ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
37
Wiring and DIP switch configurations 38 to 40 – FC systems - 4-pipe
Outputs
Config. 38:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Heat valve PID,
Cool valve PID
Config. 39:
4-Pipe, VFS Fan, Cool
valve PID, Floor heating
Config. 40:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Humidifier,
Dehum/Reheat for
Dehumidification
11
Fan high
X
Fan high
12
Fan medium
(or Economizer
(5)
)
Economizer
(5)
(option – SW2.6 ON)
Fan medium
(or Economizer
(5)
)
13
Fan low
X
Fan low
14
Heat element
(2)
(2nd stage heat)
Floor heating
(1st stage heat – no
fan)
Heat element
(2)
(2nd stage heat)
15
X
X
Cool valve
(3)
16
X
Heat valve
(2nd stage heat)
Heat valve
(1st stage heat)
AO1
Cool valve PID
(3)
Cool valve PID
(3)
Humidifier
AO2
Heat valve PID
(1st stage heat)
Fan VFS
Dehumidifier
(4)
(option - See SW2.3)
SW1
SW2
(1)
SW1.1, SW1.2 – Fan speeds:
1 speed (Low):
2 speeds(Low and High):
3 speeds(Low, Medium, and High):
SW1.1 = ON, SW1.2 = OFF
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – 2nd heating stage:
ON = Enable, OFF = Disable
(3)
SW1.5 – Chilled beam option:
ON = Enable chilled beam (fan will not run with 1st stage cooling)
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation:
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in
Wiring terminals and DIP switches
(page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
PID valves: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Cool/Heat valves, Economizer: 110-230 Vac, 0.3A max.