 1 ES2 75 0 57 0 26 0 75 0 39 6 63 3 80 0 ES3 70 0 54 0 24 0 70 0 42 3 59 7 81 4 ES4 65 0 51 0 22 0 65 0 44 8 55 7 84 2 ES5 60 0 48 0 20 0 60 0 46 9 51 3 88 5 HL 86 0 66 0 32 4 86 0 38 9 72 4 80 3 Fig 13 shows the 5 current boundaries There is also a high limit boundary for differ...

Page 11: ...dampers will be closed When SAT rises to 48o F the damp ers will re open to Minimum Position setting Should 100 outside air not be capable of satisfying the space tempera ture space temperature will rise until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at 50 to 55o F concurrent with Compressor 1 operation The Low Ambient Lockout The...

Page 12: ... power returns above 18 Vac Alarms The Economizer module provides alarm messages that display on the 2 line LCD NOTE Upon power up the module waits several seconds before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational If one or more alarms are present and there has been no keypad activity for at least 5 minutes the Alarms menu display...

Page 13: ...I am using enthalpy sensors Why did the control ask me to input a dry bulb changeover temperature In the even the humidity sensor in the enthalpy sensors fails the backup algorithm in the control is to default to the temperature sensor in the enthalpy sensor In checkout the outdoor damper closes when I command it to open Check the actuator linkage or rotation In the CHECKOUT mode the outdoor dampe...

Page 14: ...n 7310 W Morris St Indianapolis IN Manufacturer reserves the right to discontinue or change at any time specification or designs without notice and without incurring obligations Catalog No IIK CRECOMZR67 01 Edition Date 5 12 Replaces New ...

Reviews: