Carrier CRECOMZR067A00 Installation Instructions Manual Download Page 2

2

The  EconoMi$er  X  has  several  field-installed  accessories  available  to 

optimize performance. Refer to Table 4 for authorized parts and power 

exhaust descriptions

INSTALLATION

1.  Turn off unit power supply(s) and install lockout tag.

2.  Remove the existing unit filter access panel. Raise the panel and 

swing the bottom outward. The panel is now disengaged from the 

track and can be removed. (See Fig. 2.)

3.  Remove the indoor coil access panel and discard. (See Fig. 2.)
4.  The box with the EconoMi$er X hood components is shipped with 

the EconoMi$er X. Remove hood from packaging. The hood top 

and sides are shipped factory assembled.

NOTE:

  If  the  power  exhaust  accessory  is  to  be  installed  on  the  unit, 

the hood shipped with the EconoMi$er X will not be used and may be 

discarded. Save the aluminum filter for use in the power exhaust hood 

assembly.

5.  Insert the hood divider between the hood sides. (See Fig. 3) Secure 

hood divider with 2 screws (provided) on each hood side. Screws 

should go through the hood sides into the divider. The hood divider 

is also used as the bottom filter rack for the aluminum filter.  On 

hood for extra large cabinet install filter divider. (See Fig. 4A.)

6.  Set the EconoMi$er X upright. (See Fig. 5.)  
7.  Slide the EconoMi$er X assembly into the rooftop unit. (See Fig. 5). 

On small and large cabinets be sure to engage the rear EconoMi$er 

X flange under the tabs in the return-air opening of the unit base. 

(See Fig. 6)

IMPORTANT:

  These economizer outside air dampers meet ASHRAE 

90.1 leakage requirements and must be installed perfectly square.  

Verify squareness by measuring diagonally across corners of outside 

air damper.  Tol/- 1/32”.

8.  Secure  the  EconoMi$er  X  to  unit  along  side  and  bottom  flanges 

using the screws provided.

9.  Remove the tape securing the relief dampers in place.

10.  Remove  and  save  the  12-pin  jumper  plug  from  the  unit  wiring 

harness  (located  in  the  upper  left  corner  of  the  unit).  Insert  the 

EconoMi$er X plug into the unit wiring harness.  Refer to Fig. 7 and 

8 for wiring diagram.

NOTE: The 12-pin jumper plug should be saved for future use, in the 

event that the EconoMi$er X is removed from the unit. The jumper plug 

is not needed as long as the EconoMi$er X is installed.

11.  If EconoMi$er X will be operating under enthalpy control, replace 

the  factory  installed  outdoor  dry  bulb  temperature  sensor  with 

accessory enthalpy sensor HH57AC081.  (See Fig. 1.)

12.  Remove the indoor fan motor access panel. (See Fig. 9.)
13.  The supply air temperature sensor looks like an eyelet terminal with 

wires running to it. The sensor is located on the “crimp end” and 

is sealed from moisture. Mount the supply air temperature sensor 

(provided) to the lower left section of the indoor fan blower housing. 

(See Fig. 10.) Use the screw provided and use existing hole. Connect 

the violet and pink wires to the corresponding connections on the 

supply air temperature sensor. (See Fig. 8.)

Table 3 - EconoMi$er X Sensor Usage

APPLICATION

ECONOMI$ER X WITH OUTDOOR AIR

DRY BULB SENSOR

Accessories Required

Outdoor Air

Dry Bulb

None.  The outdoor air dry bulb sensor

 is factory installed

Single

Enthalpy

HH57AC081

Differential

Enthalpy

HH57AC081

CO

2

 for

DCV Control

Using a

Wall-Mounted

CO

2

 Sensor

33ZCSENCO2

or

CGCDXSEN004A00

CO

2

 for 

DCV Control

Using a 

Duct-Mounted

CO

2

 Sensor

33ZCSENCO2 or

CGCDXSEN004A00†

and

33ZCASPCO2 or

CGCDXASP00100**

CRCBDIOX005A00††

OR

†33ZCSENCO2 and CGCDXSEN004A00 are accessory CO2 sensors.

**33ZCASPCO2 and CGCDXASP00100 are accessory aspirator boxes required for duct-mounted 

applications.

††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 

accessories.

Table 4 - EconoMi$er X Field-Installed 

Accessories

DESCRIPTION

PART NUMBER

Small Cabinet Power Exhaust 208-230 v 1 Ph

CRPWREXH030A01

Small Cabinet Power Exhaust 460 v 3Ph

CRPWREXH021A01

Large Cabinet Power Exhaust 208-230 v 1 Ph

CRPWREXH022A01

Large Cabinet Power Exhaust 460 v 3 Ph

CRPWREXH023A01

Extra Large Cabinet Power Exhaust 208-230 v 1 Ph

CRPWREXH080A00

Extra Large Cabinet Power Exhaust 460 v 3 Ph

CRPWREXH081A00

Outdoor Air Enthalpy Sensor

HH57AC081

Indoor Air Enthalpy Sensor

HH57AC081

Return Air CO

2

 Sensor (4 to 20 mA)

CRCBDIOX005A00

CO

2

 Room Sensor (4 to 20 mA)

33ZCSENCO2 or

CGCDXSEN004A00

Aspirator Box for Duct Mount

CO

2

 Sensor (4 to 20 mA)

33ZCASPCO2 or

CGCDXASP001A00

Space Temperature and CO

2

 Room Sensor

with Override (4 to 20 mA)

33ZCT55CO2

Space Temperature and CO

2

 Room Sensor

with Override and Set Point (4 to 20 mA)

33ZCT56CO2

Fig. 1 - EconoMi$er X Component Locations 

(3 to 6 Ton Shown)

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury and/or 

death. 

