SELF DIAGNOSTIC FUNCTION FOR MALFUNCTIONS DETECTION
The electronic printed circuit board in the outdoor unit is equipped with
smart self diagnostic.
When the system is on and in a malfunction, Leds Status of Printed Circuit Board will
refer to malfunction reason for easy fast service and maintenance.
Leds Status of Printed Circuit Board ( PCB ) of Side Discharge Outdoor Unit
Model 38KDMT12N-718
No.
Malfunction Reason
LED ( red )
1
Indoor and Outdoor communication malfunction
flash 5 times
2
Normal operation
on
Leds status of Printed Circuit Board ( PCB ) of Side Discharge Outdoor Units
Models 38KDMT18N-718 & 38KDMT24N-718 & 38KDMT30N-718
No.
Malfunction Reason
LED ( red )
1
Indoor and Outdoor communication malfunction
flash 5 times
2
Outdoor coil temperature sensor ( open or short circuit )
flash 2 times
3
Normal operation
on
Leds status of Printed Circuit Board ( PCB ) of Top Discharge Outdoor Unit
Model 38KDMT36N-718T
No.
Malfunction Reason
LED 2 ( green ) LED 3 ( yellow )
LED 4 ( red )
1
Normal operation
on
off
off
2
Stand by
off
on
off
3
Communication error
off
flash
flash
4
High pressure protection
flash
flash
off
5
Low pressure protection
flash
off
flash
Leds status of Printed Circuit Board ( PCB ) of Top Discharge Outdoor Units
Models 38KDHT42N-518T & 38KDHT48N-518T & 38KDHT60N-518T
No.
Malfunction Reason
LED 2 ( green ) LED 3 ( yellow )
LED 4 ( red )
1
Normal operation
on
off
off
2
Stand by
off
on
off
3
Default phase
off
off
flash
4
Phase sequence error
off
flash
off
5
Communication error
off
flash
flash
6
High pressure protection
flash
flash
off
7
Low pressure protection
flash
off
flash
8
Disconnect suction pipe
sensor
compressor
on
off
on
9
Outdoor temperature sensor
flash
off
off
10
Outdoor coil temperature sensor
off
off
on
11
Do not install plug CN2
off
off
flash
Error code status of Printed Circuit Board ( PCB ) of Top Discharge Outdoor Unit
Model 38KDHT72N-518T
No.
Malfunction Reason
Error Code
1
Phase reversal error or phase loss
E1
2
Power Error
E4
3
Outdoor coil temperature sensor ( open or short circuit )
E5
4
High pressure protection
P0
5
Low pressure protection
P1
6
Current Protection
P4
7
Outdoor coil temperature sensor ( Failure )
P6
8
COOL Run
oN
NOTES
1-
Prior to the malfunction repair, disconnect the electrical mains supply by moving the circuit breaker to OFF position.
2-
After repairing the malfunction, connect the electrical main supply by moving the circuit breaker to ON position
and operate the air conditioner by using wired room controller.