P89 – De-ice in heat – cut-in temperature (AC only)
Range: -9.5…+8°C / 15...46°F
Default: 0°C / 32°F
The outdoor unit coil temperature in which de-icing will start.
P90 – De-ice in heat – cut-out temperature (AC only)
Range: 2...20°C / 35...68°F
Default: 16°C / 61°F
The outdoor unit coil temperature in which de-icing will stop.
P91 – Compressor delay (AC only)
Range: 0...360 Seconds
Default: 240 Seconds
DIP Switch SW1.5 must be in “OFF” position
– compressor delay enabled!
P98 – Display setpoint only (hide room temperature)
“00”
- Display both setpoint and room temperatures
“01”
- Display only the setpoint temperature
P99 – One or Two setpoints (for cool and for heat)
“00”
- One setpoint for cooling and heating
“01”
- Two setpoints, one for cool and one for heat
P100 – Enable screen dimming
“00”
- Disable dimming
“01”
- Enable dimming