Disconnect power supply and install lockout tag before attempting to 

install accessory.

!

Outside Air

Temperature 

Sensor

Actuator

(Hidden)

Wiring 

Harness

Summary of Contents for CRECOMZR067A00

Page 1: ...entilation is supported Units displaying 17th position of the model number to indicate that the unit is equipped with the factory installed VFD Variable Frequency Drive option for 2 speed indoor fan control The VFD option is required for units equipped with EconoMi er X For detailed information on the VFD see the Variable Frequency Drive VFD Installation Setup and Troubleshooting Supplement The Ec...

Page 2: ...y installed outdoor dry bulb temperature sensor with accessory enthalpy sensor HH57AC081 See Fig 1 12 Remove the indoor fan motor access panel See Fig 9 13 The supply air temperature sensor looks like an eyelet terminal with wires running to it The sensor is located on the crimp end and is sealed from moisture Mount the supply air temperature sensor provided to the lower left section of the indoor...

Page 3: ... 43 19 05 29 5 55 lb CRECOMZR069A00 40 37 22 28 24 48 36 27 80lb CRECOMZR071A00 52 92 27 03 33 41 49 92 98lb NOTE The CRECOMZR071A00 hood has 2 aluminum filters and a hood filter divider that installs between the filters See Fig 5A Fig 5 EconoMi er X Installed in HVAC Unit 3 to 6 Ton Shown Fig 4A Hood for Extra Large Cabinet Hood Filter Divider HVAC Unit Filters Insert Screw in EconoMi er X Flange...

Page 4: ...xhaust instructions instead 16 Install the EconoMi er X hood over the EconoMi er X Use screws provided See Fig 10 17 The W7220 EconoMi er X controller is shipped mounted to a bracket Install the controller bracket in the top left corner of the unit control box as shown in wiring diagram Fig 8 Screw in place through pre punched holes 18 Connect the plugs coming from the controller as shown in wirin...

Page 5: ...3 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the Keypad with Menus To use the keypad when working with menus Press the Up arrow button to move to the previous menu Press the Down arrow button to move to the next menu Press the Enter button to display the first item in the currently displayed menu Press the Menu Up ...

Page 6: ... sensor Displays _ _ _ o F if not connected short or out of range DA TEMP _ _ _o F 0 to 140o F Displays when Discharge Air sensor is connected and displays measured discharge temperature Displays _ _ _o F if sensor sends invalid value if not con nected short or out of range OA TEMP _ _ _o F 40 to 140o F Displays measured value of outdoor air temperature Displays _ _ _o F if sensor sends invalid va...

Page 7: ...a is only set if DCV is used This is the ventilation for less than maximum occupancy of the space In AUTO mode dampers controlled by CFM VENTMIN L 3 7 V VENTMIN H 2 8 V ERV OAT SP 32o F 0 to 50o F increment by 1 Only when AUX1 O ERV EXH1 SET With 2 speed fan units Exh1 L low speed fan and Exh1 H high speed fan settings are required 50 0 to 100 increment by 1 Setpoint for OA damper position when ex...

Page 8: ...or an out of calibration temperature sensor RA H CAL 0 RH 10 RH Allows for operator to adjust for an out of calibration humidity sensor DA T CA 0 0o F 2 5o F Allows for the operator to adjust for an out of calibration temperature sensor CHECKOUT DAMPER VMIN HS n a n a Positions damper to VMIN position DAMPER VMAX HS n a n a Positions damper to VMAX position DAMPER OPEN n a n a Position damper to t...

Page 9: ...and Terminal Blocks Time out and Screen Saver When no buttons have been pressed for 10 minutes the LCD displays a screen saver which cycles through the Status items Each Status item displays in turn and cycles to the next item after 5 seconds Label Type Description Top Left Terminal Block MAT MAT 20k NTC and COM Mixed Air Temperature Sensor Polarity insensitive connections OAT OAT 20k NTC and COM ...

Page 10: ...o F Enthalpy btu lb da Point P1 Point P2 Temp o F Humidity RH Temp o F Humidity RH ES1 80 0 60 0 28 0 80 0 36 8 66 3 80 1 ES2 75 0 57 0 26 0 75 0 39 6 63 3 80 0 ES3 70 0 54 0 24 0 70 0 42 3 59 7 81 4 ES4 65 0 51 0 22 0 65 0 44 8 55 7 84 2 ES5 60 0 48 0 20 0 60 0 46 9 51 3 88 5 HL 86 0 66 0 32 4 86 0 38 9 72 4 80 3 Fig 13 shows the 5 current boundaries There is also a high limit boundary for differ...

Page 11: ...dampers will be closed When SAT rises to 48o F the damp ers will re open to Minimum Position setting Should 100 outside air not be capable of satisfying the space tempera ture space temperature will rise until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at 50 to 55o F concurrent with Compressor 1 operation The Low Ambient Lockout The...

Page 12: ... power returns above 18 Vac Alarms The Economizer module provides alarm messages that display on the 2 line LCD NOTE Upon power up the module waits several seconds before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational If one or more alarms are present and there has been no keypad activity for at least 5 minutes the Alarms menu display...

Page 13: ...I am using enthalpy sensors Why did the control ask me to input a dry bulb changeover temperature In the even the humidity sensor in the enthalpy sensors fails the backup algorithm in the control is to default to the temperature sensor in the enthalpy sensor In checkout the outdoor damper closes when I command it to open Check the actuator linkage or rotation In the CHECKOUT mode the outdoor dampe...

Page 14: ...n 7310 W Morris St Indianapolis IN Manufacturer reserves the right to discontinue or change at any time specification or designs without notice and without incurring obligations Catalog No IIK CRECOMZR67 01 Edition Date 5 12 Replaces New ...

Reviews: