4.4 - Optional filter and filter access

4.4.1 - Description

The Carrier unit is fitted  with G3 filter as standard (85% 

gravimetrie filter) or G4 filter as option, according to 

standard EN 779. Medium fire rating M1, metal wire 

frame.

Different filter access are available:

• 

Unit with non-ducted return air: Access is from the 

rear of the unit.

•   Unit with ducted return air: Access is from below.

4.4.2 - Air filter replacement

Air filters should be changed regularly. Filter life depends on 

the rate at which the filter becomes clogged, which depends 

upon the cleanliness of the working environment.

If clogged filters are not changed they can increase the air 

pressure drop, trapped dust particles may be given off and 

entrained in the air supply, and the general performance of 

the unit may be degraded (as the air flow reduces).

NOTE: When installing a unit in a ceiling void, check 

that no T-bars will obstruct filter access and removal.

4.5 - Fresh air controller

4.5.1 - Fresh air controller with constant air volume

The 42EM unit can be fitted with a constant fresh air flow 

controller, fixed at 8.5 l/s (30 m

3

/h) or adjustable from 17 l/s 

(60 m

3

/h) to 44 l/s (160 m

3

/h) to allow contol of the 

introduction of fresh air and of the air change rate. 

Controllers with adjustable fresh air flow:

The diameter of the spigot housing the fresh air flow 

controller is 125 mm.

The fresh air controller may be modified on site by relocating 

or removing two plastic restrictors in order to change the 

maximum constant fresh air flow of 17 1/s (60 m

3

/h) to 44 1/s 

(160 m

3

/h). A label on the 42EM shows how to adjust the 

two plastic restrictors

 (Fig. 11).

Modification procedure

• 

 Disconnect the fresh air duct from the spigot on the 

unit.

• 

 Remove or reposition the two plastic restrictors, 

following the fresh air flow controller.

• 

 Reconnect the fresh air duct to the spigot.

IMPORTANT: If the unit is fitted with a return air 

temperature sensor, the constant fresh air flow rate must 

not exceed 50% of the supply air flow delivered by the 

unit at minimum speed.

NOTE: To operate correctly, the 8.5 l/s (30 m

3

/h) the 

constant fresh air flow controller requires a differential 

pressure in the range of 50 Pa to 200 Pa. The controller with 

adjustable fresh air flow from 17 l/s (60 m

3

/h) to 44 l/s 

(160 m

3

/h) requires a differential pressure in the range of 

70 to 200 Pa.

4.5.2 - Fresh air controller with variable air volume

The 42EM unit can be equipped with an optional variable 

fresh air flow controller from 0 to 55 l/s (0 to 200 m

3

/h).

This is connected to the numeric Carrier controller and can 

regulate the fresh air intake in two ways:

• 

Either using a fixed rate set by the installer that can be 

reconfigured as required

• 

Or based on the CO

2

 level; in this case it is connected 

to a CO

2

 sensor via the Carrier numeric controller (the 

CO

2

 sensor is located opposite the fresh air inlet).

NOTE: With the variable fresh air flow controller the 

upstream pressure in the fresh air duct must be 180 Pa.

4.6 - Optional water flow control valves

These valves are either two-way or four-way type (three-

way with integral bypass). The body of the valve is designed 

to withstand a 16 bar operating pressure.

With this option, the couple (valve + actuator) is usually 

normally closed (NC).Thus, the water flow is null in case of 

power cut. To fill the installation, to equalise the water 

circuits and to purge the units, the actuators must be 

connected to the power supply and the valves must be 

opened via the controller (thermostats or BMS).

For the replacement of these components refer to the 

chapter ‘‘4.6.3. - Actuator replacement procedure’’.

4.6.1 -  230 V - Actuators

Two types of valve actuators are provided : electrothermal 

actuator (on/off control) or modulating actuator (3-point).

The actuator supply is 230 V a.c.

4.6.2. 24 V - Actuators

Three types of valve actuators are provided : one 

electrothermal actuator (on/off control) or two modulating 

actuators (3-point or 0-10V).

Both modulating actuators can be operated manually with a 

hexagonal key.  The 0-10V command voltage range of the 

modulating actuator can also be adjusted.

The actuator supply is 24 V a.c. 

NOTE: 24V actuators are not compatible with Carrier 

controllers (Thermostats A/B/C/D, HDB & NTC).

4.6.3 - Actuator replacement procedure

The actuators on both the chilled water and the hot water 

valves may be replaced if either develops a fault.

WARNING : Do not connect on the same neutral wire the 

valve actuator 24 Vac and the controller.

Summary of Contents for Atmosphera 42EM series

Page 1: ...42EM Original document Ducted fan coil units INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...he control of the unit 10 2 5 Conformity 10 3 INSTALLATION OF THE UNIT 10 3 1 Installing the unit in the false ceiling 10 3 2 Installation procedure 10 3 3 Removal procedure 11 4 COMPONENTS 11 4 1 Fan...

Page 3: ...M T0 250 680 250 42EM T1 250 830 250 42EM T2 250 1250 250 42EM T3 250 1250 250 8 10a 10a 1 2 3 4 1 2 3 4 4 3 2 1 4 3 2 1 A B 11 l s m3 h A B MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR...

Page 4: ...4 13 14 17 12a 12b 12c 14a 16a 16b 17a 17a 12 16 Hg Cg N N N L L 1 2 3 4 5 6 15 15b 15a 14b 14c...

Page 5: ...5 32 33 34 28 22 23 24 25 26 27 29 30 31 23 24 20 21 41 42 22 35 36 40 39 38 37 22 L N V3 V2 V1 N 18 19 20 21 28 22 23 24 25 26 27 20 21 22 6 5 4 3 2 1 L 7 6 5 4 3 2 1 L...

Page 6: ...6 81 40 250 18 81 40 250 18 G 1 2 G 1 2 4 w V 2 w V 23 42EM Out In In Out 1 2a 3a 1 2b 3b 1 2c 3c 24a 24b 24c 24...

Page 7: ...7 26 25 27a 27b 27c 27d 27e 27f 27...

Page 8: ...27 Changeover sensor brown wire 28 Relay 29 Very high speed 1 black wire 30 Medium speed 3 red wire 31 Low speed 5 green wire 32 Very low speed 6 purple wire 33 Medium speed 4 orange wire 34 High spee...

Page 9: ...o the shipping company Do not unpack the units until just before they are due to be installed and make sure they are as close as possible to the installation site when unpacking them Do not place heav...

Page 10: ...ct heavy inductive loads to the same electrical supply circuit breaker used by the controllers power modules or speed controllers Use the screened cable type recommended by Carrier and make sure all c...

Page 11: ...ng the gas connectors WARNING Since the flexible water pipes do not have drain valves a receiver must be provided to allow the cooling coil to be drained Disconnect the supply air ducts Disconnect the...

Page 12: ...pply to the unit before carrying out any work on the unit Close the isolating valves on the manifolds Unscrew the union nuts to disconnect the flexible water pipes Remove the valve actuators taking ca...

Page 13: ...ller requires a differential pressure in the range of 50 Pa to 200 Pa The controller with adjustable fresh air flow from 17 l s 60 m3 h to 44 l s 160 m3 h requires a differential pressure in the range...

Page 14: ...em Check that there are no leaks and reconnect the power to the unit WARNING When replacing a valve always ensure that the direction of flow through the valve is as shown by the arrow on the valve bod...

Page 15: ...spigots and 2 supply air spigots V Compact unit with 3 return air spigots and 3 supply air spigots NOTE Terminal 1 highest speed Terminal 6 lowest speed Fan set Codification last digit or option 600 R...

Page 16: ...nt certification com www certiflash com Order No 14226 01 2015 Supersedes order No 14226 11 2014 Printed in the European Union Manufacturer reserves the right to change any product specifications with...

Reviews: