
2
The EconoMi$er X has several field-installed accessories available to
optimize performance. Refer to Table 4 for authorized parts and power
exhaust descriptions
INSTALLATION
1. Turn off unit power supply(s) and install lockout tag.
2. Remove the existing unit filter access panel. Raise the panel and
swing the bottom outward. The panel is now disengaged from the
track and can be removed. (See Fig. 2.)
3. Remove the indoor coil access panel and discard. (See Fig. 2.)
4. The box with the EconoMi$er X hood components is shipped with
the EconoMi$er X. Remove hood from packaging. The hood top
and sides are shipped factory assembled.
NOTE:
If the power exhaust accessory is to be installed on the unit,
the hood shipped with the EconoMi$er X will not be used and may be
discarded. Save the aluminum filter for use in the power exhaust hood
assembly.
5. Insert the hood divider between the hood sides. (See Fig. 3) Secure
hood divider with 2 screws (provided) on each hood side. Screws
should go through the hood sides into the divider. The hood divider
is also used as the bottom filter rack for the aluminum filter. On
hood for extra large cabinet install filter divider. (See Fig. 4A.)
6. Set the EconoMi$er X upright. (See Fig. 5.)
7. Slide the EconoMi$er X assembly into the rooftop unit. (See Fig. 5).
On small and large cabinets be sure to engage the rear EconoMi$er
X flange under the tabs in the return-air opening of the unit base.
(See Fig. 6)
IMPORTANT:
These economizer outside air dampers meet ASHRAE
90.1 leakage requirements and must be installed perfectly square.
Verify squareness by measuring diagonally across corners of outside
air damper. Tol/- 1/32”.
8. Secure the EconoMi$er X to unit along side and bottom flanges
using the screws provided.
9. Remove the tape securing the relief dampers in place.
10. Remove and save the 12-pin jumper plug from the unit wiring
harness (located in the upper left corner of the unit). Insert the
EconoMi$er X plug into the unit wiring harness. Refer to Fig. 7 and
8 for wiring diagram.
NOTE: The 12-pin jumper plug should be saved for future use, in the
event that the EconoMi$er X is removed from the unit. The jumper plug
is not needed as long as the EconoMi$er X is installed.
11. If EconoMi$er X will be operating under enthalpy control, replace
the factory installed outdoor dry bulb temperature sensor with
accessory enthalpy sensor HH57AC081. (See Fig. 1.)
12. Remove the indoor fan motor access panel. (See Fig. 9.)
13. The supply air temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located on the “crimp end” and
is sealed from moisture. Mount the supply air temperature sensor
(provided) to the lower left section of the indoor fan blower housing.
(See Fig. 10.) Use the screw provided and use existing hole. Connect
the violet and pink wires to the corresponding connections on the
supply air temperature sensor. (See Fig. 8.)
Table 3 - EconoMi$er X Sensor Usage
APPLICATION
ECONOMI$ER X WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required
Outdoor Air
Dry Bulb
None. The outdoor air dry bulb sensor
is factory installed
Single
Enthalpy
HH57AC081
Differential
Enthalpy
HH57AC081
CO
2
for
DCV Control
Using a
Wall-Mounted
CO
2
Sensor
33ZCSENCO2
or
CGCDXSEN004A00
CO
2
for
DCV Control
Using a
Duct-Mounted
CO
2
Sensor
33ZCSENCO2 or
CGCDXSEN004A00†
and
33ZCASPCO2 or
CGCDXASP00100**
CRCBDIOX005A00††
OR
†33ZCSENCO2 and CGCDXSEN004A00 are accessory CO2 sensors.
**33ZCASPCO2 and CGCDXASP00100 are accessory aspirator boxes required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2
accessories.
Table 4 - EconoMi$er X Field-Installed
Accessories
DESCRIPTION
PART NUMBER
Small Cabinet Power Exhaust 208-230 v 1 Ph
CRPWREXH030A01
Small Cabinet Power Exhaust 460 v 3Ph
CRPWREXH021A01
Large Cabinet Power Exhaust 208-230 v 1 Ph
CRPWREXH022A01
Large Cabinet Power Exhaust 460 v 3 Ph
CRPWREXH023A01
Extra Large Cabinet Power Exhaust 208-230 v 1 Ph
CRPWREXH080A00
Extra Large Cabinet Power Exhaust 460 v 3 Ph
CRPWREXH081A00
Outdoor Air Enthalpy Sensor
HH57AC081
Indoor Air Enthalpy Sensor
HH57AC081
Return Air CO
2
Sensor (4 to 20 mA)
CRCBDIOX005A00
CO
2
Room Sensor (4 to 20 mA)
33ZCSENCO2 or
CGCDXSEN004A00
Aspirator Box for Duct Mount
CO
2
Sensor (4 to 20 mA)
33ZCASPCO2 or
CGCDXASP001A00
Space Temperature and CO
2
Room Sensor
with Override (4 to 20 mA)
33ZCT55CO2
Space Temperature and CO
2
Room Sensor
with Override and Set Point (4 to 20 mA)
33ZCT56CO2
Fig. 1 - EconoMi$er X Component Locations
—
(3 to 6 Ton Shown)
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Disconnect power supply and install lockout tag before attempting to
install accessory.
!
Outside Air
Temperature
Sensor
Actuator
(Hidden)
Wiring
Harness