44
30XB from 1100 to 1700 with option 254 or 255
30XB with option 254 or 255
1100
1200
1300
1400
1500
1550
1700
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
- 30XB
Standard unit
Circuit 1
(a)
kW
194
223
263
283
307
445
363
Circuit 2
(a)
kW
284
309
281
304
307
223
363
Option 081
kW
478
531
544
587
613
-
-
Unit + option 15LS
Circuit 1
(a)
kW
188
217
254
274
296
431
350
Circuit 2
(a)
kW
276
298
272
295
296
215
350
Option 081
kW
464
515
526
568
592
-
-
Power factor at maximum power
(1)
- 30XB
Standard unit
Displacement Power Factor (Cos Phi)
0,87
0,87
0,87
0,87
0,87
0,87
0,88
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,87
0,87
0,87
0,87
0,87
0,87
0,88
Nominal operating current draw
(2)
- 30XB
Standard unit
Circuit 1
(a)
A
255
271
340
353
389
542
447
Circuit 2
(a)
A
357
392
353
385
389
271
447
Option 081
A
611
663
692
737
777
-
-
Unit + option 15LS
Circuit 1(
a)
A
245
261
324
337
372
518
425
Circuit 2
(a)
A
343
375
337
369
372
259
425
Option 081
A
587
636
661
706
743
Maximum operating current draw (Un)
(1)
- 30XB
Standard unit
Circuit 1
(a)
A
322
368
438
468
507
736
598
Circuit 2
(a)
A
472
510
468
503
507
368
598
Option 081
A
793
878
905
970
1013
Unit + option 15LS
Circuit 1
(a)
A
312
358
422
452
490
712
576
Circuit 2
(a)
A
458
493
452
487
490
356
576
Option 081
A
769
851
874
939
979
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS