background image

5

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
Do not supply power to unit with compressor terminal box

cover removed.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440–14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit
control box.

Connect Ground and Power Wires

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 8.

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 8 -- Line Connections

A00010

Fig. 9 -- 3–Phase Monitor Control

(Applies to 3–Phase Units Only)

Table 3 – 3–Phase Monitor LED Indicators

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

Connect Control Wiring

Route 24v control wires through control wiring grommet and

connect leads to control wiring. See Thermostat Installation
Instructions for wiring specific unit combinations. (See Fig. 10.)
Use No. 18 AWG color–coded, insulated (35

°

C minimum) wire. If

thermostat is located more than 100 ft (30.5 m) from unit, as
measured along the control voltage wires, use No. 16 AWG

color–coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

24 VAC HOT

R

C

W2

Y

G

R

C

RVS COOLING

C

W2

HP THERMOSTAT

 TYPICAL

FAN COIL

HEAT 

PUMP

G

O

E

W2

E

W3

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT

STAGE 1

INDOOR FAN

EMERGENCY

HEAT

O

*
*
*

 IF AVAILABLE

*

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

  

SHR

  

EHR

  

ODT

A02325 / A97413

Fig. 10 -- Generic Wiring Diagrams

(See thermostat Installation Instructions

for specific unit combinations)

25H

B

B

/25H

B

C

/25H

C

D

Summary of Contents for Comfort 25HBB series

Page 1: ...th a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testi...

Page 2: ...piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and 12 in 304 8 mm on all remain...

Page 3: ...for accessory requirements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere...

Page 4: ...braze liquid refrigerant tube to the filter drier A05227 Fig 6 Liquid Line Filter Drier CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation I...

Page 5: ...0010 Fig 9 3 Phase Monitor Control Applies to 3 Phase Units Only Table 3 3 Phase Monitor LED Indicators LED STATUS OFF No call for compressor operation FLASHING Reversed phase ON Normal Connect Contro...

Page 6: ...starting indoor blower motor on high speed When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors should stop NOTE If indoor unit is equipped wi...

Page 7: ...lowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system Refer to Table 5 or 6 for additional subcooling required If the indoor temperature is above 80_...

Page 8: ...item 6 and suction pressure At this intersection note suction line temperature 8 If unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is rea...

Page 9: ...5 3 CAP 30 A 3 CNP 30 A 3 3 CSPH 3012A 3 3 FB4CNF030 TXV 3 FF1ENP030 3 FF1ENP031 3 FX4DN B F 031 5 5 CAP 36 A 5 3 CNP 36 A 3 CSPH 3612A 5 3 FB4CNF036 TXV FV4C FE4A N B F 003 5 5 3 FF1ENP036 5 3 FF1ENP...

Page 10: ...4C FE4A NF002 3 FX4DNF025 CAP 30 A CNP 30 A CSPH 3012A FB4CNF030 TXV FF1ENP030 FF1ENP031 FX4DN B F 031 3 CAP 36 A CNP 36 A CSPH 3612A FB4CNF036 TXV FV4C FE4A N B F 003 FF1ENP036 FF1ENP037 FX4DN B F 03...

Page 11: ...22 23 23 23 23 65 3 7 12 18 19 21 21 22 22 70 7 14 16 18 20 20 20 75 3 11 13 16 18 18 19 82 6 8 12 15 16 17 85 4 7 11 14 15 16 90 4 8 12 14 15 95 6 10 12 14 100 4 8 11 12 105 3 6 9 11 110 5 7 10 115 3...

Page 12: ...ide with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE...

Reviews: