background image

7

OUTDOOR FAN

RELAY

Y OUTPUT TO PRESSURE

SWITCHES AND CONTACTOR

THERMOSTAT INPUTS

T1 - ENABLES DEFROST  
       TIMER.MUST BE  
       ENERGIZED FOR  
       DEFROST TIMER  
       TO START 

C - COMMON

O - REVERSING VALVE

SPEEDUP

HK32EA001

DEFROST  THERMOSTAT

MUST BE CLOSED BEFORE

DEFROST TIMER BEGINS

A05332

Fig. 11 -- Defrost Control

Table 4 – Defrost Control Speedup–Timing Sequence

PARAMETER

MINIMUM

(MINUTES)

MAXIMUM

(MINUTES)

SPEEDUP

(NOMINAL)

30–minute cycle

27

33

7 sec

50–minute cycle

45

55

12 sec

90–minute cycle

81

99

21 sec

10–minute cycle

9

11

2 sec

5 minutes

4.5

5.5

1 sec

Check Charge

Factory charge amount and desired subcooling are shown on unit
rating plate. Additional subcooling may be required to achieve

optimal heating performance based on the installed indoor unit.
(see Table 5 or 6).
Charging method is shown on information plate inside unit. For

TXV, use subcooling method. For piston, use superheat method.
To properly check or adjust charge, conditions must be favorable

for subcooling or superheat charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line

above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by super heat method for fixed
metering device and subcooling method for TXV. If any

adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly

charged system. Refer to Table 5 or 6 for additional subcooling

required.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.

If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Residential Piping and Long
Line Guideline for special charging requirements.

Units with Cooling Mode TXV

Units installed with cooling mode TXV require charging by the

subcooling method.

1. Operate unit a minimum of 10 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accur-

ate gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid line near
outdoor coil.

4. Refer to unit rating plate for required subcooling temperat-

ure.

5. Refer to Table 7. Find the point where required subcooling

temperature intersects measured liquid service valve pres-
sure.

6. To obtain required subcooling temperature at a specific li-

quid line pressure, add refrigerant if liquid line temperature
is higher than indicated or reclaim refrigerant if temperature
is lower. Allow a tolerance of

3

_

F.

25H

B

B

/25H

B

C

/25H

C

D

Summary of Contents for Comfort 25HBB series

Page 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Page 2: ...piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remain...

Page 3: ...for accessory requirements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere...

Page 4: ...braze liquid refrigerant tube to the filter drier A05227 Fig 6 Liquid Line Filter Drier CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation I...

Page 5: ...0010 Fig 9 3 Phase Monitor Control Applies to 3 Phase Units Only Table 3 3 Phase Monitor LED Indicators LED STATUS OFF No call for compressor operation FLASHING Reversed phase ON Normal Connect Contro...

Page 6: ...starting indoor blower motor on high speed When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors should stop NOTE If indoor unit is equipped wi...

Page 7: ...lowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system Refer to Table 5 or 6 for additional subcooling required If the indoor temperature is above 80_...

Page 8: ...item 6 and suction pressure At this intersection note suction line temperature 8 If unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is rea...

Page 9: ...5 3 CAP 30 A 3 CNP 30 A 3 3 CSPH 3012A 3 3 FB4CNF030 TXV 3 FF1ENP030 3 FF1ENP031 3 FX4DN B F 031 5 5 CAP 36 A 5 3 CNP 36 A 3 CSPH 3612A 5 3 FB4CNF036 TXV FV4C FE4A N B F 003 5 5 3 FF1ENP036 5 3 FF1ENP...

Page 10: ...4C FE4A NF002 3 FX4DNF025 CAP 30 A CNP 30 A CSPH 3012A FB4CNF030 TXV FF1ENP030 FF1ENP031 FX4DN B F 031 3 CAP 36 A CNP 36 A CSPH 3612A FB4CNF036 TXV FV4C FE4A N B F 003 FF1ENP036 FF1ENP037 FX4DN B F 03...

Page 11: ...22 23 23 23 23 65 3 7 12 18 19 21 21 22 22 70 7 14 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3...

Page 12: ...ide with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Reviews: