background image

3

Table 1 – Accessory Usage

Accessory

REQUIRED FOR LOW–AMBIENT

COOLING APPLICATIONS

(Below 55

F / 12.8

C)

REQUIRED FOR

LONG LINE APPLICATIONS*

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long–Line Application Guideline

No

Motor Master

Control or

Low Ambient Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Piping and Longline Guideline. .

{

Additional requirement for Low–Ambient Controller (full modulation feature) MotorMaster

r

Control.

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury

or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal.
Use all service ports and open all flow–control devices,

including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4

mm). vertical rise at service valve. Refrigerant tubing lengths

up to 36–in (914.4 mm). may be buried without further special

consideration. Do not bury lines longer than 36 in (914.4 mm).

Outdoor units may be connected to indoor section using accessory

tubing package or field–supplied refrigerant grade tubing of correct

size and condition. For tubing requirements beyond 80 ft,

substantial capacity and performance losses can occur. Following

the recommendations in the

Residential Piping and Long Line

Guideline

will reduce these losses. Refer to Table 1 for accessory

requirements. Refer to Table 2 for field tubing diameters.
There are no buried–line applications greater than 36 in. (914.4

mm)
If refrigerant tubes or indoor coil are exposed to atmosphere, they

must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

Outdoor Unit Connected To Factory Approved Indoor

Unit

Outdoor unit contains approximate system refrigerant charge for

operation with approved AHRI rated indoor unit when connected

by 15 ft (4.57 m) of field–supplied or factory–accessory tubing,

and factory supplied filter drier.

Some indoor units require

additional subcooling to achieve optimal heating performance.

Using Table 5 or 6– Additional Subcooling Required, check

refrigerant charge for maximum efficiency

Refrigerant Tubing and Sweat Connections

Connect vapor tube to fitting on outdoor unit vapor service valves

(see Table 2). Connect liquid tubing to adapter tube on liquid

service valve. Use refrigerant grade tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat–sinking material

such as a wet cloth while brazing.

Remove plastic retainer holding outdoor piston in liquid service

valve, leaving the piston and piston retainer inside the valve.

Connect sweat/flare adapter provided, to valve. (See Fig. 4.)

Connect refrigerant tubing to fittings on outdoor unit vapor and

liquid service valves. Service valves are closed from factory and

ready for brazing. After wrapping service valve with a wet cloth,

tubing set can be brazed to service valve using either silver bearing

or non–silver bearing brazing material. Do not use soft solder

(materials which melt below 800

°

F/427

°

C). Consult local code

requirements. Refrigerant tubing and indoor coil are now ready for

leak testing. This check should include all field and factory joints.

NOTE

: Some outdoor units contain a mechanical fitting at the

liquid distributor. This connection is not field serviceable and

should not be disturbed.

A05226

Fig. 4 -- Liquid Service Valve

25H

B

B

/25H

B

C

/25H

C

D

Always Ask For

Summary of Contents for Comfort 25HBB series

Page 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Page 2: ...piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remain...

Page 3: ...for accessory requirements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere...

Page 4: ...braze liquid refrigerant tube to the filter drier A05227 Fig 6 Liquid Line Filter Drier CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation I...

Page 5: ...0010 Fig 9 3 Phase Monitor Control Applies to 3 Phase Units Only Table 3 3 Phase Monitor LED Indicators LED STATUS OFF No call for compressor operation FLASHING Reversed phase ON Normal Connect Contro...

Page 6: ...starting indoor blower motor on high speed When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors should stop NOTE If indoor unit is equipped wi...

Page 7: ...lowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system Refer to Table 5 or 6 for additional subcooling required If the indoor temperature is above 80_...

Page 8: ...item 6 and suction pressure At this intersection note suction line temperature 8 If unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is rea...

Page 9: ...5 3 CAP 30 A 3 CNP 30 A 3 3 CSPH 3012A 3 3 FB4CNF030 TXV 3 FF1ENP030 3 FF1ENP031 3 FX4DN B F 031 5 5 CAP 36 A 5 3 CNP 36 A 3 CSPH 3612A 5 3 FB4CNF036 TXV FV4C FE4A N B F 003 5 5 3 FF1ENP036 5 3 FF1ENP...

Page 10: ...4C FE4A NF002 3 FX4DNF025 CAP 30 A CNP 30 A CSPH 3012A FB4CNF030 TXV FF1ENP030 FF1ENP031 FX4DN B F 031 3 CAP 36 A CNP 36 A CSPH 3612A FB4CNF036 TXV FV4C FE4A N B F 003 FF1ENP036 FF1ENP037 FX4DN B F 03...

Page 11: ...22 23 23 23 23 65 3 7 12 18 19 21 21 22 22 70 7 14 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3...

Page 12: ...ide with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Reviews: