68
CONNECTING ELECTRICAL WIRING
21-3 ELECTRICAL DATA
Split
System
Starting
Current
(Note 1)
System
Power
Supply
Electrical Consumption
Circuit
Breaker
Cooling
Model
35 °C
*
43 °C
**
46 °C
***
52 °C
****
Cool Only
Amp
V/Ph/Hz
Amp
Watt
Amp
Watt
Amp
Watt
Amp
Watt
Amp
53KDMT12N-718
30
220-240 / 1 / 50 4.7
1105
5.3
1235
5.6
1285
6.1
1383
16
53KDMT18N-718
44
220-240 / 1 / 50 6.6
1475
7.5
1690
7.9
1771
8.6
1952
20
53KDMT24N-718
57
220-240 / 1 / 50 9.0
1977 10.2 2275 10.7 2387 11.6 2611
25
53KDMT30N-718
85
220-240 / 1 / 50 14.9 3075 16.5 3503 17.1 3662 18.3 3980
32
53KDMT36N-718T
100
220-240 / 1 / 50 13.8 3080 16.3 3659 17.2 3876 19.0 4310
40
53KDHT42N-518T
45
380-420 / 3 / 50 5.4
3217
6.3
3801
6.6
4020
7.2
4458
25
53KDHT48N-518T
60
380-420 / 3 / 50 7.0
4065
7.9
4658
8.3
4879
9.0
5323
25
53KDHT60N-518T
66
380-420 / 3 / 50 8.4
4915
9.5
5540
9.9
5913 10.7 6454
25
53KDHT72N-518T
78
380-420 / 3 / 50 10.1 5840 10.4 6525
8.5
7209 12.6 7500
25
NOTES
1. Starting Current duration is usually less than 1 Second.
2. Operating Conditions.
* @ 35ºC db outdoor temperature :
27/19ºC db/wb Indoor Temperature. High air flow of indoor unit
** @ 43ºC db outdoor temperature :
27/19ºC db/wb Indoor Temperature. High air flow of indoor unit
*** @ 46ºC db outdoor temperature :
29/19ºC db/wb Indoor Temperature. High air flow of indoor unit
**** @ 52ºC db outdoor temperature :
32/23ºC db/wb Indoor Temperature. High air flow of indoor unit
Summary of Contents for ClassiCool 53KDMT12N-718