ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
39
Enter Technician Settings mode:
1
Adjust the setpoint temperature to 10ºC or 50ºF.
2
Press and hold the
button for 10 seconds to enter Technician Settings mode. “P01” will appear on
display.
View objects and make adjustments:
•
Use the [Mode] button to step forward between different settings.
•
Use the [Fan] button to step backward between different settings.
•
Press the [On/Off] button to exit Technician Settings and return to normal display.
•
If no button is pressed for 60 seconds, the thermostat will automatically exit Technician Settings and return to
normal display.
•
Use the ▲or ▼button to make adjustments when required.
Technician Settings P1 to P3
Offset for temperature readings calibration
Range: -6…+6°C / -9…+9°F.
Default: 0°C / 0°F.
Note: The offset will influence both internal or external sensors.
P2 – Setpoint limit for cooling
Range: 5…35°C / 41…95°F.
Default: 10°C / 50°F.
Note: The thermostat will stop cooling regardless of the user’s
setpoint
P3 – Setpoint limit for heating
Range: 5…35°C / 41…95°F.
Default: 30°C / 86°F.
Note: The thermostat will stop heating regardless of the user’s
setpoint
Technician Settings
Summary of Contents for ComfortVu Plus TBPL-H
Page 70: ......