Technician Settings P11 to P15
P11 – Window contact delay time
Range: 0…999 seconds.
Default: 600 seconds.
P12 – Door switch (terminals T1,0) polarity
“01”
- Normally open
“00”
- Normally closed
P13 – Door switch delay time
Range: 0…999 seconds.
Default: 180 seconds.
P14 – Enable/Disable Auto change over mode
“00”
- Disable Auto change over mode
“01”
- Enable Auto change over mode
P15 – Motion sensor logic (PIR)
“00”
- Thermostat turns off when unoccupied and back on
when re-occupied.
“01”
- Thermostat turns off when unoccupied and remains
off when re-occupied.
“02”
- Thermostat uses economy setpoints when
occupied.
“03”
- Unoccupancy – Dehumidification logic
(only available with dehumidification configuration – see DIP
switch settings)