19
30XB
250
300
350
400
450
500
600
700
750
800
Capacity control
SmartVu
TM
, Electronic Expansion Valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
15
15
Air heat exchanger
Aluminum micro-channel coils (MCHE)
Fans
FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity
6
6
6
8
8
8
11
12
12
12
Maximum total air flow
l/s
28920 28920 28920 38560 38560 38560 53020 57840 57840 57840
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
Unit + option 15LS
Maximum total air flow
l/s
23580 23580 23580 31440 31440 31440 43230 47160 47160 47160
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Water heat exchanger
Flooded multi-pipe type
Water volume
l
58
61
61
66
70
77
79
94
98
119
Max. water-side operating pressure without hydraulic
module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve,
pressure sensors, expansion tank (option)
Pump
Centrifugal pump, monocell, 48,3r/s, low or high pressure (as required),
single or dual (as required)
Expansion vessel volume
l
50
50
50
50
50
80
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
Water connections without or with hydraulic module
Victaulic
®
type
Standard & option 8, without option 116
Nominal diameter
in
5
5
5
5
5
5
5
6
6
6
Actual outside diameter
mm
141,3 141,3 141,3 141,3 141,3 141,3 141,3 168,3 168,3 168,3
Options 5, 6 et 100A
Nominal diameter
in
4
4
4
4
4
4
5
5
5
5
Actual outside diameter
mm
114,3 114,3 114,3 114,3 114,3 114,3 141,3 141,3 141,3 141,3
Options 100C
Nominal diameter
in
5
5
5
5
5
5
6
6
6
6
Actual outside diameter
mm
141,3 141,3 141,3 141,3 141,3 141,3 168,3 168,3 168,3 168,3
Options 116
Nominal diameter
in
4
4
4
4
4
4
-
-
-
-
Actual outside diameter
mm
114,3 114,3 114,3 114,3 114,3 114,3
-
-
-
-
Casing paint
Colour code RAL 7035
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS