background image

12

English

The three speeds are connected to a five-pole Wego  

connector - see Fig. 18.

Speed wiring modification 

ON a unit supplied with bare wires, the speeds are pre-

wired at the factory, as ordered.

 

To modify the wiring, change the speeds at the auto-

transformer inside the unit. See Fig. 14. 

4.1.3.2 - Multi-speeds unit with fast connector option - 6 
speeds wired

This option enables to get six speeds from the AC fan 

motor available through a fast connector. Refer to Fig. 22.

4.1.3.3 - Multi-speeds unit with control box option

This option allows the installer to connect the unit to a 

terminal board inside a control box. To comply with the 

applicable regulations, the control box can be opened with 

a screw driver. 

Three of the available six speeds are connected - the 

default factory wiring is 5-3-1 (minimum speed = 6, 

maximum speed =1).

The control box option permits changing the speed wiring 

without access to the motor. See Fig. 20.

4.1.3.4 - Variable-speed bare-wire LEC unit

Connection of the 230 V a.c. fan motor power supply is at a 

three-point Fast connector. Connection of the 0-10 V d.c. 

control signal is at a two-point Fast connector. See Fig. 19.

4.1.3.5 - Variable-speed LEC unit with control box option

This option allows the installer to connect the unit to a 

terminal board inside a control box. To comply with the 

applicable regulations, the control box can be opened with 

a screw driver.

The 0-10 V d.c. signal that controls the variable fan speed 

is directly accessible at the terminal board. See Fig. 21. 

4.1.4 - Wiring precautions during replacement of a fan 
motor on sizes 22, 23, 32, 33 with a.c. motor

During replacement of the a.c. fan motor, the installer 

must wire the speeds in accordance with the instructions in 

the table below:

Wiring for 42EM 22 and 42EM 32: Fig. 16

42EM sizes 22 and 32

Neutral (com)

1

White

Phase connected 2

Red

Wiring legend:

Minimum speed  = Terminal 6

Medium speed  = Grey wire (14b)

Maximum speed  = Terminal 1

High speed 

= Black wire (14c)

Low speed 

= Red wire (14a)

L  

Neutral 

Wiring for 42EM 23 and 42EM 33: See Fig. 27.

4.2 - Water coil

4.2.1 - Coil removal procedure

WARNING: Disconnect the power supply to the unit before 

carrying out any work on the unit.

• 

Close the isolating valves on the manifolds.

• 

Unscrew the union nuts to disconnect the flexible 

water pipes.

• 

Remove the valve actuators taking care to identify the 

cooling and heating valves.

• 

Disconnect the flexible condensate drain pipe held in 

place by a collar (the collar is not supplied by Carrier).

• 

Remove the two-way or four-way water flow control 

valve bodies. Depending on the unit configura-tion the 

four-way valve coupling may be fitted with a heating/

cooling changeover switch. If so, do not remove it.

• 

Loosen the four fixing screws (4 torx screws (T20)). 

Pull out the drain pan and coil assembly (the drain pan 

remains attached to the unit for approximately 100 mm) 

until the coil is completely detached. Then remove the 

coil from the drain pan.

• 

Replacement is by the reversal of the procedure des-

cribed above. Ensure that all gaskets are changed (new 

gaskets fitted) and that the inlet and outlet connections 

to the coil are made correctly using an appropriate 

sealing compound applied to the valve body.

• 

Bleed all air from the coil during refilling.

ATTENTION: Take care when tightening the valve body to 

the coils (15 N·m is sufficient) to ensure they are not 

damaged.

NOTE: The coil connection can be changed on site by 

changing the condensate pan and coil assembly in the guides.

For size 3 the water inlet and outlet need to be reversed to 

achieve the published performance.

4.2.2 - Coil inlet/outlet and cooling/heating side positions

Water inlets/outlets, all sizes : Fig. 23.

Coil drawing with cooling and heating side position: Fig 24.

ATTENTION: Carefully observe the direction indicated 

by the arrow on the valves, based on the valve type.

4.3 - Duct connection spigots

These are manufactured from high density plastic with a 

VO fire rating, more or less equivalent to class M1 (French 

standard). They are encased inside the unit. The ducts 

should be fixed to these spigots using circular collars or 

adhesive. Screws and rivets should not be used.

WARNING: In order to guarantee good air tightness, the 

duct should overlap the whole of the spigot.

Make sure that the maximum supply air temperature does 

not exceed 60°C.

 

Do not lift or support the unit using the spigots, place loads 

on the spigots or damage the spigots during installation or 

operation.

Summary of Contents for Atmosphera 42EM series

Page 1: ...42EM Original document Ducted fan coil units INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS...

Page 2: ...he control of the unit 10 2 5 Conformity 10 3 INSTALLATION OF THE UNIT 10 3 1 Installing the unit in the false ceiling 10 3 2 Installation procedure 10 3 3 Removal procedure 11 4 COMPONENTS 11 4 1 Fan...

Page 3: ...M T0 250 680 250 42EM T1 250 830 250 42EM T2 250 1250 250 42EM T3 250 1250 250 8 10a 10a 1 2 3 4 1 2 3 4 4 3 2 1 4 3 2 1 A B 11 l s m3 h A B MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR...

Page 4: ...4 13 14 17 12a 12b 12c 14a 16a 16b 17a 17a 12 16 Hg Cg N N N L L 1 2 3 4 5 6 15 15b 15a 14b 14c...

Page 5: ...5 32 33 34 28 22 23 24 25 26 27 29 30 31 23 24 20 21 41 42 22 35 36 40 39 38 37 22 L N V3 V2 V1 N 18 19 20 21 28 22 23 24 25 26 27 20 21 22 6 5 4 3 2 1 L 7 6 5 4 3 2 1 L...

Page 6: ...6 81 40 250 18 81 40 250 18 G 1 2 G 1 2 4 w V 2 w V 23 42EM Out In In Out 1 2a 3a 1 2b 3b 1 2c 3c 24a 24b 24c 24...

Page 7: ...7 26 25 27a 27b 27c 27d 27e 27f 27...

Page 8: ...27 Changeover sensor brown wire 28 Relay 29 Very high speed 1 black wire 30 Medium speed 3 red wire 31 Low speed 5 green wire 32 Very low speed 6 purple wire 33 Medium speed 4 orange wire 34 High spee...

Page 9: ...o the shipping company Do not unpack the units until just before they are due to be installed and make sure they are as close as possible to the installation site when unpacking them Do not place heav...

Page 10: ...ct heavy inductive loads to the same electrical supply circuit breaker used by the controllers power modules or speed controllers Use the screened cable type recommended by Carrier and make sure all c...

Page 11: ...ng the gas connectors WARNING Since the flexible water pipes do not have drain valves a receiver must be provided to allow the cooling coil to be drained Disconnect the supply air ducts Disconnect the...

Page 12: ...pply to the unit before carrying out any work on the unit Close the isolating valves on the manifolds Unscrew the union nuts to disconnect the flexible water pipes Remove the valve actuators taking ca...

Page 13: ...ller requires a differential pressure in the range of 50 Pa to 200 Pa The controller with adjustable fresh air flow from 17 l s 60 m3 h to 44 l s 160 m3 h requires a differential pressure in the range...

Page 14: ...em Check that there are no leaks and reconnect the power to the unit WARNING When replacing a valve always ensure that the direction of flow through the valve is as shown by the arrow on the valve bod...

Page 15: ...spigots and 2 supply air spigots V Compact unit with 3 return air spigots and 3 supply air spigots NOTE Terminal 1 highest speed Terminal 6 lowest speed Fan set Codification last digit or option 600 R...

Page 16: ...nt certification com www certiflash com Order No 14226 01 2015 Supersedes order No 14226 11 2014 Printed in the European Union Manufacturer reserves the right to change any product specifications with...

Reviews: