FINAL CHECKS

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub–through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and

covers.

3. Tighten service valve stem caps to 1/12–turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in

manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on this

equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for

information.

PURON

R

(R–410A) QUICK REFERENCE GUIDE

S

Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and replacement

components are designed to operate with Puron

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S

Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when

charging into suction line with compressor operating

S

Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low–side retard.

S

Use hoses with 700 psig service pressure rating.

S

Leak detectors should be designed to detect HFC refrigerant.

S

Puron, as with other HFCs, is only compatible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Do not use liquid–line filter driers with rated working pressures less than 600 psig.

S

Do not leave Puron suction line filter driers in line longer than 72 hours.

S

Do not install a suction–line filter drier in liquid line.

S

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S

A factory approved liquid–line filter drier is required on every unit.

S

Do NOT use an R–22 TXV.

S

If indoor unit is equipped with an R–22 TXV or piston metering device sized for R--22 application, it must be changed to a hard

shutoff Puron TXV or properly sized Puron piston metering device.

S

Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter

driers. Evacuate to 500 microns prior to recharging.

S

Do not vent Puron into the atmosphere.

S

Do not use capillary tube coils.

S

Observe all

warnings

,

cautions

, and

bold

text.

Copyright 2013 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Edition Date: 06/13

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 25HBB–C–HCD---03SI

Replaces: 25HBB–C–HCD--- 02SI

25H

B

B

/25H

B

C

/25H

C

D

Summary of Contents for Comfort 25HBB series

Page 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Page 2: ...piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remain...

Page 3: ...for accessory requirements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere...

Page 4: ...braze liquid refrigerant tube to the filter drier A05227 Fig 6 Liquid Line Filter Drier CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation I...

Page 5: ...0010 Fig 9 3 Phase Monitor Control Applies to 3 Phase Units Only Table 3 3 Phase Monitor LED Indicators LED STATUS OFF No call for compressor operation FLASHING Reversed phase ON Normal Connect Contro...

Page 6: ...starting indoor blower motor on high speed When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors should stop NOTE If indoor unit is equipped wi...

Page 7: ...lowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system Refer to Table 5 or 6 for additional subcooling required If the indoor temperature is above 80_...

Page 8: ...item 6 and suction pressure At this intersection note suction line temperature 8 If unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is rea...

Page 9: ...5 3 CAP 30 A 3 CNP 30 A 3 3 CSPH 3012A 3 3 FB4CNF030 TXV 3 FF1ENP030 3 FF1ENP031 3 FX4DN B F 031 5 5 CAP 36 A 5 3 CNP 36 A 3 CSPH 3612A 5 3 FB4CNF036 TXV FV4C FE4A N B F 003 5 5 3 FF1ENP036 5 3 FF1ENP...

Page 10: ...4C FE4A NF002 3 FX4DNF025 CAP 30 A CNP 30 A CSPH 3012A FB4CNF030 TXV FF1ENP030 FF1ENP031 FX4DN B F 031 3 CAP 36 A CNP 36 A CSPH 3612A FB4CNF036 TXV FV4C FE4A N B F 003 FF1ENP036 FF1ENP037 FX4DN B F 03...

Page 11: ...22 23 23 23 23 65 3 7 12 18 19 21 21 22 22 70 7 14 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3...

Page 12: ...ide with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Reviews: