28
30XBP 850 to 1500
30XBP
850
900
1000
1100
1200
1300
1400
1500
Sound levels
Standard unit
Sound power
(1)
dB(A)
101
104
102
103
102
104
104
104
Sound pressure at 10 m
(2)
dB(A)
70
71
69
70
69
71
71
71
Unit + option 15
(3)
Sound power
(1)
dB(A)
97
99
98
98
98
100
99
99
Sound pressure at 10 m
(2)
dB(A)
65
66
65
65
65
67
65
65
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
94
95
94
94
94
99
95
96
Sound pressure at 10 m
(2)
dB(A)
61
62
61
61
61
66
62
63
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
91
93
92
93
93
97
94
95
Sound pressure at 10 m
(2)
dB(A)
58
60
59
60
60
66
61
62
Dimensions
Standard unit
Length
mm
8380
8380
9574
11962
11962
11962
11962
13157
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2322
2322
2322
2322
2322
2322
2322
2322
Operating weight
(4)
Standard unit
kg
5795
6080
6561
7812
7949
8565
8640
8941
Unit + option 15
(3)
kg
6126
6411
6892
8183
8320
8939
9014
9315
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
75
72
79
82
84
115
121
124
teqCO
2
107,3
103,0
113,0
117,3
120,1
164,5
173,0
177,3
Circuit B
kg
67
74
83
118
130
121
127
130
teqCO
2
95,8
105,8
118,7
168,7
185,9
173,0
181,6
185,9
Oil
Circuit A
l
27,6
27,6
27,6
27,6
27,6
36,0
36,0
36,0
Circuit B
l
23,5
27,6
27,6
36,0
36,0
36,0
36,0
36,0
(1) In dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS